VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION MONTHLY OPERATING REPORT REPORP NO. 82-07 JUNE, 1982 APPROVED BY:

Seh STATION MANAGER

(

l 8208120204 820715

{DRADOCK 05000280 PDR a

8 Section M

Operating Data Report - Unit #1 1

Operating Data Report - Unit #2 2

Unit Shutdowns and Power Reductions - Unit #1 3

Unit Shutdowns and Power Reductions - Unit #2 4

i

~

Load Reductions Due to Environmental Restrictions - Unit #1 5

Load Reductions Due to Environmental Restrictions - Unit #2 6

Average Daily Unit Power Level - Unit #1 7

Average Daily Unit Power Level - Unit #2 8

iummary of Operating Experience 9, 10 nmendments to Facility License or Technical Specifications 11 Facility Changes Requiring NRC Approval 12 Facility Changes That Did Not Require NRC Approval 12 Tests and Experiments Requiring NRC Approval 13 Tests and Experiments That Did Not Require NRC Approval 13

(

14 Other Changes, Tests and Experiments 15 Chemistry Report Description of All Instances Where Thermal Discharge Limits 16 Were Exceeded 4

Fuel Handling 18 Procedure Revisions That Changed the Operating Mode Described in the FSAR 19 s

Description of Periodic Tests Which Were Not Completed Within the Time Limits Specified in Technical Specifications 20 Inservice Inspection 21 Reportable Occurrences Pertaining to Any Outage or Power Reductions 22 Maintenance of Saf ety Related Systems During Outage or Reduced Power Periods - Unit #1 - Mechanical Maintenance 24 l

Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #2 - Mechanical Maintenance 26

(

11 Section fase Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit til - Electrical Maintenance 28

{

Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #2 - Electrical Maintenance 30 Maintenance of Safety Related Systems During Outage,or Reduced Power Periods - Unit #1 - Instrument Maintenance 32 Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #2 - Instrument Maintenance 34 Health Physics Summary 35 Procedure Deviations reviewed by Station Nuclear Safety and Operating Committee after Time Limits Specified in T. S.

36 l

t 4

.m 9

{

a f

f

( -

'l y

L' 1

3 OPEhATII;G DATA REPCRT

('

DOCKET NO. 50-280 DATE 08.IUL 82 CONPLETE: BY SUE. TUNN ICLEFliONE 804-357-3184 CFEMTING. STATUS

1. Ul;IT NAME SunRY UNIT 1
2. REP 3RTIt.G PERIO:

60182 70 63082

3. LICENSE: TiiEMAL POWER (&'T) 2441 l l

4.1;AVEPLATE RATING (GRCSS WE) 847.5 ) NOTES l

5. CESIGN ELECThiCAL HATING (NET 5'E) 788
6. b:AXIXUb' :EPENDABLE CAPACITY (GROSS n'E) B11
7. NAXIMUb' :EPEN:ABLE CAPACITY (NET M E) 775
8. IF CliANGES CCCUR IN CAPACITY RATIhCS N/A (ITEMS 3 liiROUGii 7) SINCE LAST REPORT, GIVE REASONS
9. PGiER LEVEL TO L'iiiCli RESTRICTE, IF ANY N/A

(/!ET M E)

10. hEASONS FOR RESTRICTIONS, IF ANY N/A TiiiS MONTii YR-TO-: ATE CUMUTATIVE
11. 12 CURS IN REPORTING PERIO:

720.0 4343.0 83471.0

( L2. NUMBER CF iiOURS REACTOR WAS CRITICAL 720.0 3900.5 49935.0

13. REACTOR RESEEVE SiiUT:0WN iiOURS 0.0 0.0 3731.5
14. iiCURS GENERATOR ON-LINE 920.0 3843.6 48918.4
15. U!,IT RESERVE SiiUTCOWN ii&URS 00 0.0 3736.2
16. CECSS 77iERNAL ENERGY GENERATE (L'ii) 175t356.4 9106343.0 113439609.4
17. GECSS ELECTRICAL ENERGY GENERATED (Wii) 551615.0 2876230.0 36695443.0 18.1.LT ELECIRICAL ENERGY GENEhATED (&'ii) 523037.0 2727865.0 34805101.0 1
19. UNIT SERVICE FACTOR 100.0 */*

88.5 */*

58.6 */*

20. VI.IT AVAILABILITY FACTOR 100.0 */*

88.5 */*

63.1 */*

21. U/.II CAPACITY FACTOR (USING X:C NET) 93.7 */*

81.0 c/*

53.8 */*

22. UNIT CAPACITY FACTOR (USING DER NET) 92.2 */*

79.7 */*

52.9 */*

23. UNIT F0hCE: GUTAGE RATE O.0 4.5 */*

24.1 */*

24. Slu/TC0i,$5 SClis':ULE: CVER NEXT 6 NONTES 09-10-82 Fall Maintenance - 14 Days (1YPE,CATE, AN BURATION OF CACli)
25. IT SiiUT COWN AT END OF REPORI EERIGC, ECTIMATE DATE OF STARIUP
26. UNITS In TEST STATUS FORCCAST ACliIEVE:

(PRIOR TO COX4ERCIAL OPERATION)

INITIAL CRITICAla'IY 1NITIAL ELECTRICITY C M4ERCIAL GPERATION

(

2 OPERATING :ATA HEP 0iG COCKET N. 50-281

(-

COXPLETED BY 0.J. COSTELLO

ATE 08 JUL 82 7ELEPiiONE 804-357-3184 CECEATING STATUS
1. UhII HAKE SURRY UNIT 2
2. REPORTIhG PERIO:

60182 70 63082

3. LICENSE TiiERVAL POWER (&'T) 2441 l l
4. l.AKEPLATE RATING (GROSS A'E) 847.5 l NOTES l
5. DESIGN EEECTRICAL RATING (liET 5'E) 788
6. NAXIMUI* DCPEN:AELE CAPACITY (GROSS ST) 811
7. KAXIMUN :EPENDAELE CAPACITY (NET ST) 775 8, 2 CliAhGES DCCUR IN CAPACITY RATINGS N/A (HE45 3 Tiih000ii 7) SII;CE LAST REP:R"', GIVE REASOlis
9. F0VER LEYEL 70 WEICE RESTRICTE:, 2 ANY N//

(l.ET G E )

10. REASGNS F:R RESTRICTIONS, IF ANY N/A TRIS MONTii YR-TC-ATE CUMULATIVE
11. iiOURS Ib REPORTING PERIO 120.0 4343.0 80351.0
12. NUMBER OF iiCURS REACTOR WAS CRITICAL 720.0 3788.1 48648.8

\\3. REACTOR RESERVE SiiUT:0WN liGURS 0.0 0.0 0.0

( 14. iiOURS GESCRATOR ON-LINE 720.3 3717.2 47828.9

15. UNIT RESERVE SiiUTCOWN iiGURS 0.0 0.0 0.0
16. GROSS IEERNAL ENERGY GENERATE: (AVii) 1680159.7 8236180.0 111533465.9
17. GROSS ELECTRICAL ENERGY GENERATEC (MJii) 543490.0 2643425.0 36320604.0 18.1;ET ELECTRICAL ENERGY GEliERATE (5'ii) 514415.0 2492964.0 34421679.0
19. UNIT SERVICE FACTOR 100.0 e/o 85.6 e/o 59.5 e/o
20. Ul.IT AVAI.4BILITY FACTOR 100.0 */*

85.6 */*

59.5 */*

21. UNIT CAPACITY FACTCR (USING M:C NET) 92.2 */*

74.1 */*

55.3 e/o

22. UNIT CAPACITY FACTOR (USING :ER NET) 90.7 */*

72.8 e/o 54.4 e/o

23. UNIT F0ECE: GUZAGE RATE 0.0 4.4 e/o 16.4 e/o
24. Sizul: OWNS SCliE:ULE DVER NEXI' 6 MONTiiS 10-01-82 Fall Ma1ntenance - 10 Days (TYPC,DATE,AN: CURATION OF EACli)
25. 2 SiiUT l0WN AT EN: OF REPORT PERIOC, ESTIMATE : ATE OF STARTUP
26. UNITS IS TEST STATUS FORECAST ACHIEVE:

LPRIOR TC CG.WERCIAL OPERATION)

INITIAL CRITICALITY INITIAL ELECTRICITY CCAMERCIAL OPERATION

(

O w

s,.

n 4 G

2 n 8 L

R 8 a 1 l

9 3

i

^,

e 1 N

n 7

t

(

i o

5 e e el 0

8 n 3 s

si e

a 8

y a

nt nF c

r oa e) u 2

r y i

)

iDiR o

c r l v 4 tcfLE S

0 u u i

0 u or 5

S J v 8 e

e ts nfo(

m L

e r

v c

(

i n

no s

S e

e c

I i is e a

O.EEYE e orr t

c o

- a MTBN ron c r

p DlO t

u N

r e Gah A A e

i Co t

pSR e

T N D i

Ei i R ie i

E 1

K T T P

&t b r yt b

E ipr n1 i

c t e6 h

E eAn h

tnv1 x

I L

r C N L

s e

x o E

u v

EfEE0 E

O U P

T a

e D

M C

P r

O 4

5 C

S N

m a )n O

r mci IT

".3. U aSl a r

p C

c c* gc cix U

2 StaE D

8 E

9

ll m (r a a 1

duu oe R

onnt h ha a ut R

teMMAO

  • ,7G E

e W

n ga N.

MI 234 u

O J

P 3

1 D

1 O

N T

A N

O e

u SN M

eit s

nr W

T n e o v p n

O R

t o

iE e D

O L

R i

T P

tan E

U im R

l i

a S

x T

. E g :c j6 E

r w

e

)

N

..g 3 di

)

I a

i s

n n

a n i U

e a

% 7E.[*

d lp c

lp o

x nU x

i E

o E

itc&

r (t

(

s e

M5 e

e e

ig r

c lrT n

o p

u r

t r) f si e ne e n g

iao RivLi F

ai a

s i

e t

yT a l lp r

t a

t c nx nn r

r oE e3 r

ea gor ts nt oi i(

o mn iat nt c3. " 5 p

ninu ur i r e el a r c

pt el a r

o uif ge meh e

qa e e pd pt saEMRROAOO s

e - - - - - - - l i

RABCDEFGI 1

ht 2

g n

ir l*

u d

aD d

e e

n dlu o

ed rce N

h o

c 9

i-7 FS

)

FS 7

/

8 I

't L

IX)CKET NO. 50-281 UNIT SilUTDOWNS AND POWER REDUCTIONS UNIT NAME surry Two DATE Julv 8.

1982 COMPLETED gy Vivian H. Jones REPORT MONTil _ June. 1982 TELEPilONE (804) 357-3184 w.

y?

3 Y

Licensee h

Cause & Correceive No.

Date g

3g 4

2ss Event g?

f3 Action to H

yI U ;f3 g Report st in O O

Prevent Recurrence o

e v

O 82-31 06-12-82 S

0.0 H

4 Reduced power to allow returning "5B" and "6B" EW HTRS to service.

82-32 06-13-82 F

0.0 G

4 Reduced power due to high sodium concentration on secondary side of steam generators. Source of sodium was domestic water left in condensate 6

side of "6B" FW HTR following leak testing. Sodium levels were reduced to within specifications prior to power increase.

I 2

3 4

F: Forced Reason:

Method:

Exhibit G-Instructions S: Scheduled A Equipment Failure (Explain) 1-Manual for Preparation of Data B. Maintenance or Test 2 Manual Scram.

Entry Sheets for Licensee C-Refueling 3 Automatic Scrain.

Event ReporI (LliR) File (NUREG-D-Regulatory Resiriction 4 Other (Explain) 0161)

E-Operator Training & License Examination F Administrative 5

G. Operational Error (E xplain)

Exhibit I - Same Source W/77) ll-Other ( E xplain)

5 a

LOAD REDUCTIONS DUE TO ENVIRONMENTAL RESTRICTIONS UNIT NO.1 MONTH: June, 1982 DATE TI!E HOJRS LOAD, MW REDUCTIONS, IN Ka'H REASON I

Norse during this reporting p-. lod.

(

(

MONTHLY TOTAL

6 i

LOAD REDUCTIONS DUE TO ENVIRONMENTAL RESTRICTIONS UNIT NO. 2 MONTil: June, 1982

(

DATE TIIE HOURS LOAD, MW REDUCTIONS, MW MWH REASON None duz ing this reporting period.

(

i

(

MONTilLY TOTAL l

l

l 7

.~CEE2 Ni 50-2E0 U::7 SUREY I
ATC 7-1-82

(

CCXPLETE: BY & J CCSTELLC LVEEAGE CAILY U.';'I KJER LGTL A:53: Jul.E B2 AVEEACE :AILY P*eEi1 LEVEL AVEi. AGE CAILY PCnTE LEVEL CAY

( YkT-/,CT)

EAY (r.T-NET) 1 727.8 16 725.8 2

731.0 17 724.1 3

732.5 18 721.4 4

733.5 19 724.0 5

730.9 20 726.8 6

731.7 21 725.8 7

732.3 22 723.0 8

732.9 23 720.1

(

9 731.7 24 713.1 10 730.5 25 715.9 11 730.5 26 716.8 12 730.9 27 720.3 13 729.8 29 719.4 14 731.2 29 722.3 15 726.2 30 730.9

&AILY U'.%T PCwTE LEVEL F0EX INETRUCTIONS C3 WIS 70EA, !Z5T TiiC ATThAGE CAILY UNIT PCkTE LEVEL IN :.!nT-ilET FOR CACE CLY IN TiiC EEP0rIi.G MONTii. GE5E FIGUhE5 WILL BE USE: TO PLOT A GRAPH FCR EACH EEPCRT-ZNG NCNTH. NCTE TiiAT BY USIilC NAXIYUM DEPEN:ABLE CAPACITY FOR THE NET ELECTEICAL h.1TIisG :F Zhc UNIT, THERE MAY BE OCCASICNS kiiEN SE CAILY AVERAGE P0kTR EXCEE:E Tii5100 */* LTAE (CR TiiE ECSTIGCTE: F0kTh LEbTL LINC). In SUCli CASES, SE AVEFAGE

. LAILY U.i.T PCkTR CUTPUT SHEET EiiCUL: BE FCSTkCTE: TO EXPLLIN Tiir APPAEENT AN:ALY.

(

8

.'OCFCT *;

  • 5 2

.>? 1

.c,u:.r.-..-g.

p.

as

.a

' ATE 7 P. 2 C.

r* * * *g*

  • rT ".

.C. /'

.c s..

t~r.f..r.*

T **

.a AVihA:E :AILY U!;II ?:L*r? L ~iEL

%:.l.~s:

.1Jt.E S2 AVERAGE :AILY P:wEi: LETEL AVEiUGE CLILY POWEE LCi*CL

/Y (X.;E-i.El)
AY (i.VE-: ET) 1 697.5 16

'56.9 2

699.9 17 754.8 3

699.6 18 720.6 4

698.6 19 6?S.7 5

699.0 20 741.9 G

900.0 21 749.6 7

700.6 22 707.0 8

699.7 23 698.8

(

9 700.6 24 751.0 10 699.9 25 750.8 11 700.1 25 748.9 12 678.9 27 749.1 13 517.3 28 747.4 14 747.7 29 747.3

=

15 745.9 30 745.8 l

l l

lAILY U.VII EC.lEE LEVEL F:iG INSTRUCTIONS

$ TiiiS F05, [1.5"I liiC AVER /GE :AILY U:;IT PCWER LWEL I.7 WE-NET F05 EACE TAY IN Zii 1.EP:RIIt.G NC::Tii. TiiESC FIGURES WILL BC USC: TO PLCT A GEAPii TCP EACli PCP:RT-IC.%':!.Tii.1.CTE liiAT EY USING MAXINU.'-l :EPEi;:ABLE C.tPACITY F0h Tiir lic ELrCTFICAL EAZIi;G OF 2EE U!:IT, TiiEEE *-lAY BE OCCASI:l:3 WE&i THE CAILY AVEhAGE F:k'ER EXCEE:S TEC 100 */* LI;;E h*R 1EE hESTF CTE: F:i'Ch LEVEL illiC). IN SUCE CASES, TiiE AVERAGE

' AI:,Y U: CIT F.* WEE CUTPUT SEEET Sii:UL: SE FC:T!;.nTE: TC ~ EXPLAIN THE APPAEEi;T A!;: :ALY.

(

9

SUMMARY

OF OPERATING EXPERIENCE

+

JUNE, 1982

('

operating experiences for this month which required load reductions Listed below in chronological sequence by unit is a summary of or resulted in significant non-load related incidents.

UNIT ONE June 1 This reporting period begins with the unit at 100% power.

June 30 This reporting period ends with the unit at 100% power.

UNIT TWO June 1 This reporting period begins with the the unit at 740 MWe/96%

Power with the "5B" and "6B" FW HTRS bypassed and isolated for tube leaks.

June 12 1202 - Commenced reducing power in preparation for returning "5B" and "6B" FW HTRS to. service following repairs.

2316 - Stopped power reduction at 450 MWe/60% power.

June 13 0216 "5B" and "6B" FW HTRS return to service.

0225 - Chemist reported S/G cation conductivity out of specification. Started 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> clock for power reduction to <35% power.

0300 - Chemist reported S/G sodium concentration out cf

(,

specification. Started 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> clock for power reduction to <35% power.

0449 - Chemist reported S/G cation conductivity in specification. Stopped 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> clock on this item.

0955 - Commenced power reduction to <35% power due to high S/G sodium concentration, 1120 - Stopped power reduction at 37% power.

1200 - Chemist reported S/G sodium concentration within i

specification. Commenced increasing power.

1600 - Stopped power increase at 780 MWe/99% power.

June 15 2100 - Increased power to 100% after instrument technicians adjusted loop AT setpoints.

June 18 1358 - Commenced power reduction to allow securing "A" High Pressure Drain pump (HPDP) for repairs to the lower motor bearing.

1430 - Stopped power decrease at 700 MWe/92% power.

I l

1754 - Commenced raising power.

2110 - Stopped power increase at 745 MWe/99% power.

l

I 10 s

SUMMARY

OF OPERATING EXPEPlDICE (Continued)

UNIT 'IMO June 19 1133 - Started decreasing power to recover condenser vacuum with the "A" condenser waterbox out of service for tube leaks.

1147 - Stopped decreasing power at 710 MWe/974 power.

1330 - Comenced power reduction to recover condenser vacuum.

1416 - Stopped power decrease 650 MWe/90% power.

1955 - Returned "A" HPDP to service.

2057 - Commenced increasing power.

2200 - Stopped increasing power. Unit at 1004 power.

June 22 1408 - Commenced decreasing power to allow securing "A" HPDP for repacking.

1426 - Stopped power decrease at 705 MWe/96%. Secured "A" HPDP.

1432 - Commenced reducing power to allow closing the condensate polishing system bypass valve.

1514 - Stopped power decrease at 600 MWe/80% power.

Condensate polishing system bypass valve is closed.

(

1520 - Con.menced power increase.

1540 - Stopped power increase at 620 MWe/82% power.

1750 - Placed seventh condensate polisher in service and commenced raising power.

2240 - Stopped power increase at 750/100% power.

June 23 2115 "A" HPDP returned to service.

June 30 This reporting period ends with the unit at 100% power.

11 MENDbEIGS TO FACILITY LICENSE OR TECE'ICAL SPECIFICATIONS JUNE, 1982 s

None during this reporting period.

t g'

I l

I s

r

_- ~_

. = _

12 FACILITY CHANGES REQUIRIWG NRC APPROVAL

(

JUNE, 1982 None during this reporting period.

3 FACILITY CHANGES THAT i

DID NOT REQUIRE NRC APPROVAL 4

JUNE, 1982 None during this reporting period.

4 i

I l

l i,

4 l

s l

t i

I t

(_

I i

~

13 TESTS AND EXPERIMENTS REQUIRING NRC APPROVAL 4

JUNE, 1982 None during this reporting period.

TESTS AND EXPERIMENTS THAT DID NOT REQUIRE NRC APPROVAL JUNE, 1982 None during this reporting period.

1

(

i

14 OTHER CHANGES, M TS AND EXPEPlMENTS JUNE, 1982

(

None during this reproting period.

(

(

15 SURRY POL'ER STATION CHEMISTRY REPORT l

June

-19 82 T.S. 6.6.3.d DRIMARY CDCLANT UNIT NO. 1 UNIT NO. 2 ANALYSIS MAXIMUM MINIMUM AVERAGE MAXIMUM MINIMUM AVERAGE A)

Eo A)2.12 EO Eo' E-1 E-1 E-1 Gross Radioact., pCi/ml 3.96 3.00 3.85 1.45 2.66 Suspended Solids, ppm 0.1 0.1 0.1 0.1 0.1 0.1 E-1 E-1 E-1 E-1 E-2 E-1 Gross Tritium, UCi/ml 2.11 1.30 1.53 1.72 5.80 1.15

~

A)

E-1 A)

E-1 A)

E-1 E-3 E-3 E-3 Iodine-131, UCi/ml 2.82 1.08 1.44 7.37 1.36 2.83 t

I-131/I-133 1.5739

.9113 1.2327.

2.7300

.4353

.7783 B)

Hydrogen, cc/kg 49.4 26.5 33.1 38.6 18.4 30.8 4

Lithium, ppm 1.16 0.66 0.92 1.60 0.70 1.25 Boron-10, ppm +

97.02 83.69-90.53 152.68 144.98 137.40

}0xygen-16, ppm

.000

.000

.000

.000

.000

.000 Chloride, ppm

<.05

<.05

<.05

<.05

<.05

<.05 pH @ 25*C 6.94 6.67 6.79 6.71 6.14 6.54

+ Boron-10 = Total Boron x 0.196 i

NON-RADIOACTIVE CHEMICAL (C)

RELEASES, POUNDS l

T.S. 4.13.A.6 l

Phosphate Boron 978 l

Sc-Sulfate Chromate

.00 3

.4 50% NaOH Chlorine c

l REMARKS: A) Indicates failed fuel B) VCT pressure adjusted C) These levels represent no adverse effect on environment l

(

a I

16 DESCRIPTICN OF ALL INSTyCES WHERE THEPJiAL DISCilARGE lit!ITS WERE EXCEEDED JUNE, 1982 Due to the impairment of the circulating water system on the following days, the thermal discharge limits were exceeded as noted.

0 June 1, 1982 Exceeded 15 F AT across station

  • 0 June 2, 1982 Exceeded 15 F AT across station June 3, 1982 Exceeded 15 F AT across station U

June 4, 1982 Exceeded 17.5 F AT across station

  • 0 June 5, 1982 Exceeded 15 F AT across station 0

June 6, 1982 Exceeded 17.5 F AT across station June 7, 1982 Exceeded 17 5 F AT across station 3

June 8, 1982 Exceeded 15 F AT across station June 9, 1982 Exceeded 15 F AT across station 0

June 10, 1982 Exceeded 15 F AT across station

  • 0 June 11, 1982 Exceeded 15 F AT across station 0

June 12, 1982 Exceeded 15 F AT across station

  • June 14, 1982 Exceeded 17.5 F AT across station June 15, 1982 Exceeded 17.5 F AT across station June 16, 1982 Exceeded 17.5 F AT across station 0

June 17, 1982 Exceeded 17 5 F AT across station June 18, 1982 Exceeded 15 F AT across station June 19, 1982 Exceeded 15 F AT across station g

June 20, 1982 Exceeded 15 F AT across station k

June 21, 1982 Exceeded 15 F AT across station 0

U June 22, 1982 Exceeded 15 F AT across station

  • June 23, 1982 Exceeded 17.5 F M across stadon g

June 24, 1982 Exceeded 17.5 F AT across station g

June 25, 1982 Exceeded 17.5 F AT across station g

June 26, 1982 Exceeded 17 5 F AT across station

  • 3 June 27, 1982 Exceeded 15 F AT across station U

June 28, 1982 Exceeded 17 5 F AT across station 3

June 29, 1982 Exceeded 15 F AT across station

  • g June 30, 1982 Exceeded 15 F AT across station.
  • Indicates dates where station AT was less than or equal to s

15.0 F across station for some time during the day.

The AT excursions were allowable under Technical Specification 4.14.B.2.

There were no reported instances of adverse environmental impact.

4 (m

17 FUEL HANDLING JUNE, 1982 l

{

UNIT ONE A new BPRA (12P255) failed the acceptance " drag testing",

l was shipped to Westinghouse at Columbia, South Carolina on June 4

29, 1982 for repairs.

i i

i i

s l

f f

18 FUEL HANDLING UNIT ONE JUNE, 1982 DATE NO. OF ANSI NO.

NEW OR SPENT FUEL SHIFFED/ RECEIVED ASCOGLIES TER SilIPMENT INITLU. ENRICISiEFT SHIPPING CASK ACTIVITY LEVEL

!!one during this reporting period.

l UNIT Tdo

(

Mona during this reporting period.

I.

l l

I l

19 4

PROCEDURE REVISIONS THAT CHANCED THE OPERATING !! ODE DESCP,IBED IN THE FSAR

(

JUNE, 1982 None during this reporting period.

(

20 DESCRIPTION OF PERIODIC TESTS WHICH WERE NOT Cor1PLETED WITHIN THE TIME LLMITS SPECIFIED IN TECiciICAL SPECIFICATIONS JUNE, 1982 None during this reporting period.

(

.~- ~_-

l J

21 INSERVICE INSPECTION JUNE, 1982 Performed the following inspections on Units No.1 and No. 2 9

for Inservice Inspection.

1

[

Unit No. 1 - Welds #2 and #3 on 1-CH-FL-3 Welds #1 and #3 on 1-CH-FL-3 All weld's satisfactory.

Unit No. 2 - Welds #2 and #3 on 2-CH-FL-2 All weld's satisfactory.

4 i

f 4

(

k' i

j 1

l

(

i l

i l

r

22 REPORTABLE CCCURREs4CES PERTAIEIE4G TO ANY OUTAGE OR PCEER REDUCTIONS JUNE, 1982 None during this reporting period.

23

.[

i i

i.

MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS i

UNIT NO. 1 l

MECHANICAL MAINTENANCE i

J i

i i

i t

l

(

24 i

j MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS

(

UNIT NO. 1 MECHANICAL MAINTENANCE JUNE, 1982 i

l s

I

~

None during this reporting period.

4 i

i l

1 4

e i

t l

l 1

[

t l

C

-e 4

a.. -

wa 4-.

a e

e e

s.,.a_.i j

25 0

MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS i

UNIT NO. 2 MECHANICAL MAINTENANCE 4

1 a

I 1

i I

k a

i 1

4 i

-,n,

.ra,, _ =..---,.-..,-,,-

n,, - ---

-,,. - - - - - -,...~-- -

4 l

i 26 i

.*a MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS

(

i UNIT NO. 2 MECHANICAL MAINTENANCE JUNE, 1982 i

1 Hone during this reporting period.

i

'f i

i

}

I b

6 i

.I i

e 8

3 1

27 1

o i

i

(

MAINTENANCE OF SAFETY RELATED SYSTEMS DURING j

OUTAGE OR REDUCED POWER PERIODS UNIT NO. 1 ELECTRICAL MAINTENANCE f

i i

i o

I f

m l

t f

I l

l

-.- ~. _.._. -. - -

.. = -... _-

- ~-..._..-.... -

2B MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED PCMER PERIODS UNIT NO. I a

ELECTRICAL MAINTENANCE i

4 l

JUNE, 1982 l

None during this reporting period.

1 6

I I

,i i

+,

a f

I h

.I f

(

i 1

l i

t n

.i e

e i

i ~

l l

l i

r i

r l

l l

l l

l

O 29 9

9

(

MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 ELECTRICAL MAINTENANCE 1

I l

l l

l 1

l e

I

m -

m -

m,-m

(.

~

a.

.......a-

i,......,u..-

,,.:,,.:,i:.

r i

i I

l 30 i

i i

j I

i i

I I

l l

I i

.l i

(-

I i

l i

i i

l l

1 i

j i

i i

t.

i i

i l

e i

i i

I' l

l di I

i n

I cm i

i A

cn'

{

l i

i g

at o

l l

I

=

1 at i R i

o I

l l

l l

o 8

!=

l 9

'8 I

i i

l i

I l

l l

j~

I I

=

i I

i l

e l

}

I i

i j

l l

G i

i t

l l

3 j,

~

C 1

~

i l

O ld i

tv 8

j '.

j l

4 i.

i I

6 i

2

& ik y.6 h

-1 i*

A

  • N

(

.d i

9 I

4 i

' gb l

l I

l.n I

i ag d

5 m

W l

1 ti l

N

' m c ls W 4 8 ok I

l I

l 5

ti I

~

i E

l 2 l' :

?

I a.e I'

i I faJ l

l

% 'O 1

6 2

{

l

.i i

i l

l l

i er l

i i

i I

i N U i

l a

i N

D I

i

  • a i

=.

3

)

a y

1 s

t k3 h.

=

o.

i

,y

e 31 5

  • t e

g

(

MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 1 INSTRUMENT MAINTENANCE

(

P i

e 32 ei MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS l

UNIT NO. 1 INSTRUMENT MAINTENANCE

_ JUNE, 1982 None during this reporting period.

i 1

a l

I

?

(

I a

4

,o 33 l

j J

l 1

(

MAINTEhANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS 4

UNIT NO. 2 INSTRUMENT MAINTENANCE i

l I

i l

j i

'l

,i 4

i 4

1 f

}

t i

1

,9 t

,-,n-,n--,-,n-r,,,.

,,e-

.,_.e...-.~.-

,-..,,,,,--.-.,,.......-~,..-,,-n-,,~,

--a

I P

D m

9 9

5 "a

4 hA m.

w e.

M T

=

1 t

=

M1 2

2 p

t.

2 T

8 C

9 T

o 1

R 9

e M

e 0

m n

1 u

t 6

J 0

2 U

2 3

=.

e a

S e

)

C I

R E

e T

R m

E i0 E.

M

.~.

C G

U w

C A

E R.

D m

f e

R T

C C

K A

F L

M F

F R

E A

W R

T.

M.

0 0

m G

s N

2 I

i w

R 0

ll HT S

2 t I

TD W

TT K

VS C

/

t A

t S.

C D

C E

I T

SF U

E 0

E 0

5 I

1 T

E 0

E A

T C

S.

R C

A U

E M

G M

T r

U E

E S

R C

R A

2E T

N I

A M

0

(

M h

A M

P E

M G

C A

C C

S T

V w

S E

L

. M A

T_

X 2

s b

/

X.

R V

9 iL

_ H 1

T m

2 y

T

/

W

=

W r

s r

0 r

l l

,t t

O O

q 4

M' GR 4

eg t

e i O

t e

O' e

1 4

g 9

P E

9 t

3

.A

35 HEALTH PHYSICS i

I JUNE, 1982

(

t There was no single release of radioactivity or radiation exposure specifically assolcated with an outage that accounted for more than 10% of the allowable annual values in 10CFR20.

1 i

1 l

i l

T l

r

\\

(

l s

l l

l i

l I

i i

f C

l f,

,m--w-.y,

,_._-.m.m--,m.,a~-=

=, -

i+-----tt-r--

--e r>

w

,e

- <~ - -

w-

s 36

[

PROCEDURE DEVIATIONS REVIEUED BY STATION NUCLEAR SAFETY AND OPERATING CO D!ITTEE AFTER TI!!E LD!I"5 e ' ' '

  • SPECIFIED IN TECHNICAL SPECIFICATIONS

{

JULY, 1982 Date SNSOC Procedure No.

Unit Title Date Deviated Reviewed MMP-C-V-001.1 1

Grinnell Diaphragm Valves 05-11-82 06-10-82 Mark No. 1-CH-147 PT-36 1

Instrument Surveillance 06-09-82 06-24-82

(

(

l l

l I

I 1 (

1 l

i L