ll!b 9 ENTERGY l">'*M* "" "'""*'

Ryt Gtnan.MS 39150 Td 601437 2830 '

C. R. Hutchinson vcef w an (p Wn

'Mm RM iumar h;n December 21, 1993 U.S. Nuclear Regulatory Commission Mail Station P1-37 Washington, D.C.

20555 Attention:

Document Control Desk

Subject:

Grand Gulf Nuclear Station Docket No. 50-416 License No. NPF-29 Confirmation of Completed Actions Requested by NRC Bulletin 90-01, Supplement 1

" Loss of Fill-Oil in Transmitter Manufactured by Rosemount GNRO-93/00162 Gentlemen:

By letter dated December 22, 1992, the NRC issued.

Supplement 1 to Bulletin (NRCB) 90-01 " Loss of. Fill-Oil in Transmitters Manufactured by Rosemount".

Supplement 1 to NRCB 90-01 was issued to evaluate licensees compliance with regulations requiring that Rosemount Model 1153 (Series B ar.0 D) and Model 1154 transmitters manufactured prior to July 11, 1989 achieve the desired degree of high functional reliability.

The specific safety concern is that a gradual loss of fill-oil from the transmitter's j

sealed sensing module has the potential to induce transmitter failure and remain undetected while the j

transmitter is in service, resulting in a common mode i

failure.

NRCB 90-01 Supplement i requested licensees to i

take certain actions to resolve this issue and provide j

written confirmation, notifying the staff when these actions were completed.

The GGNS response to NRCB 90-01 Supplement 1 was transmitted by letter dated March 5, 1993.

In this response, we committed to 1) tag non-installed suspect lot i

Rosemount transmitters (i.e.,

transmitters manufactured prior to July 11, 1989). to prevent inadvertent use in their current configuration, 2) to changt the monitoring frequency of transmitters that were projected to " mature" during 1993, and 3) to replace certain " suspect lot" A

.A Q f' h

G9312151 - 1 j

)

9401030164 931221 6

-[3[

PDR ADOCK 05000416 G

.PDR

F,

,e~

2

+

t 21, 1993

[

December GNRO-93/00162 Page 2 of 3 transmitters during our 1993 refueling. outage.

As requested by the Reporting Requirements (Item 2c) of NRCB 90-01 Supplement 1, we are providing the staff with written confirmation documenting completion of Requested Actions Items 1 and 2 of.NRCB 90-01. Supplement 1. We plan no further actions regarding this matter. Details of the actions taken are delineated in Attachment 1.

This information is being submitted'under affirmation in accordance with 10CFR50.54 (f) (Attachment 2).

Please contact C. E.

Brooks at-601-437-6555 should you have any 3

questions or required additional information regarding.

this matter.

Yours truly,

-l l

v.

CRH/CEB/mtc a

attachments: 1)

GGNS Follow Up Response to NRCB 90 >

Supplement 1 (Confirmation of Completed Actions)

~-

2)

Af firmation per.10CFR50.54 (f) cc:

Mr. R. H. Bernhard (w/a)

Mr. H. W. Keiser'(w/a)

Mr.

R. B. McGehee (w/a)

Mr. N. S. Reynolds (w/a)

Mr. H. L. Thomas (w/o) 1 Mr. Stewart D. Ebneter (w/a)

Regional Administrator U. S. Nuclear regulatory Commission Region II 101 Marietta St., N. W.,

Suite 2900 Atlanta, Georgia 30323 Mr. P. W.

O'Connor, Project Manager (w/2)

Office of Nuclear reactor regulation U. S. Nuclear Regulatory Commission Nbil Stop 13H3 Washington, D.

C.

20555 Mr. Alex Marion (w/a)

Nuclear Management and Resources Council 1776 Eye Street, N. W.,

Suite 300

{

Washington, D. C.

20006-2996.

G9312151 2

j

i l

December 21, 1993 GNRO-93/00162-1 Page 3 of 3' bec:

Mr. M. N. Bakarich (w/a)

Mr. H. D. Berryhill (w/a)

Mr. D. G. Bost (w/a)

Mr. C. A. Bottemiller (w/a) i Mr. C. E. Brooks (w/2)

Mr.

R. W.

Byrd-(w/a)

Mr.

L. F. Dale (w/a)

Mr.

L.

F. Daughtery (w/a)

Mr. M. A. Dietrich (w/a)

Mr.

J. P. Dimmette (w/a)

Mr.

C.-M.

Dugger (w/a)

Mr. J. J. Fisicaro (w/a)

Mr. M.

L.

Humphries (w/a) l Mr.

L. W. Laughlin (w/a)

Mr.

T. W. Matson (w/a)

Mr. M. J. Meisner-(w/a)

Mr. D. L. Pace (w/a)

Mr. R.

L. Patterson-(w/a)

Mr.

J. C. Roberts (w/a)

.j Mr. S. A. Saunders (w/a)

]

(-

Ms. J. Summers (w/a)

/

Mr. J. A. Webb(w/a)

Mr. G. A. Zinke (w/a)

File (LCTS) (w/a)

.j File (Hard Copy) (w/a)

H File (RPTS) (w/a)

File (NS&RA (w/a)

File (Central) (w/a) ( 13 )

'0 G9312151 - 3

4.,

I 4.-

1-i

-i i

GGNS Follow Up Response to NRC Bulletin 90-01 Supplement 1

" Confirmation of Completed Actions" 3

..f l

' l 1

i

)

. 4 h

G9312151 - 4

4 Grand Gulf Nuclear Station Follow Up Response to NRC Bulletin 90-01, Supplement 1 Reporting Requirements for Operating Reactors

" Confirmation of Completed Actions" NRCB Item 2 (c) :

When completed, provide the Staff a written statement confirming completion of Requested Actions Items 1 and 2 to NRCB 90-01 Supplement 1.

GGNS Response:

This transmittal satisfies the request to provide written confirmation upon completion of Items 1 and 2 from the Requested Actions of NRCB 90-01 Supplement 1.

A point by point comparison between a summarized extract from Requested Actions Items 1 and 2 of NRCB 90-01 Supplement 1 and the corresponding GGNS response is provided below.

We plan no further action regarding this issue.

Reauested Actions (Item 1)

Licensees are requested to_ review plant records and identify Rosemount Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters manufactured prior to July 11,-

1989, that are used or may be used in the future in either safety-related systems or systems installed in accordance with 10CFR50.62 (the ATWS rule), and perform the following requested actions:

Regpested Actions Item 1(a)

Expeditiously replace, or monitor for the

[

life of the transmitter on a monthly basis t

using an enhanced surveillance monitoring program, any transmitters that have a normal operating pressure greater than 1500 psi and that are installed in the reactor protection trip system, ESF actuation systems or ATWS systems...

GGNS Response to Itag,1(a) j GGNS has no transmitters installed that are enveloped by this criteria. As committed in our initial response to NRCB 90-01 Supplement 1,

non-installed Rosemount transmitters 1

manufactured prior to July 13, 1989 have b'een tagged to prevent inadvertent installation in their current configaration. Model 1154-transmitters manufactured by Rosemount are not used in any plant applications. This agIj_on has been comoleted.

G9312151 -5

~*

Grand Gulf Nuclear Station Follow Up Response to NRC Bulletin 90-01, Supplement 1 Reporting Requirements for Operating Rea7 tors

" Confirmation of Completed Actions" Requested Actions Recuested Action Item 1(b)

Continued Replace, or monitor for the life of the transmitter on a. quarterly basis using an enhanced surveillance monitoring program, any transmitters that have a normal operating pressure greater than 1500. psi and that are used in safety-related applications but are not installed in reactor protection trip systems, ESF actuation systems or ATWS systems...

GGNS Response to Item 1(b)

GGNS.has no transmitters installed that are enveloped by this criteria. As committed in our initial response to NRCB.90-01 Supplernnt 1, non-installed Rosemount transmitters nanufactured prior to July 11, 1989 have been tagged to prevent. inadvertent installation in-their current configuration. Model 1154 transmitters manufactured by Rosemount are not used in any. plant applications. This action has been comnleted.

Requested Actions Item 1(c)

Replace or monitor on a monthly basis using an enhanced surveillance monitoring program, until the transmitter reaches the appropriate psi-month threshold criterion recommended by Rosemount, any transmitters that have a normal operating pressure greater than 500 psi and less than or equal to 1500 psi, that are installed in reactor protection trip systems, ESF actuation systems, or ATWS j

systems. On a case-by-case basis except for j

transmitters that initiate reactor protection i

or ATWS trips for high pressure or low water level, licensees may monitor using an

)

enhanced surveillance monitoring program at least once every refueling' cycle, but not.

exceeding 24' months, if sufficient justification is provided based upon transmitter performance in service and its specific safety function.

j G9312151 - 6

4 Grand Gulf Nuclear Station Follow Up Response to NRC Bulletin 90-01, Supplement 1

)

Reporting Requirements for Operating Reactors l

" Confirmation of Completed Actions" 1

Requested Actions Continued j

GGNS Response to Item 1(c)

In the GGNS response to NRCB 90-01 Supplement 3

1, we reported 10 installed transmitters as i

being enveloped by this criteria.

The 5 transmitters listed in Table 1 of our response were reported to have accumulated 53,450 psi-months against the Rosemount threshold criteria of 130,000 psi-months. As committed in our response, these transmitters have been replaced with transmitters manufactured after July.11, 1989. This astion has been comoleted.

The remaining 5 transmitters were are listed in Tables 2 and 3 of our~ response to Supplement 1 were projected to reach the appropriate psi-month criteria recommended by Rosemount during this year (1993). These transmitters were to remain in the' current 18 month enhanced-surveillance monitoring program until the appropriate psi-month threshold recommended by Rosemount was achieved or until replacement.

l The information reported for these transmitters in our response to NRCB 90-01 Supplement i reflected psi-month data accumulated as of January 1, 1993-(53,320 psi-months). These transmitters have since accumulated an additional 9.8 psi-months prior to plant shut down for the sixth refueling outage (i.e.,

9.4 months of operation

  • 1040 psi). These transmitters i

have now accumulated approximately 63,120

)

psi-months, thereby exceeding the psi-month.

threshold of 60,000 psi-months established by Rosemount to warrant continued inclusion in

'i an enhanced surveillance monitoring program.

I As such, these transmitters have been removed from the enhanced surveillance monitoring program.

This action has been completed.

G9312151 - 7

Grand Gulf Nuclear Station Follow Up Response to NRC Bulletin 90-01, Supplement 1 Reporting Requirements for Operating Reactors

" Confirmation of Completed Actions" Requested Actions Continued Requested Actions Item 1(dl

'ndtor at least once every Replace, or )

i refueling (yt, but not exceeding 24 months, using an ennc ced surveillance monitoring program until the transmitter reaches the appropriate psi-month threshold criterion recommended by Rosemount, any transmitter used in safety-related systems that have a normal operating pressure greater than 500 psi and less than or equal to 1500 psi, and that are not installed in reactor protection trip systems, ESF' actuation systems, or ATWS systems.

GGNS Resoonse to Item 1(dl As provided in Table 4 of our response to-NRCB 90-01 Supplement 1, GGNS has 4 transmitters that are enveloped by this criteria.

As recommended by the bulletin supplement, these transmitters were included in our enhanced surveillance monitoring program to be monitored on a 18 month frequency until the appropriate psi-month criteria recommended by Rosemount is achieved.

Requested Action 1(e) i At licensee discretion, exclude from the enhanced surveillance monitoring program any transmitters that have a normal operating pressure greater than 500 psi and less than or equal to 1500 psi that have reached the appropriate psi-month threshold recommended by Rosemount (60,000 psi-months or 130,000 psi-months depending on the range code of the transmitter)...

GGNS Response to Item 1(e)

GGNS has 7 transmitters that are enveloped by.

this criteria. As stated in our' response to NRCB 90-01 Supplement 1, these transmitters have been excluded from the enhanced' surveillance monitoring program.

G9312151 - 8

~

Grand. Gulf Nuclear Station Follow Up Response to NRC Bulletin 90-01, Supplement 1 Reporting Requirements for. Operating Reactors

" Confirmation of Completed Actions" Requested Action 1(f)

At licensee discretion, exclude from the enhanced surveillance monitoring program any transmitters that have a normal operating pressure less than or equal to 500 psi...

GGNS ResDonse to Item 1(f)

GGNS has 95 transmitters that are enveloped by this criteria. As permitted by NRCB 90-01 Supplement 1, these transmitters have been excluded from the enhanced surveillance monitoring program.

Requested Actions (Item 2)

Licensees are requested to evaluate the enhanced surveillance monitoring program to ensure that-the program provides measurement data with an~ accuracy range consistent with that needed for-comparison with manufacturers drift data criteria for determining degradation caused by a loss of fill-oil.

GGNS Response to Item 2 As stated in our initial response to NRCB 90-01 Supplement 1, the enhanced surveillance monitoring program has been evaluated for measurement data accuracy. The calibration data trending has sufficient.

accuracy to detect drift consistent with manufacturers criteria.

G9312151 - 9 C.o

^'

l 4

}

GGNS Follow Up Response to NRC Bulletin 90-01 Supplement 1

" Confirmation of Completed Actions" Af firmation per 10CFR50.54 (f)

'G5312151 - 10

,o BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION LICENSE NO. NPF-29 DOCKET NO. 50-416 IN THE MATTER OF MISSISSIPPI POWER & LIGHT COMPANY and SYSTEM ENERGY RESOURCES, INC.

and SOUTH MISSISSIPPI ELECTRIC POWER ASSOCIATION and ENTERGY OPERATIONS, INC.

SfFIRMATION I,

C.

R.

Hutchinson, being duly sworn, state that I am Vice President, Operations GGNS of Entergy Operations, Inc.; that on behalf of Entergy Operations, Inc., System Energy Resources, Inc.,

and South Mississippi Electric Power Association I am authorized by Entergy Operations, Inc. to sign and file with the Nuclear Regulatory Commission, this confirmation of completed actions requested by NRC Bulletin 90-01 Supplement 1 for the Grand Gulf Nuclear Station; that I signed this confirmation as Vice President, Operations GGNS of Entergy Operations, Inc., arid that the statements made and the matters set forth therein ame true and correct to the best of my knowledge, information and belief.

,/

3

//

f,F j-7

(_;),,? ),7

/ 1/b,4m, C.

R.

Hutchinson STATE OF MISSISSIPPI COUNTY OF CLAIBORNE SUBSCRIBED AND SWORN TO before me, a Notary Public, in and for the ty State above named, this f/48 day of

{

g(+ _

1993.

(SEAL) d a h A faa a l A tt a

//'

Nota @Public

.My commission expires:

9661'll184meADN 88Ji r3uolss}wmog Ayg d

My Commiss!on Expires November 11,1996

..