ML20058B167

From kanterella
Jump to navigation Jump to search

Talen Energy Presentation Slides Susquehanna Steam Electric Station Pre-Application Meeting of February 27, 2020 License Amendment Request to Create an Action for an Inoperable Manual Synchronization Circuit
ML20058B167
Person / Time
Site: Susquehanna  
Issue date: 02/27/2020
From:
Talen Energy
To:
Division of Operating Reactor Licensing
Goetz, Sujata
References
Download: ML20058B167 (8)


Text

Susquehanna Steam Electric Station Pre-Application Meeting February 27, 2020 License Amendment Request to Create an Action for an Inoperable Manual Synchronization Circuit

Meeting Purpose

  • Describe a future license amendment request
  • Establish a common understanding of the scope of the request
  • Establish a common understanding of the schedule
  • Obtain NRC feedback

© Talen Energy 2

Proposed Changes

  • Creation of a new Condition, Required Action, and Completion Time in LCO 3.8.1

© Talen Energy 3

Reason for Proposed Change

  • Circuit is shared by all DG, 4.16 kV, and 13.8 kV ESS buses on both units
  • Required Action is not commensurate with the overall risk of the Condition

© Talen Energy 4

Basis for the Proposed Change

  • Automatic transfer and loading capabilities are not impacted by inoperable circuit

- All analysis assumptions in Chapters 6 and 15 of the FSAR remain valid

  • There is no conflict between manual synchronization circuit and automatic transfer logic for representative situations

© Talen Energy 5

Basis for the Proposed Change (cont.)

- Uncredited function (RCIC and manual transfers) is lost

- Credited function (HPCI and automatic transfers) remains unaffected

© Talen Energy 6

Summary

  • Automatic transfer capabilities maintained with inoperable circuit
  • Completion Time commensurate with RCIC
  • Expect to submit by early April 2020

© Talen Energy 7

List of Acronyms 10 CFR - Title 10, Code of Federal Regulations DG - Diesel Generator ESS - Emergency Safeguard System FSAR - Updated Final Safety Analysis Report HPCI - High Pressure Coolant Injection kV - Kilovolt LCO - Limiting Condition for Operation RCIC - Reactor Core Isolation Cooling

© Talen Energy 8