ML20056D250
| ML20056D250 | |
| Person / Time | |
|---|---|
| Site: | Quad Cities |
| Issue date: | 07/27/1993 |
| From: | Lieberman J, Troskoski W NRC OFFICE OF ENFORCEMENT (OE) |
| To: | |
| References | |
| EA-93-127, EN-93-074, EN-93-74, NUDOCS 9308050144 | |
| Download: ML20056D250 (1) | |
Text
-
~
)
l July 27, 1993 EN 93-074 OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION e
Licensee:
Commonwealth Edison Company (EA 93-127)
(Quad Cities Station, Unit 2)
Docket No. 50-265 i
Subiect:
PROPOSED IMPOSITION OF CIVIL PENALTIES - $100,000 Tnis is to inform the Commission that a Notice of Violation and Proposed Imposition of Civil Penalties in.the amount of $100,000 will be issued on or about July 30, 1993, to Commonwealth Edison Company.
This action is based on two violations involving the i
inoperablity of emergency diesel generators which have each been classified as Severity Level III violations.
In the first, the shared emergency diesel generator was inoperable under certain conditions, due to a design deficiency in some associated logic circuitry.
In the second, the Unit 2 emergency generator was i
determined to be inoperable because the associated cooling water pump was incapable of performing its function.
In each case, the escalation and mitigation factors were considered.
In-the first case, the base civil penalty of $50,000 was escalated a total of 50 percent to $75,000 after partially offsetting escalation for prior opportunities to identify with mitigation for licensee i
identification.
In the second case, the base civil penalty was mitigated 50 percent to $25,000 based upon mitigation for prior i
good licensee performance.
It should be noted that the licensee has not been specifically informed of the enforcement action.
The schedule of issuance and notification is:
Mailinc )f Notice July 30, 1993 Telephone Notification of Licensee July 30, 1993 The State of Illinois will be notified.
The licensee has thirty days from the date of the Notice in which to respond.
Following NRC evaluation of the response, the civil penalty may be remitted, mitigated, or imposed by order.
Contaqt: W.
Troskoski, OE, 504-3281 J.
Lieberman, OE, 504-2741 r
Distribution:
OWFN /
C5' OWFN /IS f MNBB /<3'C' PHIL /rf~ [ NL // T[
Chairman Selin EDO OC IRM RES' Comm. Rogers DEDR AEOD i
Comm. Remick DEDS Op Ctr Comm. de Planque OE i
Reg /Sf3_ Offices /?S'S,,ADM: Doc. Mgt. Br.
ional MAIL l
GPA RI RIV 930B050144 930727 PDR ILE RII / < ( {~ 'RV /rr\\" PDR l
EN-93-074 PDR RIII /: 57F OIG j
PRELIMINARY INFORMATION - NOT FOR PUBLIC 0k DISCLOSURE UNTIL PUBLICLY ANNOUNCED
/65'EE3 i
~