Amend 86 to License NPF-38,revising TS by Adding Footnote to Containment Isolation Valves 3/4 3.6.3 Requirements
ML20057E047
Person / Time
Site: Waterford 
Issue date: 10/01/1993
From: Adensam E
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20057E048 List:
References
NUDOCS 9310070181
Download: ML20057E047 (5)


Text

....

l p arag

'4\\

UNITED STATES 8

?>

NUCLEAR REGULATORY COMMISSION

(-

~j WASHINGTON, D.C. 20b554001

%,...../

I ENTERGY OPERATIONS. INC.

DOCKET NO. 50-382 WATERFORD STEAM ELECTRIC STATION. UNIT 3 AMENDMENT TO FACILITY OPERATING LICENSE

{

Amendment No. 86 License No. NPF-38 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Entergy Operations, Inc. (the licensee) dated September 30, 1993, as corrected by letter dated October 1, 1993, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by j

this amendment can be conducted without endangering the health and i

safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

9310070181 931001 PDR ADDCK 0D000382 p

PDR

2.

Accordingly, the license is amanded by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. NPF-38 is hereby amended to read as follows:

(2) Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 86, and the Environmental Protection Plan contained in Appendix 8, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION 4A A

Elinor G. Adensam, Assistant Director for Region IV & V Reactors Division of Reactor Projects - III/IV/V Office of Nuclear Reactor Regulation

Attachment:

I Changes to the Technical Specifications Date of Issuance: October I, 1993 i

l 1

i j

ATTACHMENT TO LICENSE AMENDMENT NO. 86 TO FACILITY OPERATING LICENSE NO. NPF-38 DOCKET NO. 50-382 Replace the following page of the Appendix A Technical Specifications with the attached page.

The revised page is identified by Amendment number and contain vertical lines indicating the areas of change. The corresponding overleaf page is also provided to maintain document completeness.

i REMOVE PAGE INSERT PAGE 3/4 6-19 3/4 6-19 P

T I

i I

i

m

/

1 j

CONTAINMENT SYSTEMS 3/4.6.3 CONTAINMENT isolation VALVES j

i LIMITING CONDITION FOR OPERATION l

3.6.3 Each containment isolation valves shall be OPERABLE.

  • i APPLICABILITY; MODES 1, 2, 3, and 4.

ACTION:

With one or more of the isolation valve (s) inoperable, maintain at least one isolation valve OPERABLE in each affected penetration that is open and either:

a.

Restore the inoperable valve (s) to OPERABLE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, or b.

Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> by use of at least one deactivated automatic valve secured in the isolation position, or c.

Isolate each affected pen'etration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> by u n of at least one closed manual valve or blind flange; or d.

Be in at least fl0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i provisions of Specification 3.0.4 do not apply.

1 Locked or sealed closed valves may be opened on an intermittent basis under administrative control.

f Containment Sorav Valves CS-125 A and/or B may be left in the Ocen oosition trnt11 startvo (orior to enterina Mode di followina Refuelino Outace 6.

SURVEILLANCE REQUIREMENTS 4.6.3.1 Each contain:rrent isolation valve shall be demonstrated OPERABLE prior to returning the valve to service after maintenance, repair or replacement work is performed on the valve or its associated actuator, control or power circui? Sy performs.nce of a cycling test and verification of isolation time.

WATERFORP - UNIT 3 3/46-19 AMENDMENT NO. 86 8

4 e

t CONTAINMENT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4.6.3.2 Each containment isolation valve shall be demonstrated OPERABLE at

'l least or.ce per 18 months by:

a.

Verifying that on a containment isolation test signal, each isolation valve actuates to its isolation position.

b.

Verifying that on a containment Radiation-High test signal, each containment purge valve actuates to its isolation position.

4.6.3.3 The isolation time of each power-operated or automatic containment isolation valve shall be determined to be within its limit when tested pursuant to Specification 4.0.5.

l i

WATERFORD - UNIT 3 3/4 6-20 Amendment No.J5