ML20062E148

From kanterella
Jump to navigation Jump to search
Notice of Issuance of Amend 44 to Lic DPR-33 Amend 40 to Lic DPR-52 & Amend 17 to Lic DPR-68 Which Revise Tech Specs
ML20062E148
Person / Time
Site: Browns Ferry  
Issue date: 11/16/1978
From: Ippolito T
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20058A306 List:
References
NUDOCS 7812050026
Download: ML20062E148 (3)


Text

_.

~

7590-01 UNITED STATES NUCLEAR REGULATORY COMMISSION l

DOCKET N05. 50-259, 50-260 AND 50-296 TENNESSEE VALLEY AUTHORITY NOTICE OF ISSUANCE OF AMENDMENTS TO FACILITY

]

OPERATING LICENSE i

j The U. S. Nuclear Regulatory Commission (the Commission) has issued i

l Amendment No. 44 to facility Operating License No. DPR-33, Amendment No. 40 to Facility Operating License No. DPR-52, and Amendment No. 17 to Facility Operating License No. DPR-68 issued to Tennessee Valley Authority (the I

' licensee), which revised Technical Specifications for operation of the i

I Browns ferry Nuclear Plant, Unit Nos.1, 2 and 3, (the facility) located

)

in Limestone County, Alabama. The amendments are effective as of the

?

date of issuance.

These amendments change the Technical Specifications to (1) permit j

the average power range monitor system to be inoperable in the refuel

\\

mode, provided the source range monitors are connected to give a non-coincidence, high flux scram; (2) permit less than three intermediate

)

range monitors (IRMs) per trip channel to be operable in the shutdown or refuel modes, provided at least four IRMs (one in each core quadrant) are connected to give a non-coincidence, high flux scram; (3) clarifies i

j ambiguous portions of the Technical Specifications related to the rod i

block monitor system; (4) removes reference to an obsolete 1968 version of an ASTM procedure; (5) modifies the list of snubbers that are required to be operable; (6) removes a specification for additional tests of secondary containment that only applied during the first fuel; cycle for 3

l each Browns Ferry Unit, and (7) changes one of the four locations where.

i milk samples are collected.

1 781205007

%6

.~

7590-01 i The applications for the amendments comply with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and l

the Commission's rules and regulations. The Commission has made appro-priate findings as required by the Act and the Commission's rules and l

l regulations in 10 CFR Chapter I, which are set forth in the license amend-(

ments. Prior public

  • notice of these amendments was not required since the amendments do not involve a significant hazards consideration.

l The Commission has determined that the issuance of these amendments

)

l l

will not result in any significant environmental' impact and that pursuant l

to 10 CFR Section Sl.5(d)(4) an environmental impact statement, or negative declaration and environmental impact appraisal need not be prepared in connection with issuance of these amendments.

For further details with respect to this action, see (1) the applications for amendments dated August 2,1978 and August 11,1978,(2) Amendment No. 44 to License No. OPR-33, Amendment No. 40 to License No. OPR-52, and Amendment No.17 to License No. OPR-68, and (3) the Commission's related Safety Evaluation. All of these items are available for public inspection at the Commission's Public Document Room,1717 H Street, N. W., Washington, D. C., and at the Athens Public Library, South and Forrest, Athens,

i e

i l

l I

~,,.

a o

v w

e, e

7590-01 Ala bama 35611. A copy of items (2) and (3) may be obtained upon request j

addressed to, the U. S. fluclear Regulatory Commission, Washington, D. C.

20555, Attention:

Director, Division of Operating Reactors.

Dated at Bethesda, Maryland, this 16 day of flovember 1978.

l FOR THE NUCLEAR REGULATORY COMMISSION

$2../ w(h Thot;s A.'

polito, Chief Operating Reactors Branch #3 I

Division of Operating Reactors 1

1