Responds to Violations Noted in Insp Rept 50-341/90-07. Corrective Actions:Improperly Labeled Container,Pushbroom & Mop Removed & Procedural Adherence in Transient Combustibles Addressed in General Orientation Training
ML20059M113
Person / Time
Site: Fermi 
Issue date: 09/21/1990
From: Shelton D
DETROIT EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
1-930, NUDOCS 9010030165
Download: ML20059M113 (3)


Text

-

l l

TOLEDO I

EDISON A Cemannr (ne gv Crsqpeny DONALD C. SHELTON Docket Number 50-346' f;* y p =

Lic.nse Number NPF-3 Serial Number 1-930 l

q September 21, 1990

]

United States Nuclear Regulatory Commission

]

Document Control Desk j

Vashington, D. C.

20555

{

Subject:

Response to Inspection Report 90007 j

Gentlemen Toledo Edison (TE) has received NRC Inspection Report 50-346/90007 (DRS) (Log

/

Number 1-2345) and provides the following response.

Violation:

Technical Specification 6.8.1.f requires that written l

90007 02 procedures be established, implemented and maintained covering the fire protection program implementation. Administrativ9 Procedure DB-FP-00007, " Control of Transient combustibles,"

l requires that com'.,ustible materials, not having a transient l

control permit, are not lef t unattended in the cable :;preading room for more than one hour at the end of the work activity.

Toledo Edison Company Procedure ISG-26 RO, " Industrial Safety i

Guidelines," specifies the labeling criteria of chemical containers.

Step 3 of this procedure requires that when the chemicals are transferred to a different container, the chemical container shall be labeled.

The transfer labels shall specify the chemical name, appropriate signal verd and the appropriate statement of hazard.

Contrary to the above, on April 24, 1990, in the cable spreading room, an inspector observed various minor amounts of individual accumulations of ordinary combustible materials. No work activity was evident for more than one,',ur and these combustibles were not removed at what appeared to be the end of the job. No transient combustible permit had been issued.

In addition, a four gallon sized container inproperly labeled as a "flammabh" liquid was also found in the able spreading room.

)

This container did not specify the chemical name, appropriate signal word or appropriate statement of hacard as required.

9010030165 90921 Q

PDR ADOCK 06000341 L

0

  • NRE NLEDO EDISON COMPANY s

EDISON PLAZA 300 MAD! SON AVENUE TOLEDO, OHIO 43652 l

o

b

+ Dock t Number 50-346 Lic;nsa Nu:ber NPF-3 Serial Number 1-930 6,Page 2 l

Response

Accep;ance or Denial of the Alleged Violation Toledo Edison acknowledges the alleged violation.

Reason for the Violation Toledo Edison personnel examined the container in the cable l

spreading room and discovered that it was not a Toledo Edison i

approved flammable liquid storage container. The container was instead a commercial small hand-pump sprayer, containing r.able pulling lubricant, which is a non-flammable material. The container had been paintad red and was labeled es containing flammable liquids. Toledo Edison personnel also valked down the rest of the cable spreading rosm and found the following additional transient combustibles:

a vacuum cleaner with valid transient combustible p9rmit attached, mop and a-pushbroom.

No other transient combustibles were fc.

during the walkdown.

Toledo Edison's review determined tha

<t likely reason for the container not having a transi

.nl permit was that the lubricant was brought onsite unnota.

ium centractor.

The lubricant was used for cable pulling 1.4 tne cable spreading room and the contain..' vss inappropriately labeled.

In addition, it appears the ordinary transient combustibles were left unattended due to failure to adequately clean the area y(

af ter the cable pulling job vas completed. Therefore, a failure to follow procedures involving transient combustibles is the overall reason fcr the violation.

Corrective Action Taken and Results Achieved As noted in Paragraph 11 (Page 34) of the Inspection Repert, immediate corrective actions were taken prior to the inspector departing the site. The immediate actions were to remove the improperly labeled container, t'ae mop, and the pushbroom.

l 8

5

g hi;

' Dockst Nuxber 50-346 j.

License Nuxber NPF-3

. Serial Number 1-930

'iPage 3 Corrective Actions to Prevent Recurrence Toledo Edison considers this to be an isolated case of failure to control transient combitstibles. The recently completed Annual Quality Assurance Audit of the Fire Protection Program cited the control of transient combuntibles as a program strength, which supports the determination that this incident is an isolated case.. To preclude further violations of there controls, Toledo Edison has ensured that procedural adherence, in transient ~ combust (bles, is adequately addressed-in General Orientation Training (GOT) and pre-job briefings.

D_a g Vhen Pull Compliance Vill Be Achieved As stated above, both immediate corrective actions and-corrective' actions to prevent recurrence heve been completed.

If you have any questions regarding this matter, please contact Mr. R. V.

Schrauder, Manager - Nuclear Licensing, at (419) 249-2366.