Informs NRC of New Action Incorporated Into Svc Water Sys Corrosion Action Plan to Specifically Address Occurrences of Microbiologically Induced Corrosion
ML20063L634
Person / Time
Site: Cooper Entergy icon.png
Issue date: 02/18/1994
From: Horn G
NEBRASKA PUBLIC POWER DISTRICT
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NSD940203, NUDOCS 9403070211
Download: ML20063L634 (2)


Text

4 e

~%

3 COOPER NUCLE AR ST ATK)N T 4 9. Nfr-M'4 P.O. BOX 98. BRoWNVILLE. NEBRASKA 68321 gll YkD,is Nebraska Public Power D. tn. t TELEPHONE 802)82E3811 is c

= =>="

.p.._._____..____..m.__

__,_===.m==

_ ___ )

l MSD940203 February 18, 1994 U.

S. Nuclear Regulatory Commission Attention:

Document Control Desk washington, DC 20555

Subject:

Service Water System Corrosion Action Plan Update Cooper Nuclear Station NRC Docket No. 50-298, Licen n

...).

DPR-46

Reference:

Letter from G.

R. Horn (NPPD) to Mr. James L.

Milhoan (NRC-Region IV) datea N 16 1993, " Completion of Issues Related to Unit Startup" Gentlemen:

In the reference letter, the District provided information regarding a Corrosion Action Plan established to address a throughwall leak discovered in a sample return line in the Service Water System at Cooper Nuclear Station (CNS)

The Action Plan included steps to identify the corro3 ion mechanism and to determine future activities concerning the control and monitoring of the identified corrosion mechanism in the CNS Servia Water piping.

Since the reference letter was submitted, additional testing has verified that Microbiologically Induced Corrosion (MIC) was involved in causing the throughwall leak.

It has also been determined that the service water piping appears to be most susceptible to MIC in regions of low or intermittent flow.

The District has incorporated new actions lac. the Corrosion Action Plan to specifically address the occurrence of MIC at CL,

This letter provides an update to our Corrosion Action Plan to inform you of the actions being taken or planned toward assuring the Service Water System will continue to be able to perform its intended functions under both normal and accident conditions.

The following is a description of these new,stions and a schedule for cumpletion for those yet to be fully imple: atu 1)

Periodic walkdowns of the Service iter System are taking place to visually inspect piping for evidence of any throughwall leakage which may be indicative of MIC damage.

Primary emphasis of these walkdowns is on sections of pip]..; that are most susceptible to MIC.

Any instance of throughw.

leakage identified will be entered into the Corrcr*' >e Acu or. Program for resolution.

- n34

  • $ Y, 00(

9403070211 940218 Iff PDR ADOCK 05000298 P

mymmmm ~ -gnnw[DRmmp~uyg;vwgy gep-m ganym-n,me-mm

~.nyynw m

.Dw d..

s we h MMb d.;bdm EN NINMN I4bNdr$hbrNeMs E u My ANM. w$dt J Sk MdiMiUbA h

=.v I

m.

e U.

S. Jiuclear Regulatory Commission F,ebruary 18, 1994 Page 2 2)

The CNS erosion / Corrosion program will be augmented to include service water piping potentially susceptible to MIC.

This will'be completed in September, 1994, and will include those piping sections examined per the CNS Corrosion Action Plan and any other piping sections deemed particularly susceptible to MIC.

3)

The procedure for heat exchanger inspection and cleaning is being enhanced to provide for more detailed inspections and docun'entation of inspections of the water box and existing water.

box coatings. The procedure revision will be completed in April, 1994.

4)

Controls will be established to insure that'any time a Service Water System component is opened for maintenance, the component internals will be inspected for MIC related degradation.

The Procedural Controls will be completed in September, 1994.

5)

The operation of various portions of the service water system that are normally left in a stagnant condition will be evaluated for conversion to continuous flow.

Industry experience has found this abatement method to be very effective. This evaluation will be completed in October, 1994.

6)

A study will be performed to evaluate the merits of adding a biocide injection system to the service water system based on the experience with the CNS service water piping to date.

The use of j

oxidizing as well as non-oxidizing biocides will be evaluated.

l This evaluation will be completed in November, 1994.

l We believe the Corrosion Action Plan including the elements discussed above will identify, address, and mitigate, if not prevent instances of MIC at CNS.

Should you have questions or would like additional information about the Corrosion Action Plan provided above, please call.

i i

I l

Sin erely i

i I

d~

i l

t Horn 1

(

L Vibe. resident -. Nuclear l

l

/nw l