Download: ML20062F032 (2)


Text

_

M Q $ jggg AEOD/E233 UE.':0RA';DU." FOR:

liarold R. Dentm, Director Office of Nuclear Reactor Remlation FRO:!:

Carlyle Michelson, Director Office for A1alysis.cnd Evaluation of Operational Data

SUBJECT:

CARB0:; DIOXIDE SYSTECS USED FOR FIRE PROTCCTIO::

IN OR ADJACENT TO CCITICAL AREAS A recent occurrence at the Grand Gulf Unit : reactor involved the actta tion of the CO2 systen in the ECCS penetratial roca. The event was initiated by a short in the initiation circuit relay. The systea operated repeatedly until the pressure in the roon forced open the locked door to the auxiliary bu il ding negion II daily report - July 14, 1932..

In addition to use in the ECCS penetratial rocn at Grand Gulf, AEOD is aware that C00 is used in the diesel generator rocas at several nuclear facilities, propose!I for use for fire protection in the coltrol roca and diesel generator rou;s at Perry, and believe that there may be other cases in which CO2 is used either in or adjacent to areas coltaining ecliplent reluired to nitigate or prevent reactor accidents.

x The use of CO2 in critical plant areas gives rise to several concerns which nay not have been fully addressed in licensing revicus. The following are cur co1cerns:

Recocnizing the force developed in the Crand Gulf event, was missile cencration cmsidered durinq the revieus of CO2 use in areas coltaining egliirent required to prevent or uitigate reactor accidents or in areas a(U aceit to such locations?

2.

Has the degradation in the perfarnance of solid state devices resulting fro. exposure to the cooling effect of CO2 been revieued?

J'any solid state devices are rated for service oily to 00C. The neiti19 point of CO2 is -5G.60C.)

8a08110215 820728 PDR ADOCK 05000416 F

PDR omce>

SUHNSME) omy OFFICIAL RECORD COPY

= =-323.m

-u

r l

g l

JUL 281982 Ilarold R. Denton l l

3.

flas the effect of rapid abandonr.ent of the control roon in the event of CO2 actuatici been reviewed? Can accidents resulting from the need for CO2 operatim (or perhaps caused by it) be adequately controlled in such cases?

4.

lias the possibility of CO2 entry into the ventilation system and its effect on personnel in other plant areas been considered?

I transmitted a similar concern in a neaorandun to R. Vollner and E. Jordan, dated January 23,1932. copy enclosed).

A aceting to discuss these issues will be arrmged at your request.

If you should desire additiani infomation or assistance, please cmtact either myself or Karl Seyfrit of my staff.

Original Signed by Carlyle Micht 1 son Carlyle f41chelson, Director Office for Analysis and Evaluation of Operational Data

Enclosure:

As Stated cc u/ enclosure:

DElsenhut, !.'RR RVollner, ;RR l

EJordan, IE Glainas, i:RR i

RFerguson, ;,RR ZRoszteczy, ERR l

VBenarcya, NRR Dis tribu tion :#

Central File AEOD Reading File AE0D Chron. File NRC PDR FAshe, AEOD MChiramal, AEOD KSeyfrit, AEOD CJHeltemes, AEOD CMichelson, AE00 omca >

.hE.Q2...

..hE.00 /g,c,

. hE.QD.,p....a,pQQ.,.

.. AE.QQ...f$.

.....O.k..

......h...... 9..

SURNAMEk

.h..I....

.I.,0.9.h...

,...hk..(....

.1/..i..'. /.6 2...

.l/21./.g2..

.2/gl./.q2....

.lG.gB!.2..

...ll.4.7/.q2....

om>

rec ronu ais com emcu caa OFFICIAL RECORD COPY usem im-me