Text
.
Donald A. Wells Managar QuaMy Assurance (313) 237 % 57 2000 Second Avenue 31 3
Novenber 5,1982 EF2-60505 Mr. Janes G. Keppler, Regional Administrator Region III U.S. Nuclear Regulatory Ccanission 799 Roosevelt Road Glen Ellyn, Illinois 60137
Subject:
Interim Report of 10CFR50.55(e) Item on Defective Spot Welds and Power Strut Support Material (#55)
Dear Mr. Keppler:
This interim report on the defective spot welds and Power Strut support material problem has been prepared to provide the current status of this problem.
The problem was originally reported to Mr. J.E. Konklin of NRC Region III by Detroit Edison's Mr. H.A. Walker, Supervisor-Construction Quality Assur-ance, on February 11, 1982.
L.K. Cmstock (a Detroit Edison Contractor) had noted a number of problems with spot welds on ' Power Strut" type PS202 support material. This material was ordered by the site electrical contractor, L.K. Cmstock, frca the Van Huffel Tube Corporation. The problem was first noted in the field when the material separated at several of the manufacturer's spot welds. As a result, twelve samples of the " Power Strut" formed netal channels were sent to Detroit Testing Laboratory. All tw21ve pieces tested exhibited spot weld failures.
To date, approximately fifty hangers have been found with defective Power Strut support material. An investigation to locate additional defective hangers is continuing. These hangers in question will remain "On Hold" pending final dis-position by Sargent and Lundy and Edison Engineering.
Anothar report on this item, either interim or final, is scluduled to be sent on or before March 5, 1983. If you have questions corcerning this tratter, please contact Mr. G.M. Trahey, Assistant Director-Project Quality Assurance.
Very truly yours, DAW /DF/cp 8211110159 821105
~
GOV 5 1982 PDR ADOCA 05000341 S