Mr. Tom O'Hara Yankee Atomic Electric Company l
508 Main Street Bolton, MA 01740 i
Dear Tom:
i l
2 Attached are the peak ground acceleration and spectral values you requested in your letter of July 14, 1993 for the New England sites (Haddam Neck, Maine Yankee, Millstone, Pilgrim, Seabrook, Vermont Yankee, Yankee Rowe). These probabilistic hazard estimates were developed by Lawrence Livermore National Laboratory (LLNL) in July 1993. We are developing a NUREG report which will summarize the 1992/1993 LLNL probabilistic hazard work performed for the Office of Nuclear Reactor Regulation. The probabilistic hazard results for l
each nuclear power plant site in the eastern U.S. will be included in the report as tables of data.
If you have any questions about the attached data please call me at 301-504-2738.
I Sincerely,
{
l Original 5 gned try i
Phyllis Sobel, Geophysicist Civil Engineering and Geosciences Branch i
1 i
~
t j
Attachment:
Hazard estimates i
l DISTRIBUTION:
PSobel RRothman GBagchi j
ECGB R/F Central File PDR
')
l ECGB:DE. - ECGB:DC l
PSobel/+
RRot
'ewdv ?
/g'7(~defe/;y c
" '4 9/ 8 /93 9/ T q
C j
i (bAc )
(,;
.t,f n , ' 10
- )
i I
uJ I
J I!!YCTS ptt & p
-JJ,7 k 9309160032 930908 "i Ml-djP i
^~
(
PDR ADOCK O$000029 P
t
%s l
t SEP 0 81993 l
Mr. Tom O'Hara i
Yankee Atomic Electric Company l
508 Main Street Bolton, MA 01740
Dear Tom:
l l
Attached are the peak ground acceleration and spectral values you requested in your letter of July 14, 1993 for the New England sites (Haddam Neck, Maine Yankee, Millstone, Pilgrim, Seabrook, Vermont Yankee, Yankee Rowe).
These probabilistic hazard estimates were developed by Lawrence Livermore National l
Laboratory (LLNL) in July 1993. We are developing a NUREG report which will summarize the 1992/1993 LLNL probabilistic hazard work performed for the l
Of fice of Nuclear Reactor Regulation. The probabilistic hazard results for each nuclear power plant site in the eastern U.S. will be included in the i
report as tables of data.
If you have any questions about the attached data please call me at 301-504-2738.
{
l 1
I Sincerely, Odginal signed by Phyllis Sobel, Ceophysicist Civil Engineering and Geosciences Branch I
l
Attachment:
Hazard estimates DISTRIBUTION:
PSobel RRothman GBagchi ECGB R/F Central File PDR ECGB:DE ECGP:DE,I RRotf.,'()
o PSobeld.
1 9/ET/93 9/SI/9 4
o
l 1993 LLNL HAZARD ESTIMATES FOR PEAK ACCELERATION i
Haddam Neck acceleration best estimate arithmetic geometric (cm/sec/sec) 0.5000E+02 0.6562E-03 0.1114E-02 0.5097E-03 0.7500E+02 0.3514E-03 0.6349E-03 0.2660E-03 0.1500E+03 0.1036E-03 0.2085E-03 0.7506E-04 0.2500E+03 0.3437E-04 0.7697E-04 0.2371E-04 0.3000E+03 0.2178E-04 0.5146E-04 0.1467E-04 0.4000E+03 0.9773E-05 0.2577E-04 0.6282E-05 0.5000E+03 0.4861E-05 0.1435E-04 0.2985E-05 O.6500E+03 0.1947E-05 0.6817E-05 0.lll8E-05 0.8000E+03 0.8748E-06 0.3624E-05 0.4700E-06 0.1000E+04 0.3421E-06 0.1762E-05 0.1682E-06 acceleration 0.15 0.50 0.85 0.5000E+02 0.1380E-03 0.5170E-03 0.2010E-02 0.0000E+00 0.0000E+00 0.7500E+02 0.6520E-04 0.2690E-03 0.ll30E-02 0.0000E+00 0.0000E+00 0.1500E+03 0.1740E-04 0.7630E-04 0.3760E-03 0.0000E+00 0.0000E+00 0.2500E+03 0.4760E-05 0.2490E-04 0.1350E-03 0.0000E+00 0.0000E+00 0.3000E+03 0.2760E-05 0.1550E-04 0.8830E-04 0.0000E+00 0.0000E+00 j
0.4000E+03 0.1000E-05 0.6880E-05 0.4340E-04 0.0000E+00 0.0000E+00 O.5000E+03 0.4020E-06 0.3340E-05 0.2350E-04 0.0000E+00 0.0000E+00 0.6500E+03 0.1210E-06 0.1360E-05 0.1080E-04 0.0000E+00 0.0000E+00 0.8000E+03 0.4020E-07 0.6080E-06 0.5750E-05 0.0000E+00 0.0000E+00 0.1000E+04 0.ll20E-07 0.2330E-06 0.2470E-05 0.0000E+00 0.0000E+00 Maine Yankee acceleration best estimate arithmetic geometric O.5000E+02 0.9317E-03 0.1328E-02 0.6177E-03 0.7500E+02 0.4840E-03 0.7214E-03 0.3156E-03 0.1500E+03 0.1390E-03 0.2230E-03 0.8722E-04 0.2500E+03 0.4629E-04 0.8094E-04 0.2782E-04 0.3000E+03 0.2951E-04 0.5414E-04 0.1740E-04 0.4000E+03 0.1342E-04 0.2733E-04 0.7636E-05 0.5000E+03 0.6768E-05 0.1540E-04 0.3727E-05 0.6500E+03 0.2762E-05 0.7462E-05 0.14 51 E-05 0.8000E+03 0.1260E-05 0.4047E-05 0.6324E-06 0.1000E+04 0.5005E-06 0.2019E-05 0.2363E-06 acceleration 0.15 0.50 0.85
+
0.5000E402 0.1490E-03 0.7040E-03 0.2290E-02 0.0000E+00 0.0000E+00 0.7500E402 0.7430E-04 0.3480E-03 0.1270E-02 0.0000E400 0.0000E+00 j
0.1500E+03 0.1730E-04 0.9750E-04 0.4000E-03 0.0000E+00 0.0000E+00
~
0.2500E+03 0.4910E-05 0.3220E-04 0.1470E-03 0.0000E+00 0.0000E+00 O.3000E+03 0.2950E-05 0.2010E-04 0.9550E-04 0.0000E+00 0.0000E+00 l
0.4000E+03 0.ll50E-05 0.9120E-05 0.4770E-04 0.0000E+00 0.0000E+00 0.5000E+03 0.4780E-06 0.4620E-05 0.2670E-04 0.0000E+00 0.0000E+00 0.6500E+03 0.1650E-06 0.1910E-05 0.1240E-04 0.0000E+00 0.0000E+00 0.8000E+03 0.5900E-07 0.8840E-06 0.6440E-05 0.0000E+00 0.0000E+00 0.1000E+04 0.1670E-07 0.3580E-06 0.3110E-05 0.0000E400 0.0000E+00 1
i
-,,v
~ _ _
i
)
Millstone acceleration best estimate arithmetic geometric 0.5000E+02 0.6550E-03 0.9965E-03 0.4668E-03 0.7500E+02 0.3612E-03 0.5635E-03 0.2482E-03 O.1500E+03 0.ll21E-03 0.1823E-03 0.7203E-04 2
0.2500E+03 0.3800E-04 0.6635E-04 0.2302E-04 O.3000E+03 0.2412E-04 0.4410E-04 0.1427E-04 0.4000E+03 0.1077E-04 0.2189E-04 0.6117E-05 l
0.5000E+03 0.5307E-05 0.1211E-04 0.2906E-05 0.6500E+03 0.2093E-05 0.5713E-05 0.1087E- 05 5
0.8000E+03 0.9267E-06 0.3025E-05 0.4560f-06 0.1000E+04 0.3566E-06 0.1469E-05 0.1629E-06 i
acceleration 0.15 0.50 0.85 l
1 0.5000E+02 0.ll80E-03 0.4890E-03 0.1720E-02 0.0000E+00 0.0000E+00 0.7500E+02 0.6000E-04 0.2590E-03 0.9750E-03 0.0000E+00 0.0000E+00 I
O.1500E+03 0.1500E-04 0.7570E-04 0.3130E-03 0.0000E+00 0.0000E+00 O.2500E+03 0.4360E-05 0.2500E-04 0.ll60E-03 0.0000E+00 0.0000E+00 0.3000E+03 0.2540E-05 0.1560E-04 0.7580E-04 0.0000E+00 0.0000E+00 O.4000E+03 0.1000E-05 0.6700E-05 0.3790E-04 0.0000E+00 0.0000E+00 l
0.5000E+03 0.4050E-06 0.3350E-05 0.2040E-04 0.0000E+00 0.0000E+00 0.6500E+03 0.1290E-06 0.1350E-05 0.9180E-05 0.0000E+00 0.0000E+00 i
0.8000E+03 0.4440E-07 0.6070E-06 0.4650E-05 0.0000E+00 0.0000E+00 0.1000E404 0.1220E-07 0.2430E-06 0.2180E-05 0.0000E+00 0.0000E+00 l
Pilgrim acceleration best estimate arithmetic geometric O.5000E+02 0.1853E-02 0.2814E-02 0.1025E-02 0.7500E+02 0.1044E-02 0.1777E-02 0.5763E-03 0.1500E+03 0.3403E-03 0.7154E-03 0.1865E-03
)
O.2500E+03 0.1312E-03 0.3272E-03 0.6917E-04 0.3000E+03 0.8979E-04 0.2410E-03 0.4628E-04 i
0.4000E+03 0.4653E-04 0.1441E-03. 0.2297E-04
{
0.5000E+03 0.2628E-04 0.9379E-04 0.1248E-04 O.6500E+03 0.1239E-04 0.5446E-01 0.5577E-05 0.8000E+03 0.6381E-05 0.3430E-04 0.2733E-05 0.1000E+04 0.2909E-05 0.2016E-04 0.ll69E-05 i
acceleration 0.15 0.50 0.85 i
0.5000E+02 0.2400E-03 0.1090E-02 0.4520E-02 0.0000E+00 0.0000E400 t
0.7500E402 0.1210E-03 0.6110E-03 0.2820E-02 0.0000E+00 0.0000E400 l
0.1500E+03 0.3260E-04 0.1990E-03 0.1060E-02 0.0000E+00 0.0000E+00 0.2500E+03 0.9780E-05 0.7750E-04 0.4510E-03 0.0000E+00 0.0000E+00
[
0.3000E+03 0.6530E-05 0.5320E-04 0.3320E-03 0.0000E+ 00 0.0000E+00 0.4000E+03 0.2830E-05 0.2800E-04 0.2000E-03 0.0000E+00 0.0000E+00 O.5000E+03 0.131CE-05 0.1680E-04 0.1250E-03 0.0000E+00 0.0000E+00 i
0.6500E+03 0.4650E-06 0.7930E-05 0.6980E-04 0.0000E+00 0.0000E+00 l
l 0.8000E+03 0.1760E-06 0.4150E-05 0.4250E-04 0.0000E+00 0.0000E+00 l
0.1000E404 0.5780E-07 0.1970E-05 0.2330E-04 0.0000E+00_ 0.0000E+00
}
l f
i l
2 i
j 4
2 Seabrook t
i acceleration best estimate arithmetic geometric 0.5000E+02 0.1947E-02 0.2339E-02 0.9805E-03 O.7500E402 0.1090E-02 0.1372E-02 0.5399E-03 0.1500E+03 0.3351E-03 0.4617E-03 0.1628E-03 i
0.2500E+03 0.1134E-03 0.1714E-03 0.5363E-04 0.3000E403 0.7239E-04 0.1147E-03 0.3376E-04 0.4000E+03 0.3285E-04 0.5739E-04 0.1493E-04 0.5000E+03 0.1646E-04 0.3188E-04 0.7314E-05 4
0.6500E+03 0.6632E-05 0.1504E-04 0.2853E-05 0.8000E+03 0.2978E-05 0.7923E-05 0.1242E-05 0.1000E+04 0.ll56E-05 0.3797E-05 0.4625E-06 acceleration 0.15 0.50 0.85 0.5000E+02 0.2160E-03 0.1080E-02 0.4070E-02 0.0000E400 0.0000E+00 0.!600E+02 0.1130E-03 0.5930E-03 0.2460E-02 0.0000E+00 0.0000E+00 O.1500E+03 0.3110E-04 0.1820E-03 0.8140E-03 0.0000E+00 0.0000E+00 i
0.2500E+03 0.9240E-05 0.5820E-04 0.2930E-03 0.0000E+00 0.0000E+00 0.3000E+03 0.5240E-05 0.3590E-04 0.1920E-03 0.0000E+00 0.0000E400 0.4000E+03 0.2050E-05 0.1570E-04 0.9440E-04 0.0000E+00 0.0000E+00 0.5000E+03 0.9130E-06 0.7980E-05 0.5150E-04 0.0000Et00 0.0000E+00 0.6500E+03 0.3080E-06 0.3320E-05 0.2370E-04 0.0000E+00 0.0000E+00 0.8000E+03 0.1110E-06 0.1530E-05 0.1230E-04 0.0000E+00 0.0000E400 0.1000E+04 0.3280E-07 0.5780E-06 0.5480E-05 0.0000E+00 0.0000E+00 4
e Vermont Yankee l
l acceleration best estimate arithmetic geometric l
l 0.5000E+02 0.7363E-03 0.1293E-02 0.6769E-03 0.7500E+02 0.3518E-03 0.6738E-03 0.3237E-03 O.1500E403 0.8842E-04 0.1963E-03 0.7827E-04 0.2500E403 0.2737E-04 0.6913E-04 0.22642-04 0.3000E403 0.1709E-04 0.4583E-04 0.1368E-04 i
0.4000E403 0.7555E-05 0.2286E-04 0.5687E-05 I
i 0.5000E+03 0.3742E-05 0.1279E-04 0.2658E-05 l
O.6500E+03 0.1503E-05 0.6148E-05 0.9816E-06 l
0.8000E+03 0.6799E-06 0.3315E-05 0.4094E-06 l
j 0.1000E+04 0.2693E-06 0.1644E-05 0.1457E-06 i
acceleration 0.15 0.50 0.85 0.5000E+02 0.2040E-03 0.7060E-03 0.2040E-02 0.0000E+00 0.0000E+00 j
0.7500E+02 0.9150E-04 0.3310E-03 0.1040E-02 0.0000E+00 0.0000E+00 i
O.1500E+03 0.1990E-04 0.7680E-04 0.2920E-03 0.0000E+00 0.0000E+00 0.2500E+03 0.4870E-05 0.2320E-04 0.1010E-03 0.0000E400 0.0000E+00 l
0.3000E+03 0.2710E-05 0.1400E-04 0.6620E-04 0.0000E+00 0.0000E+00 0.4000E+03 0.9840E-06 0.6060E-05 0.3220E-04 0.0000E+00 0.0000E+00 0.5000E+03 0.3990E-06 0.3010E-05 0.1720E-04 0.0000E+00 0.0000E+00 0.6500E+03 0.1200E-06 0.1190E-05 0.7570E-05 0.0000E+00 0.0000E+00 0.8000E+03 0.4270E-07 0.5300E-06 0.3880E-05 0.0000E+00 0.0000E+00 0.1000E+04 0.1140E-07 0.2010E-06 0.1780E-05 0.0000E+00 0.0000E+00
)
i I
i 3
l
, _ =
Yankee Rowe acceleration best estimate arithmetic geometric O.5000E+02 0.1038E-02 0.2297E-02 0.97'2E-03 0.7500E+02 0.5117E-03 0.1289E-02 0.4875E-03 i
0.1500E+03 0.1434E-03 0.4281E-03 0.1303E-03 0.2500E+03 0.5183E-04 0.1725E-03 0.4209E-04 i
0.3000E+03 0.3476E-04 0.1219E-03 0.2681E-04 0.4000E+03 0.1744E-04 0.6851E-04 0.1231E-04 0.500GE+03 0.9605E-05 0.4266E-04 0.6300E-05 0.6500E+03 0.4395E-05 0.2365E-04 0.2631E-05 0.8000E+03 0.2212E-05 0.1442E-04 0.1224E-05 s
0.1000E+04 0.9846E-06 0.8230E-05 0.4964E-06 acceleration 0.15 0.50 0.85 O.5000E+02 0.2390E-03 0.1010E-02 0.4040E-02 0.0000E+00 0.0000E+00 l
0.7500E+02 0.ll20E-03 0.5220E-03 0.2310E-02 0.0000E+00 0.0000E400 i
0.1500E+03 0.2260E-04 0.1450E-03 0.6990E-03 0.0000E+00 0.0000E+00 0.2500E+03 0.6100E-05 0.4910E-04 0.2670E-03 0.0000E+00 0.0000E+00 0,3000E+03 0.3510E-05 0.3210E-04 0.1900E-03 0.0000E+00 0.0000E+00 0.4000E+03 0.1310E-05 0.1550E-04 0.1040E-03 0.0000E+00 0.0000E+00 0.5000E+03 0.5460E-06 0.8180E-05 0.6290E-04 0.0000E+00 0.0000E+00 0.6500E+03 0.1700E-06 0.3610E-05 0.3380E-04 0.0000E400 0.0000E+00 0.8000E+03 v.6530E-07 0.1800E-05 0.1970E-04 0.0000E+00 0.0000E+00 0.1000E404 0.2270E-07 0.7790E-06 0.1080E-04 0.0000E+00 0.0000E+00 i
e P
l I
(
i 4
2
l l
1993 LLNL SPECTRAL HAZARD ESTIMATES VARIABLE IS SPECTRAL VELOCITY (CM/SEC) velocity spectra frequency best estimate arithmetic geometric mean mean return period 0.5000E+03 0.1000E+01 0.8114E400 0.1616E+01 0.9471E+00 0.2500E+01 0.1043E+01 0.1956E+01 0.1032E+01 l
0.5000E+01 0.8373E+00 0.1542E+01 0.8402E+00 0.1000E+02 0.5162E400 0.8918E400 0.4776E+00 i
O.2500E+02 0.2121E+00 0.3284E+00 0.1875E+00 return period 0.1000E+04 0.1000E+01 0.1204E+01 0.2779E+01 0.1317E+01 0.2500E+01 0.1517E401 0.3551E+01 0.1515E+01 0.5000E+01 0.1299E401 0.2663E+01 0.1301E+01 0.1000E+02 0.9324E+00 0.1482E+01 0.8425E+00 0.2500E+02 0.3682E+00 0.6002E+00 0.3093E+00 return period 0.2000E+04 0.1000E+01 0.1654E+01 0.4780E+01 0.1789E+01 0.2500E+01 0.2208E+01 0.6098E+01 0.2224E+01 0.5000E401 0.1898E+01 0.4598E+01 0.1889E+01 0.1000E+02 0.1449E401 0.2377E+01 0.1313E+01 0.2500E+02 0.6393E400 0.1059E+01 0.5100E+00 return period 0.5000E+04 1
0.1000E+01 0.2519E+01 0.9121E+01 0.2680E+01 1
0.2500E+01 0.3625E+01 0.ll29E+02 0.3694E+01 i
0.5000E401 0.3135E+01 0.7864E+01 0.3094E+01 i
0.1000E+02 0.2528E+01 0.4027E+01 0.2199E+01 l
j O.2500E+02 0.1194E+01 0.1738E+01 0.9882E400 i
i return period 0.1000E+05 l
0.1000E401 0.3461E+01 0.1399E+02 0.3638E+01 1
0.2500E+01 0.5201E+01 0.1798E+02 0.5285E+01 l
0.5000E+01 0.4581E+01 0.ll59E+02 0.4494E+01 0.1000E402 0.3603E+01 0.5745E+01 0.3177E+01 0.2500E402 0.1687E+01 0.2528E+01 0.1315E+01 i
i results for the 3 percentiles:
i i
freq. (hz) 0.150**
0.500**
0.850**
j return period 0.5000E403 1.00 0.397E+00 0.103E+01 0.248E+01 1
2.50 0.391E+00 0.ll2E+01 0.312E+01 5.00 0.325E+00 0.921E+00 0.232E401 j
10.00 0.202E+00 0.508E+00 0.134E+01 j
25.00 0.713E-01 0.201E+00 0.537E+00 i
return period 0.1000E+04 1.00 0.620E+00 0.142E401 0.420E+01 2.50 0.623E+00 0.162E+01 0.534E+01 5.00 0.515E400 0.137E401 0.388E401 1
10.00 0.320E+00 0.895E+00 0.218E+01 i
25.00 0.127E+00 0.330E400 0.995E+00 1
5 f
I
l i
return period 0.2000E+04 1.00 0.967E+00 0.195E+01 0.708E+01 2.50 0.992F+00 0.236E401 0.801E+01 5.00 0.817E+00 0.197E+01 0.598E+01 l
10.00 0.508E+00 0.138E+01 0.339E+01 25.00 0.200E+00 0.543E+00 0.145E+01 return period 0.5000E+04 1.00 0.131E+01 0.299E+01 0.116E+02 2.50 0.147E+01 0.388E+01 0.137E+02 5.00 0.131E401 0.320E+01 0.952E+01 l
10.00 0.933E400 0.233E+01 0.541E+01 i
25.00 0.365E+00 0.103E+01 0.238E+01 return period 0.1000E+05 1.00 0.163E+01 0.413E+01 0.168E+02 2.50 0.197E+01 0.547E+01 0.205E+02 5.00 0.177E401 0.461E+01 0.135E+02 10.00 0.134E+01 0.333E+01 0.772E+01 25.00 0.575E+00 0.141E+01 0.328E+01 j
i i
e i
I i
j l
i i
I i
i b
6
l 4
Maine Yankee velocity spectra 1
frequency best estimate arithmetic geometric mean mean return period 0.5000E403 0.1000E+01 0.1252E+01 0.1913E+01 0.ll66E+01 0.2500E+01 0.1430E+01 0.2239E+01 0.1264E+01 0.5000E+01 0.ll74E+01 0.1708E+01 0.1050E+01 O.1000E+02 0.7272E+00 0.1008E+01 0.5829E+00 0.2500E402 0.2811E+00 0.3562E+00 0'.2158E+00 return period 0.1000E+04 0.1000E401 0.1721E401 0.3111E401 0.1598E+01 0.2500E+01 0.2056E+01 0.3808E+01 0.1826E+01 0.5000E+01 0.1683E+01 0.2783E+01 0.1501E+01 0.1000E+02 0.1201E401 0.1549E+01 0.9992E+00 0.2500E+02 0.4726E400 0.6096E400 0.3482E+00 4
return period 0.2000E+04 0.1000E+01 0.2365E401 0.5059E+01 0.2190E+01 0.2500E401 0.2956E+01 0.6157E+01 0.2639E+01 0.5000E401 0.2414E+01 0.4537E+01 0.2147E+01 0.1000E402 0.1795E401 0.2379E+01 0.1458E+01 0.2500E402 0.7945E+00 0.1029E+01 0.5620E+00 return period 0.5000E+04 0.1000E401 0.3601E+01 0.9039E+01 0.3322E+01 3
J 0.2500E401 0.4776E401 0.1083E+02 0.4295E+01 j
0.5000E+01 0.3887E+01 0.7516E401 0.3445E+01 0.1000E402 0.3040E+01 0.3907E+01 0.2402E+01 0.2500E402 0.1359E+01 0.1649E401 0.1035E401 l
return period 0.1000E+05 5
0.1000E+01 0.4949E+01 0.1336E+02 0.4553E+01 0.2500E401 0.6329E+01 0.1661E+02 0.5837E+01 i
0.5000E+01 0.5400E401 0.1081E402 0.4927E+01 0.1000E+02 0.4141E+01 0.5478Et01 0.3372E+01 0.2500E+02 0.1928E401 0.2356E401 0.1390E+01 results for the 3 percentiles:
freq. (hz) 0.150**
0.500**
0.850**
return period 0.5000E+03 1.00 0.569E+00 0.119E+01 0.264E+01 2.50 0.582E400 0.131E+01 0.316E+01 5.00 0.451E+00 0.109E+01 0.232E+01 10.00 0.260E+00 0.620E+00 0.143E+01 25.00 0.103E+00 0.234E400 0.558E+00 return period 0.1000E+04 1.00 0.931E400 0.166E401 0.415E+01 2.50 0.965E+00 0.189E401 0.513E+01 5.00 0.720E+00 0.156E401 0.366E401 10.00 0.412E400 0.105E401 0.222E+01 25.00 0.157E+00 0.382E+00 0.957E+00 7
l return period 0.2000E+04 1.00 0.123E+01 0.231E+01 0.651E+01 2.50 0.132 E401 0. 275E+01 0. 763 E+01 5.00 0.110E+01 0.223E+01 0.557E+01 10.00 0.652E+00 0.154E+01 0.333E+01 25.00 0.240E+00 0.623E+00 0.139E+01 return period 0.5000E+04 3
l.00 0.171E+01 0.359E+01 0.103E+02
{
2.50 0.195E+01 0.448E+01 0.129E+02 5.00 0.164E+01 0.357E+01 0.874E+01 10.00 0.ll5E+01 0.255E+01 0.520E+01 25.00 0.422E400 0.112E+01 0.224E+01 return period 0.1000E+05 j
l.00 0.219E+01 0.500F401 0.143E+02 2.50 0.262E+01 0.604t+01 0.192E+02 5.00 0.222E+01 0.507E+01 0.123E402 10.00 0.164E+01 0.355E+01 0.730E401 25.00 0.646E+00 0.154E+01 0.313E401 t
f 1
i t
E 1
b i
i i
8
}
l t
I l
l Millstone l
3 velocity spectra frequency best estimate arithmetic geometric mean mean return period 0.5000E+03 0.1000E+01 0.7670E+00 0.1522E+01 0.8826E+00 i
0.2500E+01 0.1006E+01 0.1847E+01 0.9766E+00 l
0.5000E+01 0.8012E400 0.1472E+01 0.7900E+00 l
0.1000E+02 0.4976E+00 0.8501E+00 0.4550E400 0.2500E402 0.2067E+00 0.3180E+00 0.1819E+00 i
return period 0.1000E+04 0.1000E+01 0.1160E+01 0.2618E+01 0.1264E+01 i
j 0.2500E+01 0.1471E+01 0.3348E+01 0.1449E+01 0.5000E401 0.1270E+01 0.2540E+01 0.1256E+01 3
0.1000E+02 0.9095E+00 0.1435E+01 0.8040E+00 0.2500E+02 0.3682E+00 0.5833E+00 0.3051E+00 i
i l
return period 0.2000E+04 l
0.1000E+01 0.1592E+01 0.4503E+01 0.1714E+01 i
i 0.2500Ee01 0.2150E+01 0.5820E+01 0.2133E+01 O.5000E+01 0.1871E+01 9.4382E+01 0.1836E+01 l
1 0.1000E+02 0.1444E+01 0.2303E+01 0.1281E+01
~
0.2500E+02 0.6558E+00 0.1042E+01 0.5115E+00 l
j return period 0.5000E+04 O 1000E+01 0.2420E+01 0.8707E+01 0.2564E+01 0.2500E+01 0.3550E401 0.1076E+02 0.3554E+01 i
0.5000E+01 0.3125E401 0.7596E401 0.3033E+01 i
0.1000E402 0.2570E+01 0.3931E+01 0.2178E+01 i
O.2500E+02 0.1233 E+ 01 0.1708E+01 0.1007E+01 return period 0.1000E+05 l
0.1000E+01 0.3322Et01 0.1338E+02 0.3476E+01 j
0.2500E+01 0.5136E401 0.1714E+02 0.5155E+01 0.5000E401 0.4606E401 0.1119E+02 0.4434E+01 0.1000E+02 0.3665E+01 0.5601E+01 0.3177E+01 O.2500E+02 0.1758E+01 0.2481E+01 0.1340E+01 l
I i
l results for the 3 percentiles:
freq. (hz) 0.150**
0.500**
0.850**
l return period 0.5000E+03 1
1.00 0.388E400 0.965E+00 0.229E401 i
2.50 0.377E+00 0.105E+01 0.298E+01 l
5.00 0.318E+00 0.861E+00 0.222E+01 10.00 0.192E+00 0.488E+00 0.131E+01 25.00 0.683E-01 0.19)E+00 0.528E+00 return period 0.1000E+04 1.00 0.604E+00 0.134E+01 0.379E+01 3
2.50 0.600E+00 0.153E+01 0.516E401 5.00 0.509E+00 0.134E+01 0.368E401 L
10.00 0.309E+00 0.868E+00 0.210E+01 l
25.00 0.124E400 0.329E+00 0.977E+00
I return period 0.2000E+04 1.00 0.940E400 0.182E401 0.627E+01 2.50 0.957E400 0.225E+01 0.759E+01 5.00 0.814E+00 0.196E+01 0.572E+01 10.00 0.496E400 0.136E401 0.328E+01 25.00 0.195E400 0.550E+00 0.143E+01 return period 0.5000E+04 1.00 0.129E+01 0.273E+01 0.106E+02 2.50 0.144 E+ 01 0.373E+01 0.126E+ 02 5.00 0.131E+01 0.326E+01 0.901E+01 i
10.00 0.926E400 0.231E+01 0.521E401 25.00 0.355E400 0.105E401 0.233E+01 return period 0.1000E+05 l.00 0.160E+01 0.372E+01 0.153E+02 2.50 0.195E+01 0.533E+01 0.186E+02 i
5.00 0.177E+01 0.479E+01 0.127E+02 l
10.00 0.134E+01 0.333E+01 0.740E401 l
25.00 0.558E+00 0.145E+01 0.323E+01 i
l i
i f
l i
t f
i
{
10 l
l l
i L
~
1 l
l 1
l l
Pilgrim j
velocity spectra frequency best estimate arithmetic geometric
)
mean mean i
return period 0.5000E+03 0.1000E+01 0.1169E+01 0.2291E+01 0.1112E+01 l
0.2500E401 0.2176E+01 0.3965E+01 0.1739E+01 0.5000E+01 0.1769E401 0.3235E+01 0.1411E+01 0.1000E+02 0.1197E+01 0.1723E+01 0.8197E+00 O.2500E+02 0.4384E+00 0.6941E+00 0.2823E+00 l
return period 0.1000E+04 0.1000E+01 0.1619E+01 0.4057E+01 0.1551E+01 4
0.2500E+01 0.3400E+01 0.6964E+01 0.2725E+01 0.5000E+01 0.2737E+01 0.5768E+01 0.2203E+01 O.1000E+02 0.1902E+01 0.3027E+01 0.1374E+01 0.2500E402 0.8284E+00 0.1276E+01 0.5121E+00 return period 0.2000E+04 0.1000E+01 0.2242E+01 0.7144E+01 0.2162E+01 0.2500E+01 0.5211E+01 0.1164E+02 0.4270E+01 0.5000E+01 0.4236E+01 0.9139E+01 0.3438E+01 0.1000E+02 0.3016E+01 0.4658E+01 0.2162E+01 0.2500E+02 0.1338E+01 0.2056E+01 0.9290E+00 return period 0.5000E+04 l
0.1000E+01 0.3447E+01 0.1290E+02 0.3355E+01 i
0.2500E+01 0.7798E+01 0.2267E+02 0.6821E401 0.5000E+01 0.6568E+01 0.1679E+02 0.5744E401 O.1000E402 0.4797E+01 0.8234E+01 0.3672E+01 0.2500E+02 0.2313E+0!
0.3627E+01 0.1528E+01 return period 0.1000E+05 0.1000E401 0.4773E+01 0.2017E+02 0.4677E+01 0.2500E+01 0.1058E+02 0.3471E+02 0.9395E+01 0.5000E+01 0.8774E+01 0.2551E+02 0.7663E+01 O.1000E+02 0.6813E+01 0.ll89E+02 0.5145E+01 0.2500E+02 0.3274E401 0.5189E+01 0.2176E+01 results for the 3 percentiles:
i freq. (hz) 0.150**
0.500**
0.850**
return period 0.5000E+03 1.00 0.460E400 0.118E401 0.355E+01 l
2.50 0.700E+00 0.188E+01 0.651E+01 5.00 0.512E400 0.160E+01 0.491E+01 10.00 0.269E+00 0.907E+00 0.262E+01 25.00 0.969E-01 0.317E+00 0.lllE+01 return period 0.1000E+04 l
1.00 0.740E+00 0.168E+01 0.603E+01 4
2.50 0.ll3E401 0.296E+01 0.103E402 5.00 0.888E400 0.253E+01 0.728E+01 10.00 0.458E+00 0.147E+01 0.411E+01 25.00 0.159E+00 0.585E+00 0.177E+01 i
11 I
a
._-. -_._-=-...
i I
i i
return period 0.2000E+04 l.00 0.110E+01 0.239E401 0.907 E401 2.50 0.158E+01 0.467E+01 0.163E+02
{
I 5.00 0.132E401 0.400E+01 0.107E+02 10.00 0.777E+00 0.229E+01 0.625E+01 l
25.00 0.258E400 0.105E+01 0.282E+01 return period 0.5000E+04 I
i 1.00 0.153E+01 0.380E+01 0.146E+02 I
3 2.50 0.248E+01 0.735E+01 0.273E+02 i
5.00 0.210E+01 0.644E+01 0.179E+02 10.00 0.138E+01 0.389E+01 0.105E+02 25.00 0.490E+00 0.176E+01 0.434E+01 l
l return period 0.1000E+05 1.00 0.197E+01 0.540E+01 0.209E+02 2.50 0.348E+01 0.102E+02 0.377E+02 5.00 0.300E+01 0.874E+01 0.255E+02 l
10.00 0.203E+01 0.558E+01 0.146E+02 25.00 0.794E+00 0.260E+01 0.592E+01 2
l i
I i
I i
i l
i I
i I
I l
1 i
i l
r i
12 i
l I
i
l i
Seabrook i
velocity spectra frequency best estimate arithmetic geometric mean mean i
0.1000E+01 0.1290E+01 0.2025E+01 0.1134E+01 return period 0.5000E+03 0.2500E+01 0.1709E+01 0.2586E+01 0.1270E+01 3
0.5000E+01 0.1516E+ 01 0.2073E+01 0.1103E+01 d
0.1000E+02 0.1175E+01 0.1282E+01 0.6670E400 0.2500E+02 0.4716E+00 0.5120E+00 0.2510E+00 return period 0.1000E+04 0.1000E+01 0.1830E+01 0.3520E+01 0.1587E+01 0.2500E+01 0.2622E+01 0.4777E+01 0.1919E+01 i
l 0.5000E+01 0.2303E+01 0.3613E+01 0.1654E+01 O.1000E+02 0.1848E+01 0.2075E+01 0.1163E+01 0.2500E+02 0.8925E+00 0.9948E+00 0.4406E+00 i
return period 0.2000E+04 0.1000E+01 0.2596E+01 0.6118E+01 0.2222E+01 0.2500E+01 0.4024E+01 0.7629E+01 0.2900E+01 0.5000E+01 0.3500E+01 0.5833E+01 0.2480E+01 0.1000E+02 0.2905E401 0.3250E+01 0.1779E+01 4
O.2500E+02 0.1337E+01 0.1436E401 0.7735E400 return period 0.5000E+04 0.1000E+01 0.4122E+01 0.1096E+02 0.3468E+01 I
0.2500E+01 0.6271E401 0.1395E+02 0.5003E+01 0.5000E+01 0.5633E+01 0.9532E+01 0.4236E+01 l
0.1000E+02 0.4445E+01 0.5112E+01 0.3085E+01 d
O.2500E+02 0.2134E401 0.2325E+01 0.1290E+01 return period 0.1000E405 0.1000E+01 0.5848E+01 0.1662E+02 0.4856E+01 0.2500E401 0.8280E+01 0.2184E402 0.6614E+01 0.5000E+01 0.7262E+01 0.1382E+02 0.5783E+01 i
0.1000E+02 0.6086E401 0.7200E+01 0.4150E+01 O.2500E402 0.3020E+01 0.3208E+01 0.1732E401 i
results for the 3 percentiles:
freq. (hz) 0.150**
0.500**
0.850**
i return period 0.5000E+03 i
8 1.00 0.511E+00 0.116E+01 0.282E+01 i
2.50 0.498E+00 0.133E+01 0.403E+01 5.00 0.399E+00 0.ll6E+01 0.303E+01 i
10.00 0.240E400 0.721E400 0.194E+01 25.00 0.812E-01 0.275E+00 0.916E+00 l
return period 0.1000E+04 1.00 0.831E+00 0.163E+01 0.464E+01 2.50 0.827E+00 0.199E+01 0.641E+01
]
5.00 0.644E+00 0.174E+01 0.510E+01 10.00 0.391E+00 0.123E+01 0.311E+01 i
25.00 0.143E400 0.485E+00 0.137E+01 13 1
i
-ww r-.
e
a 1
return period 0.2000E+04 l.00
- 0. ll8E+01 0.228E+01 0.745E+01 2.50 0.123 E+01 0.299E+01 0. 942E+01 5.00 0.103E+01 0.262E+01 0.718E+01 10.00 0.637E+00 0.187E+01 0.433E+01 25.00 0.235E+00 0.856E+00 0.196E+01 return period 0.5000E+04 1
1.00 0.167E+01 0.357E+01 0.119E+02 2.50 0.190E+01 0.507E+01 0.157E+02 5.00 0.160E401 0.448E+01 0.113 E+02 10.00 0.117E+01 0.319E+01 0.671E+01 l
25.00 0.457E+00 0.139E+01 0.310E+01 i
return period 0.1000E+05 1.00 0.218E+01 0.500E+01 0.169E+02 j
2.50 0.265E+01 0.669E+01 0.227E+02 5.00 0.224E+01 0.600E+01 0.159E+02 10.00 0.174E+01 0.431E+01 0.924E+01 4
25.00 0.754E+00 0.192E+01 0.390E+01 i
I l
l 1
1 l
i i
I I
i l
I i
i 1
i i
)
14 l
i
i 4
Vermont Yankee i
velocity spectra l
frequency best estimate arithmetic geometric 1
mean mean i
return period 0.5000E+03 0.1000E+01 0.1106E+01 0.2015E+01 0.ll71E+01 j
0.2500E+01 0.1303E+01 0.2438E+01 0.1310E+01 j
0.5000E+01 0.1087E+01 0.1834E+01 0.1115E401 1
0.1000E402 0.6464E400 0.1045E+01 0.6414E+00 O.2500E+02 0.2482E400 0.3625E+00 0.2336E400 i
return period 0.1000E+04
]
0.1000E+01 0.1495E+01 0.3306E+01 0.1594E401 O.2500E+01 0.1841E+01 0.4164E+01 0.1896E+01 i
0.5000E+01 0.1518E+01 0.2967E+01 0.1576E+01 1
0.1000E+02 0.1077E+01 0.1581E+01 0.1069E+01 0.2500E+02 0.3924E+00 0.5993E400 0.3625E+00 i
return peric. 0.2000E+04 i
0.1000E+01 0.2020E+01 0.5425E+01 0.2169E+01 l
l 0.2500E+01 0.2599E401 0.6610E+01 0.2743E+01 0.5000E+01 0.2118E+01 0.4799E+01 0.2228E+01 0.1000E+02 0.1548E+01 0.2392E+01 0.1521E+01 0.2500E402 0.6206E+00 0.9908E+00 0.5626E+00 return period 0.5000E+04 0.1000E+01 0.3007E+01 0.9615E+01 0.3261E401 0.2500E+01 0.4102E+01 0.1158E+02 0.4471E+01 0.5000E+01 0.3292E401 0.7837E+01 0.3521E+01 2
0.1000E402 0.2500E+01 0.3897E+01 0.2425E+01 l
0.2500E+02 0.1096E+01 0.1589E+01 0.1003E+01 return period 0.1000E+05 0.1000E+01 0.4064E+01 0.1425E+02 0.4438E+01 j
0.2500E+01 0.5579E+01 0.1769E+02 0.5965E+01 0.5000E401 0.4594E401 0.ll27E+02 0.4977E+01 i
0.1000E402 0.3467E401 0.5461E+01 0.3332E+01 0.2500E+02 0.1518E401 0.2267E401 0.1309E401 i
results for the 3 percentiles
~
freq. (hz) 0.150**
0.500**
0.850**
l return period 0.5000E+03 1.00 0.537E+00 0.120E401 0.329E+01 2.50 0.570E+00 0.137E401 0.430E+01 i
5.00 0.473E+00 0.ll4E+01 0.296E+01 10.00 0.284E+00 0.681E+00 0.159E+01 i
25.00 0.120E+00 0.242E+00 0.580E+00 l
return period 0.1000E+04 i
1.00 0.864E+00 0.166E+01 0.534E401 2.50 0.948E400 0.197E+01 0.673E+01 5.00 0.775E400 0,160E+01 0.481E+01 10.00 0.454E+00 0.ll2E+01 0.240E401 25.00 0.175E+00 0.381E+00 0.967E+00 15 I
l l
l return period 0.2000E+04 l.00 0.118E+01 0.229E+01 0.816E+01 i
]
2.50 0.130E+01 0.283E+01 0.101E+02 l
5.00 0.114E+01 0.225E+01 0.685E+01 10.00 0.725E+00 0.159E+01 0.347E+01 l
25.00 0.255E+00 0.598E+00 0.138E+01 4
return period 0.5000E+04 l
1.00 0.160E+01 0.351E+01 0.129E+02 l
2.50 0.192E+01 0.458E+01 0.173E+02 5.00 0.165E+01 0.351E+01 0.108E+02 l
10.00 0.121E+01 0.254E+01 0.530E401 l
25.00 0.421E400 0.105E+01 0.218E+01 return period 0.1000E+05 l
1.00 0.203E+01 0.486E+01 0.lF2E+02 i
2.50 0.259E+01 0.604E+01 0.244E+02 5.00 0.217E+01 0.493E+01 0.152E402 t'
10.00 0.163E+01 0.346E401 0.731E+01 25.00 0.614E+00 0.140E+01 0.306E+01 I
f i
1 j
t i
i i
I j
4 f
s f
16 i
y g,.- ~=,
-r,~
r,-y 4
1 Yankee Rowe velocity spectra frequency best estimate arithmetic geometric mean mean return period 0.5000E+03 0.1000E+01 0.1279E+01 0.2984E+01 0.1259E+01 2
0.2500E+01 0.2184E+01 0.5271E+01 0.2089E+01 0.5000E+01 0.1416E+01 0.3212E+01 0.1421E+01 O.1000E+02 0.7688E+00 0.1541E+01 0.7565E+00 0.2500E402 0.2944E+00 0.5362E+00 0.2779E400 i
return period 0.1000E404 0.1000E401 0.1752E+01 0.5136E401 0.1734E+01
)
0.2500E401 0.3234E+01 0.8592E+01 0.3182E+01 0.5000E+01 0.2022E+01 0.5444E+01 0.2072E+01 0.1000E+02 0.1222E+01 0.2465E+01 0.1211E+01 i
0.2500E+02 0.4723E+00 0.9442E+00 0.4450E+00 return period 0.2000E404 0.1000E401 0.2C1E401 0.8395E+01 0.2389E+01 0.2500E+01 0.4790E+01 0.1401E+02 0.4848E+01 O.5000E+01 0.2887E+01 0.8370E+01 0.3021E+01 l
0.1000E+02 0.1783E+01 0.3718E+01 0.1759E+01 l
0.2500E402 0.7578E+00 0.1421E+01 0.7126E+00 return period 0.5000E+04 O.1000E+01 0.3640E+01 0.1467E+02 0.3649E+01 O.2500E+01 0.7079E401 0.2598E+02 0.7222E401 f
0.5000E+01 0.4622E401 0.1478E+02 0.4973E401 f
0.1000E+02 0.2940E+01 0.6058E+01 0.2882E+01 i
0.2500E+02 0.1333E401 0.2381E+01 0.1186E+01 return period 0.1000E+05 O.1000E401 0.4986E401 0.2239E+02 0.5027E401 i
0.2500E+01 0.9430E+01 0.3921E+02 0.9694E+01 l
O.5000E+01 0.6187E+01 0.2243E+02 0.6397E401 0.1000E+02 0.4064E+01 0.8729E+01 0.3858E+01 I
0.2500E402 0.1970E+01 0.3414E401 0.1576E+01 l
I l
4 results for the 3 percentile;:
i j
freq. (hz) 0.150**
0.500**
0.850**
return period 0.5000E+03 1.00 0.485E+00 0.133E+01 0.473E+01 i
2.50 0.854E+00 0.227E401 0.815E+01 5.00 0.539E+00 0.148E+01 0.514E+01 3
10.00 0.283E+00 0.777E+00 0.213E+01 25.00 0.120E+00 0.296E+00 0.825E+00 I
return period 0.1000E+04 i
1.00 0.769E+00 0.186E+01 0.761E+01 2.50 0.126E401 0.348E401 0.130E+02 5.00 0.887E+00 0.219E401 0.729E+01 l
1 10.00 0.452E+00 0.123E+01 0.329E+01 3
25.00 0.182E400 0.477E+00 0.129E+01
)
17 l
e 5
y
.-.-.-.-.m.,_
_.,_y
..mm,
.m.
m
l-return period 0.2000E404 1.00 0.111E+01 0.259E+01 0.107E+02 2.50 0.175E401 0.522E401 0.206E+02 5.00 0.125E+01 0.325E401 0.103E+02 10.00 0.721E+00 0.180E+01 0.481E+01 l
25.00 0.278E+00 0.771E+00 0.192E401 return period 0.5000E404
)
1.00 0.152E401 0.400E+01 0.169E402 2.50 0.270E401 0.766E+01-0.322E+02 1
l 5.00 0.186E401 0.530E401 0.164E+02 10.00 0.123E+01 0.298E+01 0.794E+01 25.00 0.486E+00 0.128E+01 0.317E401 return period 0.1000E+05 1.00 0.193E401 0.558E+01 0.239E+02 2.50 0.375E+01 0.102E402 0.446E+02 5.00 0.251E+01 0.686E+01 0.227E402 i
10.00 0.171E+01 0.396E401 0.110E402 25.00 0.741E+00 0.175E401 0.424E401 i
i e
i i
p l
l 1
2 18 l
4 I
..