ML20065B540

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Installation of Unqualified Namco EA740 Limit Switches SGT-POS-V/2A & 2B in Class IE Applications.Switches Replaced W/Qualified Class IE Limit Switches.Quarterly Repts Will Be Submitted
ML20065B540
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 02/02/1983
From:
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
Shared Package
ML20065B530 List:
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8302230209
Download: ML20065B540 (1)


Text

. _.

Attachment I WASHINGTON PUBLIC POWER SUPPLY SYSTEM NUCLEAR PROJECT NO. 2 DOCKET NO. 50-397 LICENSE NO. CPPR-93 10CFR50.55(e) CONDITION #221 NAMCO EA180 AND EA740 LIMIT SWITCHES INTERIM REPORT Description of Deficiency Unqualified NANCO EA740 limit switches SGT-POS-V/2A and SGT-POS-V/2B are installed in Class lE cpplications and are required to function during a Design Basis Accident (DBA).

Safety Implication These limit switches are used to indicate the positions (open/close) of safety related valves. Failure of the limit switches could result in erroneous valve position indication, thereby causing operator confusion or error during a DBA.

Corrective Action Limit switches SGT-POS-V/2A and SGT-POS-V/2B will be replaced with quali-fied Class lE limit switches. Additionally, other Class lE applications of NAMCO EA-180 and EA-740 limit switches are being reviewed for installa-tion of unqualified limit switches.

Status of Cerrective Action A Project Engineering Directive (PED) will be issued directing the replace-ment of unqualified NAMC0 EA-180 and EA-740 limit switches identified l

during the review. Quarterly reports will be filed with your office until l

resolved.

l l

l l

l 8302230209 830202 PDR ADOCK 05000397 S

PDR

- _ _ - _.