ML20066J404

From kanterella
Jump to navigation Jump to search

Forwards Application for Amend to License NPF-3,changing TS 3/4.7.1.3 Re Plant Sys,Condensate Storage Tank & Bases 3/4.7.1.3 Re Plant Sys,Condensate Storage Facilities to Delete Ref to Deaerator Storage Tanks
ML20066J404
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 02/15/1991
From: Shelton D
CENTERIOR ENERGY
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20066J406 List:
References
1886, TAC-M79673, NUDOCS 9102260116
Download: ML20066J404 (2)


Text

-

..; e -

3 l

CENTERf0R ENERGY.

Donald C. Shelton 300 Madison Avenue

'(

Yee Pre:ident Nuclear Tokdo, OH 436520001 Davis Besse (419)2e92300

Docket Number 50-346 License Number NPF-3

. Serial Number 1886

. February 15 1991 l United States Nuclear Regulatory Commission Document Control Desk

-Vashington,-D. C.

20555 Subjec t:

License Amendment Request to Delete References to Deaerator Storage Tanks'(TAC Number M79673) s Centlement

^

The enclosed application requests that the Davis-Besse Nuclear Power LStation, Unit Number 1 Operating Licenst,: Appendix A, Technical y

Spacifications.(TS) be-revised to reflect the changes attached. The proposed changes' involve TS 3/4.7.1.3, Plant Systems, Condensate Storage Tank,-and Bases Section 3/4.7.1.3, Plant Systems, Condensate Storage Facilities.

1

The proposed changes vould delete the reference.to the Deaerator Storage
Tanks'(DSTs) as condensate storage facilities for the Auxiliary Feedvater System _in Limiting-Condition for Operation (LCO) 3.7.1.3, and would revise the nomenclature for " condensate storage tank" and " condensate storage facilities" to " Condensate Storage Tanks"~in LCO 3.7.1.3,' Surveillance-l Requirement.4.7.1.3.1,.and Bases Section 3/4.7.1.3.

These changes are being L

made to correct the TS in that the alignment'of the DSTs to the-Auxiliary

'Feedvater Pumps-(AFPs) is not allowed because=1) the high-temperature _ vater from:the DSTs can damage the AFPs' bearings, and 2)-the AFPs'-discharge i

lines _vould be considered.high energy lines. The changes.in nomenclature are being made because, with the deletion of the deaerator storage tanks,-

the only. condensate' storage facilities remaining are the condensate storage L

tanks.

4.

l ~

9102260116 910215 h

PDR ADOCK 05000346 l-P PDR opemung companies.

L Cleveland Electne muminonng g l\\

t-

> - y.G Toicdo Edison a

Docket Numb 3r 50-346 Licznsa Numb 2r NPF-3 Serial Number 1886 Page 2 Toledo Edison requests that the Nuclear Regulatory Commission Staf f issue this amendment by November 29. 1991.

If you have any questiens concerning the above, please contact Mr. R. V. Schrauder, Manager - Nuclear Licensing, at (419) 249-2366.

Very truly yours, 1

RMC/mmb cci P. H. Byron, DB-1 Senior Resident Inspector A. B. Davis, Regional Administrator, NRC Region III D. C. Di Ianni, DB-1 NRC Senior Project Manager General J. Villiams, Chief of Staff, Ohio Adjutant General's Office Utilicy Radiological Safety Board 1

-