_ _. -. _ _ _ _ ___ --
w,
'e
~
g
'B Vahey Power Staton
{:
Shmmepor1, PA 15077 0004
- o w n w eta wo n.uw. n,u, cm, mms 2ss -
August 10, 1990 l
U.-S.. Nuclear Regulatory Commission Attn: -Document Control Desk Washington, DC 20555 i
Reference:
Beaver Valley Power Station, Unit No. 2 Docket No. 50-412, License No. NPF-73 Primary Component Support Snubber Elimination.
Gentlemen:'
Enclosed are:
1.
Five (5) copies of WCAP-12093, Supplement 3 entitled,
" Evaluation of Pressurizer.
Surge Line Transients Exceeding 320*F for Beaver Valley Unit 2 (Proprietary)."
1 2.
Five (5) copies of WCAP-12094, Supplement 3 entitled,
" Evaluation of-Pressurizer Surge Line Transients Exceeding 320*F for Beaver Valley Unit 2-(Non-Proprietary)."
Jj 3.
A Westinghouse Application for Withholding, CAW-90-058, i
Accompanying Affidavit, Proprietary Information Notice, and copyright Notice.
t As Item 1
contains information. proprietary to Westinghouse Electric Corporation, it.is supported by an affidavit signed by Westinghouse, the owner of the information.
This affidavit sets l
forth the basis on which the information may be withheld from public disclosure by the Commission and addresses with. specificity the considerations listed in paragraph (b)(4) of Section 2.790 of the Commission's regulations, 1
Do Accordingly, it is respectfully requested that the information 3o@
which.is proprietary tx)
Westinghouse be withheld from public 20 disclosure in accordance with 10 CFR Section 2.790 of the 88 Commission's regulations.
Correspondence with. respect to the "O
copyright or proprietary aspects of the' items. listed above or the supporting Westinghouse affidavit should reference. CAW-90-058 and oo should be addressed to R.
A. Wiesemann, Manager ~ Regulatory and 8@
Legislative
- Affairs, Westinghouse Electric Corporation, y
P. O. Box 355, Pittsburgh, Pennsylvania 15230-0355.
85
[!h
~#o #
Nlle j
0"20'5
.Th4a /%r
Beavor Valloy Powar Station, Unit No. 2
-Docket No. 50-412, License No. NPF-73 Primary Component-Support Snubber Elimination Page 2 l
The enclosed WCAPs are being provided in response to a telecon between Messrs.
Sam Lee, Arnold Ime, shou Hou-and Peter S. Tam of l
the NRC staff and Mr. Brian F. Sepelak of my staff in March, 1990 which discussed exceeding a 320*r system delta temperature during.
the heatup from the Beaver-Valley Unit 2 (BV-2) first refueling i
outage.
WCAP-12093, Supplement 3-concludes' that the maximum stress intensity, fatigue usago factor and growth of postulated cracks are not significantly affected and that the forty year design life is. not impacted.
In addition, we have revised our operating procedures to add precautions and limitations to prevent exceeding a 320'F-system delta temperature in the future.
We believe that the anclosed information along with our May 15, 1990 submittal which reviewed load combination case'B/G 1
provides the necessary information for the NRC staff to complete I
its review on the subject request (TAC No.
71086).
In its y
March 3,
1989
- letter, the NRC provided interim approval of our request for the BV-2 second fuel cycle.
1[f the NRC staff cannot' complete its review by -the start of the BV-2 second refueling outage (scheduled-for S(stember 1,
1990),
then we request an extension of the interim' approval until-the NRC staff's review is complete.
If you have any questions concerning this matter, please contact my office.
Very-truly yours,
(
. Sieber ice President Nuclear Group cc:
Mr. J.
Beall, Sr. Resident Inspector Mr.
T.
T. Martin, NRC Region I Administrator Mr. A. W. DeAgazio, Project Manager i
W J