Amend 136 to License DPR-28,revising TS Table 4.2.5 Startup Range monitor/intermediate-range Monitor Surveillance Requirement for Detector Not Fully Inserted Trip Function by Replacing Note 6 Under Calibr,W/N/A
ML20056G238
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 08/25/1993
From: Butler W
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20056G239 List:
References
NUDOCS 9309020300
Download: ML20056G238 (4)


Text

fpa anc %

o n

G f E

UNITED STATES 4

5 i,.M -'~ /

NUCLEAR REGULATORY COMMISSION k../

WASHINGTON, D C. 20555-0001 VERMONT YANKEE NUCLEAR POWER CORPORATION DOCKET NO. 50-271 VERMONT YANKEE NUCLEAR POWER STATION AMENDMENT TO FACILITY OPERATING LICENSE I

Amendment No. 136 License No. DPR-28 l

1.

The Nut lear Regulatory Commission (the Commission or the NRC) has found that:

A.

The application for amendment filed by the Vermon! Yankee Nuclear Power Corporation (the licensee) dated December 15, 1992, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the i

Commission; C.

There is reasonable assurance:

(i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and 9

E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifica-f tions as indicated in the attachment to this license amendment, and paragraph 3.B of facility Operating License No. DPR-28 is hereby amended to read as follows:

l 930902c300 930825 PDR ADDCK 05000271 P

PDR

' Technical Specifications The Technical Specifications contained in Appendix A, as revised i

through Amendment No.136, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance and shall be implemented within 30 days.

FOR THE NUCLEAR REGULATORY COMMISSION f(s' i f

'!\\

+

w Walter R. Butler, Director Project Directorate I-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

August 25, 1993 t

i I

I

L 1

i F

ATTACHMENT TO LICENSE AMENDMENT NO.136 FACILITY OPERATING LICENSE NO. DPR-28 DOCKET NO. 50-271 Replace the following pages of the Appendix A Technical Specifications with the attached pages.

The revised pages are identified by Amendment number and contain vertical lines indicating the area of change.

Remove Insert t

59 59 t

N 5

I a

[

i i

p i

i L

1 VYNPS TABLE 4.2.5 MINIMUM TEST AND CAllBRATION FREQUENCIES CONTROL ROD BLOCK INSTRUMENTATION Trip Function Functional Test Calibration Startup Range Monitor a.

Upscale Notes 4 and 6 Note 6 b.

Detector Not Fully inserted Note 6 NA l

Intermediate Range Monitor a.

Upscale Notes 4 and 6 Note 6 b.

Downscale Notes 4 and 6 Note 6 l

c.

Detector Not fuily Inserted Note 6 NA Average Power Range Monitor a.

Upscale (Flow Slas)

Notes 1 and 4 Every Three Months b.

Downscale Notes 1 and 4 Every Three Months Rod Block Monitor a.

Upscale (Flow Bias)

Notes 1 and 4 Every Three Months b.

Downscale Notes 1 and 4 Every Three Months Trip System logic Once/ Operating Cycle Once/ Operating Cycle (Note 3)

High Water level in Scram Ever.y Three Months Refueling Outage Discharge Volune Amendment No. 106, 110, 136 59

_ _