ML20066E539

From kanterella
Jump to navigation Jump to search
Third Interim Deficiency Rept Re Inadvertent Sensitizing of Penetrations 40 & 41 While Performing post-weld Heat Treatment.Initially Reported on 820513.New Penetrations Will Be Installed by 830129.Final Rept by 830211
ML20066E539
Person / Time
Site: Waterford Entergy icon.png
Issue date: 11/05/1982
From: Maurin L
LOUISIANA POWER & LIGHT CO.
To: Jay Collins
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, W3I82-0084, W3I82-84, NUDOCS 8211150279
Download: ML20066E539 (1)


Text

4 I OUISIANA

,4a OctAnONOE Srnt a POWER & LIGHT P O UOX 6008

  • 1504) 366 2345

' T E sysVl0 November 5, 1982 S

u L V MAURIN Vce Presodent Nuclear Operations W3I82-0084 Q f k'/

I Mr. John T. Collins, Regional Administrator, Region IV i

U. S. Nuclear Regulatory Commission i vj; g b Ib8 f

611 Ryan Plaza Drive, Suite 1000

]I Arlington, Texas 76012

/

L v

l

]

SUBJECT:

Waterford SES Unit No. 3 Docket No. 50-382 j

Significant Construction Deficiency Report No. 52 "Bi-Metallic Penetration Welds, No Stress Relief" Third Interim Report

REFERENCES:

LP&L Letter W3K82-0275, Dated May 13, 1982 LP&L Letter W3182-0022, Dated August 31, 1982 l

Dear Mr. Collins:

While performing post weld heat treatment on penetrations 40 and 41, as part of the required corrective action, excessive heat was applied resulting in the sensitizing of the material. Both penetrations were therefore rejected with an engineering disposition to cut out and replace. Replacement penetrations have been received on site.

Installation of the replacement penetrations is anticipated to be completed by January 29, 1983.

l Based on the above, a Final Report vill be submitted by February 11, 1983.

Very truly yours, Acccc.sN L. V. Maurin LVM/ MAL:keh cc:

1) Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D. C.

20555

2) Director Office of Management Information and Program Control h

Washington, D. C.

20555

/

/

3)

E. Blake

/

l l

4)

W. Stevenson 8211150279 821105 PDR ADOCK 05000382 S