Monthly Operating Repts for Feb 1983
ML20069B380
Person / Time
Site: Point Beach  
Issue date: 03/07/1983
From: Fay C
WISCONSIN ELECTRIC POWER CO.
To:
Shared Package
ML20069B352 List:
References
NUDOCS 8303160577
Download: ML20069B380 (7)


Text

_ _ _ _ - _ _ _ _ _ _ _ _ _ _ - _ - _ _ _. - _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _

201s tD g

E8u 3

C&

@hl CPERATING DATA REPORT A;j DCCKET NO. 50-266 0

DATE March 7, 1983 oo ou 1D u e-COnPLEYED BY C. W. FA) 000

0 0-TELEPHONE 414 277 :811 0FEciiING STATUS
1. UNIT NAME: POINT SEACH NUCLEAR PLANT UNIT 1

. NOTES

2. REPORTING FERIOD: FEBRUARY 1983
3. LICENSED THERHAL POWER (nWT):

1518.

4. NAMEFLATE R4 TING (GkOSS MWE):

523.8

5. DESIGN ELECTRICAL RATING (HET MWE):

497.

6. MAXIhUM DEPENDABLE CAPACITY (GROSS MWE): 519.
7. MAXInUh DEPENDABLE CAPACITY (NET MWE):

495.

8..IF CHANGES OCCUR IN CAPACITY RATINGS (ITEN3 NUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REAS9NS:

NOT APPLICABLE

9. POWER LEVEL 10 UHICH RESTRICTED, IF ANY INET nWE):

390.0

10. REASONS FOR RESTNICTIONS, (IF ANY):

Power level restricted because of self-imposed hot Icg temperature limitation in an attempt to limit steam generator tube corrosion.

THIS n0 NTH YR T6 DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD 672 1,416 107,952
12. NuhBER OF HOURS REACTOR WAS CRITICAL 672.0 1.416.0 88,988.3
13. REACTOR RESERVE SHUIDOWN HGURS 0.0 0.0 624.0
14. HOURS GENERATOR ON LINE 672.0 1,416.0 86,524.3
15. UNIT REbERVE SHUTDOWN HOURS 0.0 0.0 793.5
16. GROSS THERMAL ENERGY GENERATED (MWH) 778,703 1,648,0E3 117,597,077
17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 258,930 547,720 39.423,510
18. NET ELECTRICAL ENERGY GENERATED (HWH) 245.612 51?,680 37,501,398
19. UNii SERVICE FACTOR 100.0 100.0 80.2
20. UNIT AVAILABILITY FACTOR 100.0 100.0 80.9
21. UNIT CAPACITY FACICR (USING nDC NET:

73.8 74.1 71.1

22. UNIT CAPACITY FACTOR (USING DER NET) 73.5 73.8 69.9
23. UNIT FORCED OUTAGE RATE 0.0 0.0 2.8
24. SHUIDOWNS SCHEDULED DVER NEXT 6 MONTHS (TiPE, DAIE, AND DURATION OF EACH):

NONE

25. IF 3HUTUOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTLP: NOT SHUTDOWN DATA RE?CRTED AND FACTORS CALCULATED AS REQUESTED IN NRC LETTER DATED SEPTEMBER 22, 1977

DOCKET NO.

50-266

~

UNIT NAME Point Beach Unit 1 DATE March 7, 1983 COMPLETED BY C.

W.

Fay TELEPHONE 414/277-2811 AVERAGE DAILY UNIT POWER LEVEL MONTH February, 1983 AVERAGE AVERAGE AVERAGE DAILY DAILY DAILY POWER LEVEL POWER LEVEL POWER LEVEL DAY MWe NET DAY MWe NET DAY MWe NET 1

371 11 373 21 350 2

372 12 357 22 370 3

370 13 356 23 359 4

370 14 354 24 363 5

359 15 371 25 371 6

365 16 371 26 372 7

372 17 371 27 364 8

371 18 370 28 372 9

372 19 365 29 10 371 2d 332 30 31 AD-28A (1-77)

'i llll

!,!i!:;

t ll l1!

!;i.

j;!]

4 (A

0D 1-

- 2 N

78 o

8B

)

1 D

SF a

te SF co hr ec de a

ud ege le d

Qoyo3a

~mgu2

~

HGFEDCBAR Mogoa" e

a OOAORRMEs tp dp e e a q o h e m e g fiu n 2evjm W

U R

N e r ir u u n i:

24geBt E

I U

P n P

T ranaletp titalem

C yeRo4 O

s

( isotine R

S eotronan T

H xnr rgnt L

U paaTy c

i M

T lltr eF c

O D

a iaR a

Re N

O iEvie oi en T

W nrans rl ps H

N r

it u

oe S

)

o nr Tr re r

gi ee t

F A

c s

E e

N

&t t(

Nv b

D (e

i e

o. e r

x Lo x

n u

P p

in p

t a

O l

c l

r W

a e

a y

E i

n i

R mym?

n s

n e

e

)

)

1 RE 9

E 8

D x

U 3

a C

m T

uosyci4 I

n o

e O

3 NS 432lM e

t C

OAMMh a

tuaao Tu htnnd os eouu:

e rmaa P

all ra C

t en TO

(

eiS vd EM D

xcc e

LP UO p

r nC EL NC lSa to PE IK acm r

HT TE ir Rr OE T

na ee NDDN m

cc E

AAN

)

ut BTMO 5

4 ri YEE.

rv SE Sate ee 4

(

C. M P 5 ox Nhtix n

1 a o 0 uh U e io h cA 4

r i

ri Reoni ec

/ W c n 2

cb Etnsb t

2 h t 6

ai Gs i

i 7

6 t

oft o

7 F 7 B 0ffo n

- a e

I 1o rG 2 y a

6rD 8

1 c 1

API 1

9 h

Ltrn S

)

1 8

a Eaes 3 U m

R pt n

n Ear i

Fnru t

it c

lr 1

ey

NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE

.t Docket No.

50-266 Unit Name Point Beach Unit 1 Date March 7, 1983 Completed By C. W. Fay Telephone 414/277-2811 Unit 1 operated at approximately 371 MWe net throughout the entire reporting period with no major load reductions.

The primary-to-secondary leakage remains stable at less than 10 gallons per day.

l No safety-related maintenance was performed in conjunction with the operation of Unit 1.

i f

i 1

i t

a w

n,

-, w o - pw e,

,a

,y-n e n e e-,------...--

- ~ ~, - -

.,wc-.-r-n c---e,,--,m-

-es,-e-w.----

-y--v, 7,-,,,- - - - ---,-

w,e v,

OPERATING DATA REPORT DOCKET NO. 50-301 DATE March 7, 1983 1

COMPLETED BY C. W. FAf 1

i TELEPHONE 414 277 2811 OPERATING STATUS 1

1. UNIT NAME: POINT BEACH NUCLEAR PLANT UNIT 2

. NOTES I

2. REPORTING PERIOD: FEBRUARf 1983
3. LICENSED THERMAL POWER (HUT): 1518.
4. NAMEPLATE RATING (GROSS MWE):

523.8

5. DESIGN ELECTRICAL RATING (NET nWE):

497.

o. HAXIMUM DEPENDABLE CAPACITY (GROSS MWE): 519.
7. MAXIHun DEPENDABLE CAPACITY (NET MWE): 495.
b. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:

NOT APPLICABLE

9. F0WER LEVEL 10 UHICH RESTRICTED, IF ANY (NET MWE): NOT APPLICABLE
10. REASONS FOR RESTRICTIONS, (IF ANY): NOT APPLICABLE THIS HONTH YR TO DATE CUMULATIVE
11. HOURS IN REPORTING PERIOD 672 1,416 92,737
12. NUMBER OF HOURS REACTOR WAS CRITICAL 672.0 1,416.0 83,474.1
13. REACTOR RESERVE SAUTDOWN HOURS 0.0 0.0 196.8
14. HOURS GENERATOR ON LINE 672.0 1,416.0 82,071.2
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 181.2
16. GROSS THERMAL ENERGY GENERATED (MWH) 1,016,200 2,137,699 113,653,293

!?. GROSS ELECTRICAL ENERGY GENERATED (MWH) 341,180 716,440 38,517,840

18. NET ELECTRICAL ENERGY GENERATED (MWH) 326,812 686,211 36.675.178
19. UNIT SERVICE FACTOR 100.0 100.0 89.5
20. UNIT AVAILABILITY FACTOR 100.0 100.0 88.7
21. UNIT CAPACITY FACTOR (USING nDC NET) 98.2 97.9 80.5
22. UNIT CAPACITY FACTOR (USING DER NET) 97.9 97.5 79.6
23. UNIT FORCED OUTAGE RATE 0.0 0.0 1.5
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

Fourteen week refueling and steam generator sleeving outage scheduled to begin March 25, 1983.

25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: NOT SHUTDOWN DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC LETTER DATED SEPTEMBER 22, 1977

DOCKET NO.

50-301 UNIT NAME Point Beach Unit 2 DATE March 7, 1983 1

COMPLETED BY C.

W.

Fay TELEPHONE 414/277-2811 AVERAGE DAILY UNIT POWER LEVEL MONTH February, 1983 l

AVERAGE AVERAGE AVERAGE DAILY DAILY DAILY POWER LEVEL POWER LEVEL POWER LEVEL DAY MWe NET DAY MWe NET DAY MWe UET i

1 485 11 489 21 487 l

2 484 12 480 22 487 3

485 13 469 23 487 4

485 14 487 24 488 5

487 15 487 25 486 6

487 16 488 26 487 7

486 17 487 27 491 8

486 18 487 28 491 i

9 488 19 490 29 10 487 2d 490 30 31 AD-28A (1-77)

ob 7a Zo wm mm H

Cn tn M OO D* N 20 Type H

tD Duration (Hours)

N

O N M C O to > W Reason 1

I e i 1 i I (DA O O > O W W % M to h3 N $ $ f.$ 0 Method Of d y py C g y" Shutting 3 5

E ft P rt W H (D 9 DOwn Reactor O

- P D O tt H D (D W

(n O O rt M O D W D 8

lI:

MMN N Q U tt t4 O

T W W 8 84 O

H 8

V' H rt M G%

O O

O W

HWW W

W (D Z

O P M < P- (D OH (D D 8

E D N f) D to NH

'O fn 3:

Z wN H et d

O (D in O

DN 8N N (D h

D

$O "m

N o

a "s

e 1

M M

MO M

=D d

'O PD T

rt O

50 P-D P.

W Systeg D

m D

~*

~

Code M

O X

COmpOngnt d

)

Code y

(n AWNHX 1 1 I i (D ft O

O > % % D'

?

ft c W D O 8 s.

D' ft D D Q.

O (n (D O C C **

2 N3WW

'Il WHH MW O

$m 2

M O

MOO (D

t" C4 O

'O N

DO M td ZO H fn >

tt O

't2 M H>

DQB N

3 8 8M PN NN OM 8

DR (D (D ZOOZ w3 OO t:3 Z

c et tp 8 O

m M P-MM N<

MM

-mmWM mG u n g m m OM 27&HM D

p o o g

C D*

O tD P O D*

O>

a n

y.

g NH z m O D P-2O s g o p y

O O' M ft D rn O' rt N

. :r rt o

() P-Q (A H

H y

p I

Ome o

q q

q w ommO D

i p o

H F' O NO N.<

p 1

mNO I-m p

O M

M ND

[

R MWmm W C 3

W

'O tt p

u MWN p.

NDNd et P rt iO

r NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE Docket No.

50-301 Unit Name Point Beach Unit 2 Date March 7, 1983 Completed By C. W.

Fay Telephone 414/277-2811 Unit 2 operated at approximately 488 MWe net throughout the entire reporting period with no major load reductions.

The primary-to-secondary leakage remains stable at less.

than 10 gallons per day.

No safety-related maintenance was performed in conjunction with the operation of Unit 2.