Forwards Insp Rept 50-309/93-21 on 930823-27.No Violations Noted
ML20059A019
Person / Time
Site: Maine Yankee
Issue date: 10/19/1993
From: Durr J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Frizzle C
Maine Yankee
Shared Package
ML20059A022 List:
References
NUDOCS 9310260200
Download: ML20059A019 (3)


See also: IR 05000309/1993021

Text

y-

. -

-

\\

y

<

,

'

g

-

OCT l 91993

r.

s

,

iDocket No. 50-309

,

Mr. Charles D. Frizzle

. President -

. Maine Yankee Atomic Power Company-

- 83 Edison' Drive

Augusta, Maine 04336

-

..

' Dear Mr. Frizzle:

SUBJECT: NRC REGION I INSPECTION REPORT NO. 50-309/93-21

This letter transmits the NRC Region I inspection report for the announced inspection

conducted by Mr. Skokowski of this office on August 23-27,1993, at the Maine Yankee

Nuclear Station in Wiscasset, Maine. Mr. Skokowski discussed the findings of this

inspection with Messrs. Whittier and Blackmore and other members of the Maine Yankee

Atomic Power Corporation,.on August 27,1993.

' Areas' examined during this inspection focused on the following issues identified at the Maine

. Yankee Nuclear Station: 1) the wiring configuration discrepancy in the emergency diesel

generator load permis~sive circui'.; 2) loose adjusting screw found within the cover of the ".B"

. load permissive relay; and 3) the spurious trips'of circuits breakers equipped with

,

.

[:

MicroVersaTrip RMS-9 overcurrent devices.

,

k

We noted that your initial actions and plans to resolve both issues related to the load

permissive relays were good. Your corrective actions associated with the load permissive

circuit' wiring' discrepancy and the significance of the as-found setting associated .with the "B"

EDG load permissive relay are considered unresolved items. In addition, you have

committed to ensure that the following issues are addressed prior to plant startup: 1) the

elimination of the wiring configuration discrepancy in the EDG load permissive circuit;

2) the development of a plan to search for other possible single failure wiring discrepancies;

. 3) the evaluation of the significance of the loose adjusting screw associated with the "B"

EDG load pennissive relay, and determine the potential for the same problem occurring in

similar relays; and 4) the implementation of corrective actions to ensure that the safety-

related circuits previously containing RMS-9 devices are operable with respect to the

potential common mode failure. If your understanding of these commitments is different,

please contact me.

p

'

'

250102

>

/ d@

9310260200 931019

A

'PDR- ADOCK 05000309L

G-

ppg '

+

.

g;, ;,

-

-

,

ill:

OCT l 91993

"

..

"

~Mr. Charles D. Frizzle

2

r

No response to this' letter is necessary. Thank you for your cooperation.

,

Sincerely,

n"

'

Ocic*u n !;tc r,a py;

6 9ua P, 7:u.t-

Jacque P. Durr, Chief

<

Engineering Branch

Division of Reactor Safety

e

' Enclosure: NRC Region I Inspection Report 50-309/93-21

cc w/ enc 1:

,.

'

. G. Leitch, Vice President, Operations

P. L. Anderson, Project Manager (Yankee Atomic Electric Company)

R. W..Blackmore, Plant Manager

L. Diehl,' Manager of Public and Governmental t.ffairs

J. A. Ritsher, Attorney (Ropes and Gray)

P. Dostie, State Nuclear Safety Inspector

P. Brann, Assistant Attorney General

U. Vanags, Maine State Planning Office

CJBrinkman, Combustion Engineering, Inc.

First Selectmen of Wiscasset '

Maine State Planning Officer

Public Document Room (PDR)

locf Public Document Room (LPDR)

]

~

'

Nucicar Safety Information Center (NSIC)

,

K. Abraham, PAO (2)'

NRC Resident Inspector -

g

State of Maine, SLO Designec

..

I

b

g

. ,

,

?h q..

'

OCT -l 91993

\\;

-

<

,

,

Mr. Charles D. Frizzle

3

.bcc w/ encl:

Region I Docket Room (with concurrences)

- bec w/enci (VIA F MAIL):

V. McCree, OEDO

' E. Trottier, LPM, NRR -

W. Butler, NRR

n.

S. Alexander, NRR/RVIB

!

?.

r-

1

F

-

l

' RI:DRS

RI:DRS

RI:DRS

""

10/q/93

10//f/93

10////93

OFFICIAL RECORD COPY

A:MY9321. INS

.