4 SEEMENS r)o-iM7 i
November 30,1993 Washington State Department of Ecology Attn: Mr. Kim H. Sherwood Water Quality Division 106 S. Eth Ave.
Yakima, WA 98902-3387
Dear Mr. Sherwood:
J WASTE LIQUID EFFLUENT REPORT October 1993 i
Measurements of liquid waste discharges from the Siemens Power Corporation facility to the j
Richland Municipal Sewerage System are reported herein. Discharges were in full compliance with limits specified in the Siemens State Waste Discharge Permit (Permit No. ST3919) with the exception of the daily maximum nitrate exceedance on October 19,1993. This has previously been reported to your office by phone on October 21 and via letter on October 27.
l Waste discharge records are maintained by Siemens and are available for review at your convenience.
[
Very truly yours, J
A) L y'~
V. u t
_ }
L. J. Maas, Manager Regulatory Compliance i
LJM:KHT:pm j
LJM:93:175/ File i
Attachment i
cc:
S. R. Arlt - Water & Waste Utilities, Director, City of Richland B. H. Faulkenberry, Regional Administrator, NRC Region V M. L St. Martin - City of Richland
':NRC-HQ, Document Control Center l l
i, 0700'!0 b
Siemens Power Corporation
.+
9
~
T "jl t-
- c,, L1 - i-5.s Q k-.rgT]. 7JA 9335? 0130 Te! (509) 375 8100 Far (503) 375 6402 l
9312090313 931031 II i
PDR ADOCK 07001257 n
.C
,PDR N
j
SIEMENS POWER CORPORATION Waste Discharge Permit No. ST3919 Report No.:
10-93
{
i Report Period:
October 1.1993 through October 31.1993 t
i i
SPC - WASTE EFFLUENT STATION Parameter Monitored.
iDaily Average.
iDailyLMakirnums
- (Limit)L '
s i(Lirnit)1 Flow Volume (gal) 194,505 218,340 (400,000)
(500,000)
NH as N (Ib) 15 23 4
(80)
(125)
NO as N (Ib) 660 919 3
(750)
(875) e Fluoride as F Ob) 2089 2858 (2,500)
(3,150)
Total Suspended Solids (mg/t) 93 116 (300)
(600) pH Average: 8.1 Minimum:
6.8
(> 6.0)
(> 6.0) r The daily maximum quantity of 919 pounds for nitrate (N) exceeded the 875 pound limit on October 19, 1993. After receipt of verified sampling results on October 20,'1993, verbal notification was made on October 21,1993 and written notification on October 27,1993.