,.O 9 ENTERGY Ins"s """*"'"" '

/

' Kdbna LA 700EE.;

4 504 739 6774-R. F. Burski

.m iE { *'I h-I V;. wi ed :

W3F1-93-0211' A4.05 PR November 8,1993 U.S. Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, D.C. 20555

Subject:

Waterford 3 SES Docket No. 50-382 License No. NPF-38 Generic Letter (GL) 92-01, Revision 1 Gentlemen:

The USNRC submitted a letter dated September 2,1993 to Entergy Operations Inc., Waterford 3, requesting that Waterford 3 provide the initial Charpy Upper Shelf Energy (USE) value for each weld in the beltline region. The purpose of this letter is to provide the informetion requested by the USNRC.

The following table provides the initial Charpy USE value for each weld in the beltline region.

UPPER SHELF ENERGY FOR BELTLINE WELDS WELD LOCATION WELD NUMBER Initial USE (ft.-lbs)

Intermediate Shell 101-124 A 106 Longitudinal Welds Intermediate Shell 101-124 B, C 131 Longitudinal Welds Lower Shell 101-142 A, B, C 129 Longitudinal Welds Lower to Intermediate 101-171 166 Circumferential Weld Weld Repair 101-142 B 110 e 9 M.

O, ~

D{h 9311100312 931108 1 ~1 I

f PDR ADOCK05000382[j PDR.

1-l l

/

Generic Letter (GL) 92-01, Revision 1 i

W3F1-93-0211-Page 2 November 8,1993

'l

~!

The Charpy USE values are based on available Charpy impact test data-documented by Certified Material Test Reports (CMTR's)'during vessel-

.l fabrication.

j Please contact me or Robert J. Murillo (504) 739-6715 should.there be'any' questions.

Very truly yours,-

]

d i

f

'I

//,//

=

. W Burski Director l

Nuclear Safety I

l RFB/RJM/tmm i

cc:

J.L. Milhoan, NRC Region IV l

D.L. Wigginton, NRC-NRR R.B. McGehee l

N.S. Reynolds NRC Resident inspectors Office i

.-