Evaluation of Util Response to Suppl 1 to NRC Bulletin 90-001,Grand Gulf,Unit 1, Technical Evaluation Rept
ML20063B550
Person / Time
Site: Grand Gulf Entergy icon.png
Issue date: 01/24/1994
From: Udy A
EG&G IDAHO, INC.
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20063B553 List:
References
CON-FIN-L-1695 EGG-ERTP-10908, IEB-90-001, IEB-90-1, TAC-M85392, NUDOCS 9402010120
Download: ML20063B550 (16)


Text

'

ATTACHMENT' EGG-ERTP-10908 TECHNICAL EVALUATION REPORT Evaluation of Utility kesponse to Supplement I to NRC Bulletin 90-01: Grand Gulf-1 Docket No. 50-416 Alan C. Udy Published October 1993 l

EG&G Idaho, Inc.

Idaho National Engineering Laboratory Idaho Falls, Idaho 83415 Prepared for the U.S. Nuclear Regulatory Comission Washington, D.C. 20555 Under DOE Contract No. DE-AC07-761D01570 FIN No. Ll695, Task No. 11 TAC No, M85392 f {l: {  !  ;

\

\ /

9 SU N RY This report documents the EG&G Idaho, Inc., review of the Grand Gulf Nuclear Station, Unit 1, submittal that responds to Supplement I to NRC Bulletin 90 01. This NRC Bulletin provides information regarding the loss of fill-oil in certain pressure and differential pressure transmitters manufactured by Rosemount, Inc. This report identifies areas of non-conformance to the requested actions and the reporting requirements.

Exceptions to the requested actions and the reporting requirements are evaluated.

FIN No. L1695, Task No. 11 B&R No. 320 19-15-05-0 Docket No. 50-416 TAC No. N85392 ii

i PREFACE This report is supplied as part of the "Technica' Assistance in Support of the Instrumentation and Controls Systems Branch.' It is being conducted for the U.S. Nuclear Regulatory Comission, Office.of Nuclear Reactor Regulation, Division of Reactor Controls and Human Factors, by EG&G Idaho, Inc., Regulatory and Technical Assistance Program Unit.

iii

o - .

i CONTENTS

SUMMARY

.... ......................................................... ii t

PREFACE .............................................................. iii 1.

INTRODUCTION .............................................. ..... I 2.

NRC SPECIFIED REQUESTED ACTIONS ................................. 4 3.

EVALUATION ................................................. .... 7 3.1 Evaluation of Licensee Response to Reporting Requirements . 7 3.2 Evaluation of Licensee Response to Requested Actions ...... 8 4.

CONCLUSIONS ..................................................... 11 i

5.

REFERENCES . .................................................... 12  ;

I I

. I IV i

. , . . ~ . - . -- .

4

  • 4 Evaluation of Utility Response to Sunclement I to

NRC Bulletin 90-01: Grand Gulf-l  :

1. INTRODUCTION l

1 The NRC issued Bulletin 90-01 on March 9, 1990 (Reference 1). That

{

Bulletin discussed certain Rosemount pressure and differential pressure- i transmitter models identified by the manufacturer as prone to fill-oil leakage. The bulletin requested licensees to identify whether these transmitters were or may later be installed in safety-related systems.

Actions were detailed for licensee implementation for identified transmitters i installed in a safety-related system. These same actions apply to identified transmitters presently held in inventory for later installation in a safety- I related system.

With the gradual leakage of fill-oil, the transmittar would not have the  !

long term accuracy, time response, and reliability needet C. its intended  !

safety function. Further, this condition could go undetected over a long period. Redundant instrument channels are subject to the same degradation mechanism. This increases the potential for a common mode failure. Thus, '

this potential failure mechanism r&ised concern for the reliability of reactor i protection systems (RPS), engineered safety features (ESF) actuation systems, ,

and anticipated transient without scram (ATWS) mitigating systems. To achieve high functional reliability, there must be a low probability of component failure while operating, with any failures readily detectable.

Supplement I to NRC Bulletin 90-01 (Reference 2) was issued on December 22, 1992. The Supplement informed licensees of NRC staff activities regarding the subject transmitters, and noted continuing reports of transmitter failures. The NRC requested licensee action to resolve the issue.

L The Supplement also updated the information contained in the original bulletin. The licensee was requested to review the-information and determine- '

if it was applicable at their facility. Further, the licensee was requested to modify their actions and enhanced surveillance monitoring programs to  !

conform with the direction given. Finally, the licensee was instructed to 1

i l

l

'~ - -

.-----.--A_-

9 respond to the NRC. The Reauested Actions in Supplement I to NRC Bulletin 90-01 supersede the original NRC Bulletin 90-01 Reovested Actions.

In responding to Supplement I to NRC Bulletin 90-01, the licensee is directed to address three items.

1. A statement either conmitting the licensee to take the NRC '

Bulletin 90-01, Supplement 1, Reauested Actions or taking exception to those actions.

2. Addressing the actions committed to in the above statement, provide:
a. a list of specific actions, including any justifications, to be taken to complete the commitment,
b. a schedule for completion, and
c. after completion, a statement that confirms the actions committed to have been completed.
3. A statement identifying the NRC Bulletin 90-01, Supplement 1, Recuested Actions not taken, along with an evaluation providing the basis for exemption.

In implementing the replacement option of the NRC Reouested Actions, plant shutdown exclusively for replacing the transmitters is not required.

This allowance infers that replacements can be scheduled. With replacement in a timely manner, enhanced surveillance monitoring for interim operation is not required.

Entergy Operations, Inc., the licensee for the Grand Gulf Nuclear Station, Unit 1, responded to Supplement 1 of NRC Bulletin 90-01 with a letter dated March 5, 1993 (Reference 3). This technical evaluation report evaluates the completeness of that submittal. It also determines whether proposed surveillance methods are adequate to determine fill-oil loss-caused degradition of the transmitter. Finally, this report addresses the interval 2

4 of surveillance proposed by the licensee for any transmitters included in the enhanced surveillance program.

Many Rosemount transmitter failures have been attributed to the use of stainless steel '0"-rings between the sensing module and the process flanges.

Rosemount improved the manufacturing process for transmitters manufactured after July 11, 1989. Those improvements included a limit of the torque applied to the flange bolts. This limits the stress caused in the sensing module by the '0"-ring. Fost-production screening, including pressure testing of the sensing module for this potential latent defect, was also implemented at that time. Therefore, as tiescribed in Supplement I of NRC Bulletin 90-01, those Rosemount transmitters manufactured after July 11, 1989, are not subject to tt'is review.

3

',' { $2. NRC SPECIFIED REQUESTED ACTIONS The NR_C staff. specified the following Reouested Actions of licensees of operating Nacters'.- j.

. .- " , ', g

1. ~.Jteview plant recards and identify the following Rosemount transmitters Milman@fatturtifbefore July 11,1989) that either are used in or may be

. used 44 e(theredikfety-related or ATWS mitigating systems.

,L.;

~

a,=.e pyy

~ ~

. 6:- diassatidel 1153, Series B i-r ~4 ode , Series D y- .-

- iQ ?jj}

'. ,Follauring idist)fication, the licensee is to establish the following:

%.. .y

4. For thete:' identified transmitters having a normal operating e a ,.' pressure greater than 1500 psi, and are installed as part of "creactor pgstection trip systems, ESF actuation systems, or ATWS

,, ititigatictisystems, either replace the transmitter in an expedited

-g&neer, oremonitor monthly, for the life of the transmitter, using s.h og surveillance program.  ;

a x %g Y [

  • J.D M;}Ip(tified transmitter exceeds the 60,000 psi-month or the 130',Mai-month criterion (depending on the range code of the  !

v-transattter) established by Rosemount, enhanced surveillance on a refuell@$ot exceeding 24 months) basis is acceptable. Under thlicop4fsp, justification must be based on the service record and

.the spectP4c safety function of the transmitter. That Jytifica& don can be based on high functional reliability provided by y or diversity.

b. For those identified transmitters having a normal operating pressure greater than 1500 psi, and are installed as part of a safety-related system other than reactor protection trip systems, ESF actuation, or ATWS mitigating systems, either replace the transmitter or monitor quarterly, for the life of the transmitter, using an enhanced surveillance program.

If the identified transmitter exceeds the 60,000 psi-month or the 130,000 psi-month criterion (depending on the range code of the transmitter) established by Rosemount, enhanced surveillance on a .

refueling (not exceedino 24 months) basis is acceptable. Under -j this option, justification must be based on the service record and l the specific safety function of the transmitter. That j 4

l

justification can be based on high functional reliability provided by redundancy or diversity.

c. For boiling water reactors (BWR)--

For those identified transmitters having a normal operating pressure greater than 500 psi and less than or equal to 1500 psi, and are installed as part of reactor protection trip systems ESF actuation systems, or ATWS mitigating systems, either replace the transmitter, or monitor monthly with an enhanced surveillance monitoring program, until the transmitter reaches the designated (by Rosemount) psi-month criterion (60,000 psi-month or 130,000 psi-month, depending on the transmitter range code).

For transmitters that provide signals to the RPS or ATWS trips for high pressure or low water level, the enhanced surveillance must be monthly. For other transmitters in this classification, enhanced surveillance on a refueling (not exceeding 24 months) basis is acceptable. Under this option, justification must be based on the service record and the specific safety function of the transmitter. That justification can be based on high functional reliability provided by redundancy or diversity.

For pressurized water reactors (PWR)--

For those identified transmitters having a normal operating pressure greater than 500 psi and less than or equal to 1500 psi, and are installed as part of reactor protection trip systems, ESF actuation systems, or ATWS mitigating systems, either replace the transmitter, or monitor with an enhanced surveillance monitoring program, until the transmitter reaches the designated (by Rosemount) psi-month criterion (60,000 psi-month or 130.000 psi-month, depending on the transmitter range code) on a refueling (not exceeding 24 months) basis.

d. For those identified transmitters having a normal operating pressure greater than 500 psi and less than or equal to 1500 psi, and are installed as part of a safety-related system other than reactor protection trip systems, ESF actuation, or ATWS mitigating systems, either replace the transmitter or monitor with an enhanced surveillance monitoring program, until the transmitter reaches the designated (by Rosemount) psi-month criterion (60,000 psi-month or 130,000 psi-month, depending on the transmitter range code) on a refueling (not exceeding 24 months) basis.

5

e. Those transmitters having a normal operating pressure greater than 500 psi and less than or equal to 1500 psi, and have accumulated sufficient psi-month operating history to exceed the criterion established by Rosemount, may be excluded from the enhanced surveillance monitoring program at the discretion of the licensee.

However, the licensee should retain a high level of confidence that a high level of reliability is maintained and that transmitter failure due to loss of fill-oil is detectable.

f. Those transmitters having a normal operating pressure less than or equal to 500 psi may be excluded from the enhanced surveillance monitoring program at the discretion of the licensee. However, the licensee should retain a high level of confidence that a high level of reliability is maintained and that transmitter failure due to loss of fill-oil is detectable.
2. Evaluate the enhanced surveillance monitoring program. The evaluation is to ensure the measurement data has an accuracy commensurate with the accuracy needed to compare the data to the manufacturers drift data criteria. It is this comparison that determines the degradation threshold for loss of fill-oil failures of the subject transmitters.

The Supplement also states the NRC may conduct audits or inspections in the future to verify compliance with the established requirements.

6

3. EVALUATIDH The licensee provided a response to Supplement I of NRC Bulletin 90-01 on March 5, 1993. That response was compared to the Bulletin Reportino >

Reauirements and Reouested Actions as described below. The licensee reports they have 116 Rosemount transmitters that are subject to the Recuested Actions of the Supplement. The majority of these (95) are used in low pressure (less than or equal to 500 psi) applications.

The licensee states that transmitters manufactured before July 11, 1989, that are in spare parts inventory will be tagged to preclude the installation of a fill-oil loss susceptible transmitter in a safety-related application.

3.1 Evaluation of Licensee Response to Reoortino reouirements '

The licensee states they will take the Reauested Actions detailed in Supplement 1 of NRC Bulletin 90-01. Included with that statement is clarification, interpretation, and the limits placed on that commitrent. The licensee described the specific actions taken to implement the Recuested Actions and the associated schedule for completion.

A statement that the Reauested Actions are complete will be submitted separately after the scheduled items (surveillance interval changes and transmitter replacement) are complete. The submittal identifies where no licensee action is taken and provides evaluation and justification supporting the position that the action is not necessary.

The licensee submittal conforms with the Reoortino Recuireman11 of Supplement 1 of NRC Bulletin 90-01.

7

3.2 Evaluation of Licensee Resoonse to Recuested Actions Supplement 1 of NRC Bulletin 90-01 requested licensee action to resolve the issue of fill-oil leakage in Rosemount transmitters. In this Technical Evaluation Report, the Siouested Actions and associated transmitter criteria are suemarized in Sectson 2 of this report. The licensee identified a total ,

of 116 t.ansaitters that are in the scope of this review. The licensee has no Rosemount model 1154 transmitters currently installed that are in the scope of this review. The licensee response is discussed in the following sections.

3.2.1 Licensee Response to Recuested Action 1.a The licensee states there are no Rosemount transmitters from this classification at the Grand Gulf Nuclear Station.

3.2.2 Licensee Response to Recuested Action 1.b The licensee states there are no Rosemount transmitters from this classification at the Grand Gulf Nuclear Station.

3.2.3 Licensee Resoonse to Recuested Action 1.c The licensee states there are 10 Rosemount transmitters from this classification at the Grand Gulf Nuclear Station.

Five of these transmitters (IE31N086C, IE31N089A, IE31N089B, IE31N089C, and IE31N089D) have accumulated 53,450 psi-months of the 130,000 psi-month criteria for these transmitters. These transmitters will be replaced during the next refueling outage, scheduled for October 1993.

The other five transmitters in this classification (IB21N081A, 1B21N081C, IE32N061A, IE32N0610, and IE32N061N) will achieve their 60,000 psi-8 l

l l

1

o- .;

. 4

  • month criteria in 1993. The licensee will change the interval for monitoring these 5 transmitters to an 18 month interval. These transmitters do not provide signals for RPS or ATWS mitigation trips.

i The licensee. justified the change in the surveillance frequency to 18 months based on system diversity, redundancy, system logic, satisfactory ,

transmitter performance and calculated future availability, and calibration data. trending. Details were provided to support the change in the '

surveillance frequency. Based on these details, and that these transmitters I do not provide signals for RPS or ATWS mitigation trips, the change of the enhanced surveillance monitoring program interval to 18 months is acceptable for these 5 transmitters.

i 3.2.4 Licensee Response to Reouested Action 1.d '

The licensee states there are four Rosemount transmitters from this classification at the Grand Gulf Nuclear Station. The licensee states that these four transmitters (IB21N0027A, IB21N0027B, Id21N0044C, and IB21N0044D) will continue in the enhanced surveillance monitoring program on a refueling basis until the 60,000 psi-month criteria is reached. As each transmitter passes that threshold, each individual transmitter will be excluded from the enhanced surveillance monitoring program. See Section 3.2.5.

3.2.5 Licensee Response to Recuested Action 1 e 2

The licensee states there are currently 7 Rosemount transmitters from '

this classification at the Grand Gulf Nuclear Station. These transmitters '

were excluded from the enhanced surveillance monitoring program on March 31, 1993.

The licensee has 4 Rosemount transmitters that meet the classification requirements for Reouested Action 1.d. Three of these will soon exceed, or have by now exceeded, the psi-month criterion. At the discretion of the f

t 9

i

.T

/

i licensee, these transmittars will'be. excluded from the enhanced surveillance- I monitoring program as each transmitter reaches this threshold. This is permitted by the Supplement.

[

The Supplement does require the-licensee to have.a high degree of confilence that these transmitters remain highly reliable. The licensee state: this confidence is maintained with normal-18 month calibrations. The ,

licensee states a loss of fill-oil is detectable with these calibrations.

I 3.2.6 Licensee Response to Reouested Action 1.f i i

The licensee states there are 95 Rosemount transmitters from this '

classification at the Grand Gulf Nuclear Station. These 95 transmitters are >

excluded from the enhanced surveillance monitoring program as nemitted by the Supplement. ,

i The Supplement does require the licensee to have a high degree of '

confidence that these transmitters remain highly reliable. The. licensee states this confidence is maintained with nomal 18 month calibrations. The  :

licensee states a loss of fill-oil is detectable with these calibrations. 3 3.2.7 Enhanced Surveillance Monitorinu Prooram t

The licensee submittal includes a description of their enhanced

~

surveillance monitoring program. The program analyzes calibration drift data.

The data comes from routine surveillance testing. This method follows the drift analysis method that trends calibration data as explained.by Rosemount in their Technical Bulletin No. 4. The data is analyzed against the drift limits documented in Rosemount Technical Bulletin No. 4. The licensee l calculates the oil loss lifetime by dividing the zero drift limit for a given transmitter by the average zero drift rate. The licensee states the calibration data has sufficient accuracy.to detect drift, the accuracy being greater than recommended in Rosemount Technical Bulletin No. 4.

10 l

m--

4. CONCLUSIONS 'I Based on our review,'we find that the licensee has completed the reporting requirements of Supplement 1 of NRC' Bulletin 90-01, except notification that all actions committed to are complete. The licensee  :

commi:ted to inform the NRC of the completion of these actions after the -g compittion of the transmitter replacement in the upcoming refueling outage (approximately October 1993). Further, the licensee -*ther conforms to or has adequa'e justification for deviating from the request.. -+ ions of Supplement I to NRC Bulletin 90-01.

t i

4 11 Y

4 wv v 9

i

5. REFERENCES
1. NRC Bulletin No. 90-01: " Loss of Fill-oil in Transmitters Manufactured by Rosemount," March 9, 1990, OMB No. 3150-0011. -
2. NRC Bulletin No. 90-01, Supplement 1: " Loss of Fill-oil in Transmitters Manufactitred by Rosemount," December 22, 1992, OMB No. 3150-0011.
3. Letter, Entergy Operations, Inc., (W, T. Cottle) to NRC, " Response to NRC Bulletin 90-01, Supplement 1," March 5, 1993.