_

'Af Telephone (412) 4564000 IoIEo'[4 IbvaTber 15, 1982 Shippingport, PA 15077 0004 United States Nuclear Ibgulatory Cmmission Office of Inspecticn and Enforcement Attn: Mr. R. C. Ilaynes, Ibgional Administrator Region I 631 Park Avenue King of Prussia, PA 19406 Ibfemrx:e :

Beaver Valley Power Station, Unit No.1 Ibcket tb. 50-334, License Ib. DPR-66 Beaver Valley Power Station Drrergency Preparedness Plan NBC Inspection ?b. 50-334/82-15 Close-out Ictter G2ntlmen:

'Ihe purpose of this letter is to inform you of actions taken in regard to items identified in section C of the inspection critique.

The problem with the sirens was largely a logistics problem. In June, the county EOC was relocated. As a result of the move, the DtrIuesne Light Carpany remote radio console had to be moved to the new location and connected by Bell telephone line back to the radio base station, which rennined at the original location. The added length resulted in an attenuation of the audio signal to a level below that required to key the radio base station. Therefore, the signal was not strong enough to activate the receivers at the siren sites.

As noted in your report the prdalem encountered with the siren system Ins been corrected. The line level of the radio base station has been turned up ensuring an adequate signal to activate the system.

'Ib ensure system operability and verify adequate transmission in the future, DtxIuesne Light Ccmpany will perform a mcnthly test verification of the control system in Colunbiana County, in addition to the scheduled testing of the siren units.

8212100041 821206 PDR ADOCK 05000334 a

PDR

r..,

'1he problem of coordination of news releases between the licensee and public information personnel in the Columbiana County EOC appears to be one that will be worked out with experience. Duquesne Light provided every news release via telecopy to the Columbiana County EOC. Also available to the Ohio Public Information Officer was an t5 dated status board of plant conditions and direct contact with the Columbiana County EOC. In the future Duquesne Light Canpany will make every effort to ensure that a coordinated and timely working relationship exists with the p2blic information personnel in the offsite EOC's.

Very truly yours, f

J. J. Carey Vice President, Nuclear cc: Mr. W. F. Troskoski, Ibsident Inspector U. S. Nuclear Ibgulatory Comnission Beaver Valley Power Station Shippingport, PA 15077 U. S. Nuclear Ibgulatory Commission c/o Document bbnaganent Branch Washington, DC 20555

.