BALTIMORE GAS AND ELECTRIC CALVERT CLIFFS NUCLEAR POWER PLANT 1050 CALVERT CLIFFS PARKWAY

  • LUSBY, MARYLAND 20657-4702 CHAnLES H CRUSE PLANT GENEHAL MANAGER C ALVE R I CLIO S March 25,1994 l

l U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

Document Control Desk

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit Nos.1 & 2: Docket Nos. 50-317 & 50-318 Fire Detection Instrumentation Special Report Technical Specification 33.3.7. ACflON Reauirement b In accordance with uus Technical Specification 333.7, ACflON Requirement b, please find attached a Special Report concerning inoperable fire detection instrumentation. Specifically, the fire detection instruments in the common Unit 1 and Unit 2 intake structure were inoperable for greater than 14 days to support refueling outage related work on Unit 1.

Should you have any questions regarding this matter, we will be pleased to discuss them with you.

Very truly yours,

)

.4-l o

/

/')

/

f<

f,,V_

kV ClIC/WDM/ DEB /bjd Attachment cc:

D. A. Brune, Esquire J. E. Silberg, Esquire R. A. Capra, NRC D. G. Mcdonald, Jr., NRC T. T. Martin, NRC P. R. Wilson, N RC R.1. McLean, DNR J. II. Walter, PSC 940560660'6'9'46665

/

~

.]

PDR ADOCK 05000317 r'I I 8

PDR

~

l NITACilMENT (jJ FIRE DETECTION INSTRUMENTATION SPECIAL REPORT IIACKGROUND On February 24,1994, the Fire Detection Instrumentation for the common Unit 1 and Unit 2 intake structure was disabled. The smoke detection instrumentation in the intake structure was disabled to permit work activities to be conducted (welding, cutting, and grinding operations) during the Unit 1 Refueling Outage. This resulted in the instrumentation (smoke detectors) being inoperable for more than 14 days.

This type of activity typically results in the smoke detection system in the room sensing a " fire" condition and going into alarm, This condition results in a hanging or continuous alarm at the fire alarm panel in the Control Room (1C24B) and at the single point annunciator on the control boards (IC17). While other plant fire alarms will still be received and annunciated on the IC24B panel, they will not be annunciated to the IC17 panel. As a result, response to other plant fire alarms could be delayed. By installing the temporary alteration this condition-will be alleviated. The detection system remains inoperable until the work is complete.

As specified by Technical Specification 3.3.3.7, ACTION Statement b, a special report must be issued to the Commission pursuant to Technical Specification 6.9.2 if the detection system is not restored to an operable status within 14 days.

EFFECT ON UNIT OPERATION On February 24,1994 with Unit 1 in MODE 6 and Unit 2 at 100 percent power, the smoke detection system was disab!cd in the Unit 1 and Unit 2 intake structure via a Temporary Alteration. The smoke detection in this room is listed in Technical Specification Table 3.3-11 and is addressed by Technical Specification 3.3.3.7. In accordance with this Technical Specification, an hourly fire watch patrol was established to inspect the fire zone. In addition to the hourly fire watch patrol, a continuous fire watch is required by Calvert Cliffs procedures during welding / cutting / grinding operations in the room.

Pl ANS AND SCIIEDUI.ES Work in the area will be completed by the conclusion of the Unit 1 Refueling Outage and the-appropriate actions will continue in accordance with Technical Specification 3.3.3.7 and procedural requirements until the fire detection equipment in the area is restored to an operable status.