_-

i

. er

!" ' r"1 %%

E j

1

'42 CELARCNDE STREET P O W E R & L I G H T! P o cox coca. NEW GALEANS. LOUIS!ANA 70174

==

c,i J,.aJ L.%

. (504) 356-2345 MIDDIC GUUTH UI;Uili.S bfbiEM December 5,1978

.jgy m

LPL 10233 Q-3-A35.07.09 3-A1.01.04 4

)

Mr. K.V. Seyfrit. Director, Region IV U.S. Nuclear Regulatory Commission i

Office of Inspection and Enforcement 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76012

SUBJECT:

Waterford SES Unit 3 Docket No. 50-382 Interim Report of Significant Construction Daficiency No. 9

" Defective Emergency Diesel i

Generator Roller Pin" I

REFERENCE:

LP&L Telecon with NRC

^

dated November 6, 1978 Reporting Potentially Reportable LP&L Incident #18

Dear Mr. Seyfrit:

In accordance with the requirements of 10CFR50.55(c) we are hereby providing two copies of Interim Report of Significant Deficiency No. 9, " Defective i

Emergency Diesel Generator Roller Pin."

The final report will be forwarded j

1 by August 31, 1979.

During a recent performance test on a Cooper-Bessemer KSV Power Engine it j

was found that some power cylinder subassemblics showed abnormal wear on the surface of the roller pin in the valve crosshead (see attached report).

It j

is felt that this abnormal wear over a longer period of time could cause the engine to malfunction.

A redesigned roller. pin has been developed by Cooper-Bessemer.

The subassemblies will be replaced.

This will be completed prior to the final report.

j Very truly yours,

_,~.n-/

x.'. % f... b - &, m v.

D.L. Aswell 1

DLA/TFC/ys I

l OsPt l

l 7 gI2f t ofIf S

l

-..,-,,-..-.-n._

Mr. K.V. Seyfrit,. Director 2

December 5, 1978 Enclosure cc:

1)

Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 (with 15 copies of report) 2)

Director Office of Management Information & Program Control U.S. Nuclear Regulatory Commission Vashington, D.C.

20555 (with one copy of report)

D 9