Amend 53 to License NPF-49 Modifying Tech Spec 3/4.6.6.1 to Incorporate Revised Supplemental Leak Collection & Release Sys Flow Rate
ML20064A289
Person / Time
Site: Millstone 
(NPF-049)
Issue date: 08/22/1990
From: Stolz J
Office of Nuclear Reactor Regulation
To:
Northeast Nuclear Energy Co (NNECO)
Shared Package
ML20064A290 List:
References
NPF-049-A-053 NUDOCS 9008310086
Download: ML20064A289 (5)


Text

-

w 3.p.

  • M

'[

NUCLEAR REGULATORY COMMISSION i

E

. WASHINoToN, o, C. 20666' NORTHEAST NUCLEAR-ENERGY COMPANY, ET AL.'

DOCKET NO. 50-423 MILLSTONE NUCLEAR POWER STATION, UNIT NO. 3 AMENDMENT TO FACILITY OPERATING LICENSE

.\\

Amendment No. 53 License No. NPF-49 i

1_

The Nuclear Regulatory Comission (the Comission) has found that:

')

A.

The application for amendment by Northeast Nuclear Energy Company, et al. (the licensee) dated July 20, 1990, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set.

forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; L

C.

There is reasonable. assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and-safety of the public, and (ii) that such activities will be conducted in compliance with' the Comission's regulations; t-D.

The issuance of this amendment.will not be inimical to the comon defense.and security or to the health.and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 L.

been satisfied.

of'the Commission's regulations and all applicable requirements have i

l l'

L i

P l

3

^

c:

t i.

4 i

1

- 2:

x i

.\\

2.

'Accordingly, the license is amended by changes to'the Technical

. Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-49-is hereby-amended.to read as follows:

(2) Technical Specifications i

The Technical' Specifications contained in Appendix A,-as revised t

through Amendment No. 53-, and the Environmental Protection Plan contained in Appendix B, both of which are attached hereto are

't hereby incorporated in the license.

The licensee shall. operate the facility in accordance_with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of the date of_its issuance, to'be 1

implemented within 30 days of issuance.

j FOR THE NUCLEAR REGULATORY COMMISSION rm ohn F. Stolz, Director-R Proj!ct Directorate I-sion of Reactor Projects - I/II Office of Nuclear Reactor Regulation

.l

Attachment:

Changes to the Technical

. Specifications Date of Issuance:

August 22, 1990 7

I l

7 m

i

l-l 5

l;1 ATTACHMENT TO LICENSE AMENDMENT NO. 53 FACILTIY OPERATING LICENSE NO. NPF-49 DOCKET NO. 50-423_

L Replace the following pages of the Appendix A Technical Specifications with the enclosed pages.

The revised pages are identified by amendment number and; I

contain vertical-lines indicating the areas of change.:

Remove Insert 3/4 6-38 3/4-6-38

. 3/4 6-39 3/4 6-39 i

r 1: '

j L

1 l

1 l,

p L

1 L-l-

i l

l y

s.

m

  • ~

,g.

CONTAINMENT SYSTEMS-i,-

3/4.6.ti SECONDARY CONTAINMENT-5:

' SUPPLEMENTARY LEAK COLLECTION AND' RELEASE SYSTEM b

LIMITING CONDITION FOR OPERATION 3.6.6.1 Two independent Supplementary Leak Collection and Release Sys shall be OPERABLE.

APPLICABILITY: MODES 1, 2, 3, and 4.

1 g

AtTION:

.t With one Sus

. the inopera)plementary Leak Collection and Release System inoperable, restore STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHU 1

hours.

4 il SURVEILLANCE REOUIREMENTS l-4.6.6.1 strated OPERABLE:Each Supplementary Leak Collection and Release System s At least once per 31 days on a STAGGERED TEST BASIS by initiati a.

from the control room, flow through the HEPA filters and charcoal adsorbers and verifying a system flow rate of 7600 cfm to 9800 cfm the heaters operating;and that the system operates for at least 1 I

b.

At least. once per 18 months or '(1) after any structural maintenance on the HEPA filter or charcoal.adsorber housings, or 1

painting, fire, or chemical release in any ventilation (2) following cating with the system by:

zone communi-1)

Verifying that-the system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 0.05% and uses the test procedure guidance in Regulatory Posi-tions C.5.a. C.5.c, and C.S.d of Regulatory Guide 1.52, Revi-ston 2, March 1978,* and the system flow rate is 7600 cfm to 1

I 9800 cfm; 2)

Verifying, within 31 days after removal, that a laboratory analysis of a representative carbon sample obtained in accord-ance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2, March 1978,* meets the laboratory testing criteria 3

of Regulatory Position C.6 a of Regulatory Guide 1.52, Revi-L sion 2, March 1978,* for a methyl iodide penetration of less f

than 0.175%; and I

3)

Verifying a system flow rate of 7600 cfm to 9800 cfm during l

system operation when tested in accordance with ANSI N510 1980.

MILLSTONE - UNIT 3 3/4 6-38 Amendment No. 2, 53 i

I

A s

a

i. ;

CONTAINMENT' SYSTEMS ~

l l

pm

. SURVEILLANCE REDUIREMENTS fContinued);

1 After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of. charcoal adsorber operation, by verifying c.

within 31' days after removal.that a laboratory analysis of a repre, j

sentative carbon sample obtained in accordance with Regulatory 3

Position-C.6.b of Regulatory Guide 1.52. Revision 2. March 1978,*

l C

l meets the laboratory testing criteria of Regulatory Position C.6.a~

1

'of Regulatory Guide 1.52 Revision 2, March 1978,* for a methyl a

iodide penetration of less than 0.175%;

d.

At least once per 18 months by:

l 1)

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber >=nks is less than 6.25 inches Water Gauge while operating tb system at a flow rate of 7600 cfa to 9800 cfs, l

2)

_ Verifying that the system starts on a Safety Injection test

signal, 3)-

Verifying that each system produces a negative pressure of c

greater than or equal to 0.25 inch Water Gauge in the annulus within 50 seconds after a start signal, and g'

4)

Verifying that the heaters dissipate'50 15 kW when tested in accordance with ANSI N510-1980.

After each complete or partial replacement of a HEPA filter bank, by" l

e.

verifying that the cleanup. system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less.than 0.05% in accordance with ANSI N510-1980 for a DOP test aerosol while operating the system at a flow. rate of 7600 cfm to 9800 cfm; and.

l f.

After each complete or partial replacement of a charcoal adsorber l

bank, by verifying that the cleanup system satisfies the in place i

penetration and bypass leakage testing acceptance criteria of less than 0.05% in accordance with ANSI N510-1980 for a halogenated

-hydrocarbon refrigerant test gas while operating the system at a c

flow rate of 7600 cfm to 9800 e ~

  • ANSI.N510-1980 shall be used in place of ANSI N510-1975 referenced in Regulatory Guide 1.52, Revision 2 March 1978.

MILLSTONE - UNIT 3 3/4 6-39 Amendment No. y, 53 t

.