ML20066B787

From kanterella
Jump to navigation Jump to search
Special Rept:On 901126,portion of 3 H Fire Rated Penetration Seal Between Fire Zones 2K & 5D1 Discovered Degraded for More than 7 Days.Fire Watch Established & Work Request LO3689 Initiated to Seal Gap
ML20066B787
Person / Time
Site: LaSalle 
Issue date: 12/31/1990
From: Diederich G
COMMONWEALTH EDISON CO.
To: Davis A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 9101080383
Download: ML20066B787 (1)


Text

J4N 23 '90 15 44 P.E Commonwealth Edison LtSalle County Nu0 lear StatiOS RatalRoute 41, Box 220 Mareemes,lilinois 61341 Telephone $15/357 6761 R { ['[, v, ' ;

Decesber 31, 1990

'91 Jm 18 A9:37 pygut gut.w in d ~~

~

Mt. A. E. Davis Region 111 Administrator U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 V

Dear Dir:

'This Special Report is submitted in accordance with LaSalle linit 1 Operating License, WPF-11, Appendix A, Technical Specifications 3.7.6 and 6.6.c.

On November 26, 1990 at 0900 hours0.0104 days <br />0.25 hours <br />0.00149 weeks <br />3.4245e-4 months <br />, two Technical staff Engineers discovered that a portion of a three hour fire rated penetration seal located between fire zones 2K and 501 was degraded. A gap existed between the wall and the ceiling due to degraded silicone foam.

In accordance with action statement "a" of Technical Specification 3.7.6, an hourly fire watch patrol was established to inspect the affected fire zone and eppropriate fire detectors were determined to be operable. This will continue l

until the seal is repaired.

The p netration seal for this fire zone was inoperable in excess of the allowed seven (7) days prior to requiring a Special Report because the, work could not be completed within the specified time frame due to unavailability of materlat to repair the seat.

1 Work Request LO3689 was initiated to seal the gap. The replacsment of the penetration seal was performed and declared operable on December 26, 1990.

f 7

o. J. Diederich g4 station Manager Lasalle county station OJD/mk1 CC: Nuclear Licensing Administrator NRC kesident inspector WRC t>acument Control Desk INPO-Records Center 9101000303 901231 PDR ADOCK 05000373 1 0 S

PDR 1

0010Sa A