CE Cammenw3 lth Edisen
-s 1400 Opus Place U
Downers Grove, Illinois 60515 August 23,1993 Dr. Thomas E. Murley, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Attn: Document Control Desk
Subject:
Zion Station Units 1 and 2 Updated Fire Protection Report NRC Docket Nos. 50-295 and 50-304
Reference:
(a)
April 29,1977 letter from R.L. Bolger to V. Stello (b)
September 15,1992 letter from S.F. Stimac to T.E. Murley (c)
August 5,1992 letter from S.F. Stimac to T.E. Murley
Dear Dr. Murley:
Commonwealth Edison (CECO) submitted the Zion Station Fire Protection Report via reference (a). Since that time, various aspects of the program have been updated and addressed through correspondence to and from NRC. The most recent of these updates was I
transmitted via reference (b). The purpose of this letter is to provide the most recent update to the Fire Protection Report.
The Fire Hazards Analysis (FHA). Volume 2, has been updated to reflect plant changes made through February 22,1993, the end of the Unit 2 Cycle 12 refueling outage. In addition, Volume 2 was updated to reflect the relocation of the UFSAR Fire Protection information to the FHA. Administrative changes were made to the NRC SER section of Volume 3.
Attachment A is a Change Log which describes the individual changes made to the FHA and SER, sections. Attachment B contains the replacement pages, new index and an instruction sheet for inserting the changes.
Please direct any questions to this oflice.
Sincerely, j
e T.W. Simpkin i
Nuclear Licensing Administrator Attachment cc:
J.B. Martin, Regional Administrator - RIII C.Y. Shiraki, Project Manager - NRR J.D. Smith, Senior Resident Inspector - Zion 33583bdO71 930823 7
0h PDR ADDCK 05000295 g 0
F PDR d
\\\\g\\
k:\\nla\\1tr-nrcz.wpf/24
r l
5 l
t l
l P
i r
i l
i i
l l
i 1
k i
I L
i Attachment A Change Log t
l l
l c
1 I
f l
i I
I i
I l
l l
\\
l I
l 1
l 20SR-053/93 0SR(3) 1 l
l l
August 5. 1993 Page 1 of 13 ZION FPR CHANGE LOG Rev. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-014 Vol. 2 Table of Add Table 1.1. " Fire Technical Impell Document No. 597-361-04 Contents Suppression Water System" 2-FHA-015 Vol. 2 Table of Added new Section 1.2.2 and Technical Impell Document No. 597-361-10 Contents renumbered sections and pages.
2-FHA -015 Vol. 2 Table of Added Figure 1-1. " Zion Technical Impell Document No. 597-361-10 Contents Station Fire Detection System" (3 pages).
2-FHA-014 Vol. 2. Section 1 Add Table 1.1. " Fire Technical Impell Document No. 597-361-04 Table of Contents Suppression Water System" 2-FHA-015 Vol. 2. Section 1 Added new Section 1.2.2 and Technical Impell Document No. 597-361-10 Table of Contents renumbered sections and pages.
2-FHA-015 Vol. 2. Section 1 Added Figure 1-1. " Zion Technical Impell Document No. 597-361-10 Table of Contents Station Fire Detection System" (3 pages).
2-FHA-015 1-1 Added introductory Technical Impell Document No. 597-361-10 information about fire protection system.
2-FHA-015 1-4 Added information about FP Technical Impell Document No. 597-361-10 loop header and service water supply.
Page 2 of 13 ZION FPR CHANGE LOG Rev. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-014 1-5 Added sentence to introduce Technical Impell Document No. 597-361-04 Table 1.1.
2-FHA-015 1-5 Added sentence about manual Technical Impell Document No. 597-361-10 piping.
2-FHA-015 1-5 Added new Section 1.2.2.
Technical Impell Document No. 597-361-10 2-FHA-015 1-7 Added penetration Technical Impell Document No. 597-361-10 information.
2-FHA-015 1-14 Added information on FP Technical Impell Document No. 597-361-10 system surveillance.
2-FHA-015 1-14 Added information on alarm Technical Impell Document No. 597-361-10 tests and inspections 2-FHA-009 l-20 Added Table 1.1 (previously Technical Impell Document No. 597-361-04 in UFSAR).
2-FHA-015 Section 1 Added Figure 1-1 (3 pages, Technical Impell Document No. 597-361-10 previously in UFSAR as one page).
2-FHA-001 2-14 thru 2-20 Updates of various Technical Mods M22-0-87-027C (D), M22-combustible loading 1(2)-88-0478,M22-2-88-047E, summaries.
M22-1(2)-88-061,M22-90-007, M22-1-90-Oll,M22-1(2)-90-023, M22-1(2)-91-007,M22-1(2) 008,M22-2-92-008; Zion Station Combustible loading Calculation
Page 3 of 13 ZION FPR CHANGE LOG R:v. #
Section/Page Description of Chance Revision / Basis References / Remarks 2-FHA-017 Vol. 2, Section 2 Added Table 2.2 to include Technical FHA Section 3, " Fire Table of Contents Automatic Fire Detection and Protection Criteria and 2-21 thru 2-27 Suppression, and NFPA Code Measures" for each Fire Zone.
Deviation Information.
2-FHA-015 Vol. 2, Section 3 Added " Miscellaneous Areas."
Technical Impell Document No. 597-361-10 Table of Contents 2-FHA-007 3-4 Revised heat loads and Technical M22-1-90-Oll; Zion Station related information due to Combustible loading addition of combustibles.
Calculation 2-FHA-006 3-7 Revised heat loads and Technical M22-1-90-007; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-006 3-13 Revised heat loads and Technical M22-1-90-007; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-007 3-17 Revised heat loads and Technical M22-1-90-Oll; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-006, -010 3-20 Revised heat loads and Technical H22-1-90-007,M22-1(2)-91-008; related information due to Zion Station Combustible addition of combustibles.
Loading Calculatiot.
2-FHA-010 3-23 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation
1 Page 4 of 13 1
ZION FPR CHANGE LOG R:v. #
Section/Page Description of Change Lavision/ Basis References / Remarks 2-FHA-006, -010 3-26 Revised heat loads and Technical M22-90-007,M22-1(2)-91-008; related information due to Zion Combustible Loading addition of combustibles.
Station Calculation 2-FHA-016 3-29 Added Fire Damper Technical M22-0-91-020 Information.
2-FHA-002, -005,
- 006, 3-32 Revised heat loads and Technical M22-0-87-0270,M22-1(2) -008, -009, -010 related information due to 061,M22-1-90-007,H22-1(2)-
addition of combustibles.90-023,M22-1(2)-91-007,M22-1(2)-91-008; Zion Station Combustible Loading Calculation 2-FHA-016 3-35 Added Fire Damper Technical M22-0-91-020
)
Information.
2-FHA-005, -006, 3-36 Revised heat loads and Technical M22-1(2)-88-061,M22-1-90-007,
-008, -010 related information due to M22-1(2)-90-023. H22-1(2) addition of combustibles.
008; Zion Station Combustible loading Calculation L
2-FHA-006, -008, -010 3-39 Revised heat loads and Technical M22-1-90-007,M22-1(2)-90-023, related information due to M22-1(2)-91-008; Zion Station addition of combustibles.
Combustible Loading Calculation t
2-FHA-002, -005, 3-41 Revised heat loads and Technical M22-0-87-0270,M22-1(2) -006, -008 related information due to 061,M22-1-90-007,M22-1-(2)-
addition of combustibles.90-023; Zion Station Combustible Loading Calculation s
1
~-.
.m
Page 5 of 13 ZION FPR CHANGE LOG R v. f Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-002, -005, -006 3-45 Revised heat loads and Technical M22-0-87-0270,H22-1(2) related information due to 061, M22-1-90-007; Zion addition of combustibles.
Station Combustible Loading Calculation 2-FHA-005, -006, 3-49 Revised heat loads and Technical M22-1(2)-88-061,M22-1-90--
-008, -010 related information due to 007, M22-1(2)-90-023, H22-addition of combustibles.
1(2)-91-007,M22-1(2)-91-008; Zion Station Combustible Loading Calculation 2-FHA-002, -005, -006, 3-54 Revised heat loads and Technical M22-0-87-0270,M22-1(2) -008, -009 related information due to 061,M22-1-90-007,H22-1(2)-
addition of combustibles.90-023, M22-1(2)-91-007; Zion Station Combustible loading Calculation 2-FHA-002, -005, -006, 3-58 Revised heat loads and Technical M22-0-87-0270,M22-1(2) -008, -009, -010 related information due to 061,M22-1-90-007,H22-1(2)-
addition of combustibles.90-023, H22-1(2)-91-007, M22-1(2)-92-008; Zion Station Combustible Loading Calculation 2-FHA-010 3-60 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-016 3-60 Added Fire Damper Technical M22-0-91-020 Information.
l
Page 6 of 13 ZION FPR CHANGE LOG Ray. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-012 3-61 Revised description of Technical Existing plant configuration automatic suppression and and field walkdown.
detection system equipment location for accuracy.
2-FHA-010 3-62 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-002, -006, -008, 3-66 Revised heat loads and Technical M22-0-87-0270, M22-1-90-007,
-009, -010 related information due to M22-1(2)-90-023, H22-1(2) addition of combustibles.
007, M22-2-92-008; Zion Station Combustible loading Calculation 2-FHA-002, -005, -006, 3-70 Revised heat loads and Technical M22-0-87-027D,M22-1(2) -008, -009, -010 related information due to 061,M22-1-90-007,H22-1(2)-
addition of combustibles.90-023,M22-1(2)-91-007,M22-2-92-008; Zion Station Combustible Loading Calculation 2-FHA-006 3-73 Revised heat loads and Technical M22-1-90-007; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-006 3-76 Revised heat loads and Technical H22-1-90-007; Zion Station related information due to Combustible loading addition of combustibles.
Calculation
Page 7 of 13 ZION FPR CIIANGE LOG R;v. #
Section/Page Description of Change Revision /8 asis References / Remarks 2-FHA-003, -005, -010 3-86 Revised heat loads and Technical M22-1(2)-91-008,H22-1 related information due to 0478, M22-1(2)-88-061; Zion addition of combustibles.
Station Combustible Loading Calculation 2-FHA-003, -005, -010 3-90 Revised heat loads and Technical M22-1(2)-91-008,H22-2 related information due to 0478, H22-1(2)-88-061; Zion addition of combustibles.
Station Combustible loading Calculation 2-FHA-010 3-94 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related in Hrmation due to Combustible loading addition of combustibles.
Calculation 2-FHA-004, -010 3-98 Revised heat loads and Technical M22-2-88-047E,M22-1(2) related information due to 008; Zion Station Combustible addition of combustibles.
Loading Calculation 2-FHA-003, -005, -010 3-102 Revised heat loads and Technical M22-1(2)-92-008, M22-1 related information due to 0478, M22-1(2)-88-061; Zion addition of combustibles.
Station Combustible loading Calculation 2-FHA-005, -010 3-106 Revised heat loads and Technical M22-1(2)-88-061; M22-1(2) related information due to 008, Zion Station Combustible addition of combustibles.
Loading Calculation 2-FHA-010 3-109 Revised heat loads and Technical M22-1(2)-91-008, Zion Station related information due to Combustible Loading addition of combustibles.
Calculation
Page 8 of 13 ZION FPR CHANGE LOG Rev. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-010 3-112 Revised heat loads and Technical M22-1(2)-91-008, Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-002, -005, -006, 3-124 Revised heat loads and Technical M22-0-87-0270,M22-1(2) -008, -009, -010 related information due to 061,H22-1-90-007,M22-1(2)-
addition of combustibles.90-023, H22-1(2)-91-007, M22-1(2)-91-008; Zion Station Combustible loading Calculation 2-FHA-005, -006, -008, 3-129 Revised heat loads and Technical M22-1(2)-88-061,H22-1-90-007,
-009, -010, -011 related information due to M22-1(2)-90-023,M22-1(2) addition of combustibles.
007,M22-1(2)-91-008,H22 92-008; Zion Station Combustible loading Calculation 2-FHA-010 3-131 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-133 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-135 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to combustible Loading addition of combustibles.
Calculation 1
Page 9 of 13 ZION FPR CHANGE LOG R:v. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-010 3-151 Revised heat loads and Technical M22-1-88-0478,M22-1(2)-91-008; related information due to Zion Station Combustible addition of combustibles.
Loading Calculation 2-FHA-003, -010 3-154 Revised heat loads and Technical M22-2-88-0478,M22-1(2)-91-008; related information due to Zion Station Combustible addition of combustibles.
Loading Calculation 2-FHA-010 3-158 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible loading addition of combustibles.
Calculation 2-FHA-010 3-161 Revised heat loads and Technical M22-2-88-047E,M22-1(2)-91-008; related information due to Zion Station Combustible addition of combustibles.
Loading Calculation 2-FHA-010 3-164 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-186 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible loading addition of combustibles.
Calculation 2-FHA-010 3-190 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-192 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation
Page 10 of 13 ZION FPR CHANGE LOG R:v. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-010 3-200 Revised heat leads and Technical H22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-015 3-200 Added FP Criteria and Technical Impell Document No. 597-361-10 Heasures information.
2-FHA-003, -004, -010 3-203 Revised heat loads and Technical M22-1(2)-91-008,M22-2 related information due to 0478, M22-2-88-047E; Zion addition of combustibles.
Station Combustible Loading Calculation 2-FHA-015 3-203 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-FHA-003, -008, -010 3-207 Revised heat loads and Technical M22-1(2)-90-023,M22-1(2) related information due to 008, M22-1-88-047B; Zion addition of combustibles.
Station Combustible loading Calculation 2-FHA-015 3-207 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-FHA-003, -004, -010 3-210 Revised heat loads and Technical M22-1(2)-91-008,M22-2 related information due to 0478, M22-2-88-047E; Zion addition of combustibles.
Station Combustible Loading Calculation 2-FHA-015 3-210 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
Page 11 of 13 ZION FPR CHANGE LOG R2v. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-008, -010 3-213 Revised heat loads and Technical H22-1(2)-90-023,M22-1(2) related information due to 008; Zion Station Combustible addition of combustibles.
Loading Calculation 2-FHA-010 3-219 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-222 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-225 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-230 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-010 3-252 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-002, -010 3-284 Revised heat loads and Technical M22-1(2)-91-008. M22-0 related information due to 027D; Zion Station Combustible addition of combustibles.
Loading Calculation 2-FHA-002, -010 3-315 Revised heat loads and Technical M22-1(2)-91-008,M22-0 related information due to 027D; Zion Station Combustible addition of combustibles.
Loading Calculation
Page 12 of 13 ZION FPR CHANGE LOG R;v. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FliA-015 3-315 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-Fila-002, -010 3-341 Revis ! heat loads and Technical M22-1(2)-91-008, M22-0 related information due to 027D; Zion Station Combustible addition of combustibles.
Loading Calculation 2-Fila-002 3-344 Revisec heat loads and Technical M22-0-87-027D; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-Fila-015 3-344 Added FP Criteria and Technical Impell Documcnt No. 597-361-10 Measures information.
2-FHA-002, -010 3-357 Revised heat loads and Technical M22-1(2)-91-008,M22-0 related information due to 027D; Zion Station Combustible addition of combustibles.
Loading Calculation 2-Fila-015 3-359 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-FHA-015 3-362 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-FHA-010 3-377 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible loading addition of combustibles.
Calculation 2-FHA-015 3-378 Revised sprinkler Technical Impell Document No. 597-361-10 description.
Page 13 of 13 ZION FPR CIIANGE LOG Rev. #
Section/Page Description of Change Revision / Basis References / Remarks 2-FHA-010 3-383 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible loading addition of combustibles.
Calculation 2-FHA-010 3-393 Revised heat loads and Technical M22-1(2)-91-008; Zion Station related information due to Combustible loading addition of combustibles.
Calculation 2-FHA-010 3-397 Revised heat loads and Technical M22-!(2)-91-008; Zion Station related information due to Combustible Loading addition of combustibles.
Calculation 2-FHA-015 3-400 Revised FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-Fila-015 3-402 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-FHA-015 3-403 Added FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-FHA-015 3-.J7 Revised FP Criteria and Technical Impell Document No. 597-361-10 Measures information.
2-FHA-015 3-408 Added Section 3.0.56 Technical Impell Document No. 597-361-10 Miscellaneous Areas.
2-FHA-018 Volume 3, Tab D Revised SER Index pages to Editorial For consistency within the SER Index reflect SER deletions.
document.
2-FHA-018 Volume 3, Tab D Deleted SERs dated 1/28/80, Editorial No longer pertinent to Zion SERs 10/2/80/, 3/17/83 and 1/21/83 FPR.