APPENDIX A NOTICE OF VIOLATION 1

Baltimore Gas and Electric Company Docket Nos. 50-317 50-318 Based on the results of the NRC inspection conducted on September 5-8, 4

1978, it appears that certain of your activities were not conducted in full compliance with the conditions of your NRC Facility License Nos.

j DPR-53 and DPR-69 as indicated below.

These items are categorized as Infractions.

Item A pertains to Unit 1 and Item B pertains to Unit 2.

j A.

Technical Specification 4.5.B.5 (Technical Specification in effect prior to Amendment 20) states in part, that:

" Type B tests...shall be performed during each reactor shutdown for refueling, but in no case at intervals greater than two years."

Contrary to the above, no Type B testing of electrical penetrations was conducted from November 1973, to March 1976, an interval greater than two years.

B.

Technical Specification 6.8.1 states in part, that:

Written procedures j

shall be established, implemented, and maintained...."

Additionally, Calvert Cliffs Instruction 114, Attachment (5), Step 4, states in part, that:

"Each log sheet specifies the high and low limits anticipated for most parameters....Any readings outside this normal range will be circled and a comment entry made concerning j

the reason."

i I

Contrary to the above, readings outside the normal range for Safety i

Injection Tank 21B level were logged on the Control Room Log on September 5, 1978, during the 0800-1600 shift and during the 1600-3 j

2400 shift, without being circled and without any comment entries.

i This resulted in rendering Safety Injection Tank 21B inoperable, as defined in Technical Specification 3.5.1.b, for a period in excess of the one hour specified in Action statement a.

l '

7 812010M f

,--,