- _ _

~

.: _: 7 :

gQ-SI0 400 Chestnut Street 'Ibwer II January 7, 1981

.~

Mr. James P. O'Peilly, Director Office of Inspecticn and Enforcement U.S. Wclear Prculatory Cc=nissien Pagien II - Suite 3100 101 Marietta Street Atlanta, Georgia 30303

Dear Mr. O'Feilly:

FAN AND N 3E;D NUCLEAR PING - FIIL':TT WEID MISSetunCA= -

HTID-50-518, -519, -520, -521/31 PBED-50-553, -554/81-01 Tae subjact deficiency was initially reported to NBC-OIE Pogien II Inspector R. W. Wright on Dece:rter 3,1980, as :Ct's HTAHPP 8003, HTBHPP 8003, and PENEPP 8003. In ccatoliance with paragraph 50.55(e) of 10 CFR Part 30, no are enclosing the first interin: report en the subject deficiency, m anticicates trans:nitting the final report en or before April 6, 1981. If ycu have any questiens, please m" Ji:n Dcmer at I"S 057-2014.

Very truly yours, TE2'ESSEE VArm At7"0CRITI L. M. Mills, Manager bclear Pegulation and Safety Dv 1mure

~

cc: Mr. Victor Stello, Director (Ehclosure)

Office of Inspection and Enforcenent U.S. N clear egulatory Ccenission Washington, DC 20555 d

S//

THIS DOCUMENT CONTAINS POOR QUALITY PAGES f3101140%q

ENCIDSURE HARTSVILLE AND PHIPPS BEND NUCLEAR PLANIS FILLET WELD MISSPECIFICATICN HTRD-50-518, -519, -520, -521/81-01 PBRD-50-553, -554/81-01 10 CFR 50.55(e)

REPORT NO. 1 (INTERIM)

Description of Deficiency In a number of TVA nuclear plant systems, fillet welds were specified, in lieu of beveled groove welds, to connect members whose angle of intersection is outside the limits for fillet weld application as stipulated-in the American Institute of Steel Construction (AISC) Standards. 'Ihe AISC Standatti states that the welds which are made joining members at an angle of 600 or less are to be defined as acute angle welds. Acute angle welds should be specified as beveled groove welds according to AISC.

Interim Procress TVA is in the process of evaluating the AISC Standards and the affected welds in order to determine a satisfactory resolution.

e.