Northem States Power Company 414 Nicollet Mall Minneapolis, Minnesota 55401-1927 Telephone (612) 330-5500 March 19, 1993 10 CFR Part 50, Appendix E U S Nuclear Regulatory Commission Attn:

Document Control Desk Washington, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT i

Docket Nos. 50-282 License Nos. DPR-42

[

50-306 DPR-60 j

Revision to Emercency Response Data System Data Point Library Revisions to the Data Point Libraries for the Emergency Response Data System at Prairie Island are attached. These revisions to the Prairie Island Emergency Response Data System Data Point Libraries clarify and update the revised Data Point Libraries transmitted to the NRC by letter dated July 10, 1992. The following changes were incorporated into the attached revisions of the Prairie Island Emergency Response Syste= Data Point Libraries:

i

1. The following Point ID's were changed as shown below:

i Unit 1 Old Point ID New Point ID l

1U5062AH 1U5061AH i

Unit 2 Old Point ID New Point ID i

1 2U5062AH 2U5061AH 1U4105A 2U4105A 1U4106A 2U4106A l

1U2907A 2U2907A 1U2908A 2U2908A f

2. The units for the following points have been changed from "Deg F / Ft" to

+

"Deg F / 50' Meter" or just Deg F.

These points are calculated by I

subtracting the 60 meter height temperature from the 10 meter height temperature:

l t

1U2907A - Stability Class A - Unit 1 2U2907A - Stability Class A - Unit 2 IU2908A - Stability Class B - Unit 1 f

2U2908A - Stability Class B - Unit 2 9303260162 930319

[

I-PDR ADOCK 05000282 l

F

.PDR g

i

USNRC NORTHERN STATES POWER COMPANY March 19, 1993 Pa'ge 2

3. The engineering units, high range and conversion have been revised as shown below for the following points:

1U5017A - Containment Sump Level Wide Range 2U5017A - Containment Sump Level Vide Range Engineering units changed from percent to Ft High Range changed from 120.0% to 12.0 Ft Conversion changed from 4,685 gal /t to 40,741 gal /ft i 7,000 gal /ft

4. The engineering units, low range and high range have been revised as shown below for the following points:

IU5082A - NI Intermediate Range 2U5082A - NI Intermediate Range Engineering units changed from pA to Amps Low Engineering Range changed from 1.0E-5 pA to 1.0E-11 Amps High Engineering Range changed from 1.0E03 pA to 1.0E-03 Amps Please contact Gene Eckholt (612) 388-1121 ext 4663 if you have any questions related to the information we have provided.

1/

fjf[{Uf^N 4 omas Parker Director Nuclear Licensing c: Regional Administrator - III, NRC NRR Project Manager, NRC Sr Resident Inspector, NRC J Silberg Attachments: 1. Revision 2 to Prairie Island Unit 1 Emergency Response Data System Data Point Library

2. Revision 2 to Prairie Island Unit 2 Emergency Response Data System Data Point Lib.tary I

i I

i j

I l

l l

4 ATTAC10ENT 1

[

REVISION 2 70 FRAIRIE ISLAND UNIT 1 EMERGENCY RESPONSE DATA SYSTEM t

5 DATA POINT LIBRARY h

p 1

9 b

1 i

t s

f I

6 1

a b

Gorthtrn States Power Coppany Prairie Island Nuclear Generating Plant - UNIT 1 (P11)

NRC EROS Data point Library Mar 10, 1993 Rev 2.

Page 1 of 7 3

I I

l Nesding definitions used in this report are:

l Other notes l

l 1

i l PID

= Point ID.

l The data fields Ni power sum ly cut off and turn on leve: are l

{ EU

= Engineering units.

l not provided because the power supplies are not cut off.

l l P/S

= PROC or SENS. ( Processesd or sensor value )

l l

l #SNSR

= Ntater of sensors.

l Teeperature conpensation for DP trensmiters is mentioned in the l

l Antg/ Dig = Analog or digital point type.

l unique system description if a plicable. Else the answer is no.

l l Process

= How processed.

l l

l CV-AVG = Chauvenet Validated Average of.

l Level reference leg only applies to SG LEVEL 1/4 & 2/B.

l l

QV

= Ouality votichtien against constants.

l See unique system description for these two points.

l l Location = Sensor location.

l l

l HI RANSE = 19strinnent highest range.

l ERCS is the Emergensy Response Corputer System at the plant &

l l LO RANGE

= Instrument lowest range.

l le the feeder for all of the data used by ERDS.

l l ZERO REF

= Zero refernece point.

l l

n e

a

SUMMARY

I i

l # PID NRC PARAMETER ERCS POINT DESCR!PflDN

  1. PID NRC PARAMETER ERCS PotNT DESCRIPTION
  1. PID NRC PARAMETER ERCS POINT DESCRIPfl0N-l l

l......................

I i

l 1 1U5048A NI POWER RNG SAS avr, per rng pwr level 16 1U5049A HL TEMP 1/A SAS hot leg 1 Temperature 31 1U5022A CNTMNT RAD SAS High CNTMT radiation l

l 2 1U5022A NI INTER RNG Avg intermed rng power level 17 1U5051A HL TEttP 2/B SAS hot leg 2 Terpera, e 32 2R0009A RCS LTDN RAD RC tetdown line radiation l

l 3 195081A NI SOURC RNG Avg srce reg pwr level 18 1U5053A CL TEMP 1/A SAS cold leg 1 Tenperature 33 1U5143A MAIN SL 1/A SAS main steamline A rad'n l

l 4 1U5011A REAC YES LEV SAS avg reactor vessel level 19 1U5055A CL TEMP 2/B SAS cold leg 2 Tenperature 34 1U5144A MAIN SL 2/B SAS main steamline D rad'n l

l 5 1U5510A TEF

. EX SAS 1st hotest incore T/C 20 1U5001A RCS PRESSURE SAS avg RCS pressure 35 1U5026A SG BD RAD SAS stm gen blowdown rad'n l

l 6 1U5077A s'

~4 SAS RCS subcooling margin 21 1U5007A PRZR LEVEL SAS avg PRZR H2O Lvl (NR) 36 1U5015A CNTMNT PRESS SAS avg containment press l

l 7 1U5152A

~ d RC avg flow 22 1F0128A RCS CHG/MU Charge pnp disch hdr flow 37 1U5013A CNTMNT TEMP SAS avg containment terp l

l 8 1U5032A 1/A SAS avg atm gen 1 H2O level 23 1U5154A HP St FLOW Total safety injection flow 38 1U5021A H2 CONC SAS avg containment H2 conc l

l 9 1U5034A al,oc 4L 2/B SAS avg stm gen 2 H2O Level 24 100651A LP SI FLOW Total RHR flow 39 1U5068A BVST LEVEL SAS avg RWST tevel l

l101U5036A SG MtESS 1/A SAS avg stm gen 1 presure 25 1U5153A CTMNT SMP NR Stry 8 avg level NR 40 1U4105A WIND SPEED Met twr 10M avg wind spd A l

l111U5038A SG FPESS 2/B SAS ave stm gen 2 presure 26 1U5017A CTMNT SMP WR SAS avg contnment sm p tvl 41 1U4106A WIND SPEED Met twr 10M avg wind spd B l

l121U5040A MN FO FL 1/A SAS avg stm gant feed flow 26 1U5061AL EFF GAS RAD Shid bld gas efftnt low rng 42 IV4109A WIND DIR Met twr 10M wind dir A l

l131U5042A MN FD FL 2/B SAS avg stm gen? feed flow 28 1U5061AH EFF GAS RAD Shid bld gas effLnt hi rng 43 1T4110A WIND DIR Met twr 10M wind dir B l

l141U5044A AX FD FL 1/A SAS avg stm gent aux fd ft 29 1R0021A EFF LIQ RAD Circ wtr disch red entr 44 1U2907A STAB CLASS Met tur 50M avg delta tenp A l l151U5045A AX FD FL 2/B SAS avg stm gen 2 aux fd ft 30 1U5024A COND A/E RAD SAS air ejector radiation 45 102908A STAB CLASS Met twe 50M avg delta tenp B l i

i n, -,.

CGrthorn States Power Co m any Prairie Island Nuclear Generating Plent - L911T 1 (Pil)

NRC ERDS Data point Library Mar 10, 1993 Rev 2.

Page 2 of.7 Lo/Ni PID NRC ERDS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS PolNT DESCRIPTION P/S PROCESS NI RANGE SET-PolNT ZERO REF DATE GENERIC /COND DESCRIPTION GSNSR LOCATION FAIL MODE DP TEMP CCDEP Unluue system description 1U5048A NI POWER RNG Analog 0.0 N/A N/A This point reflects the CV-AVG of W41, N42, N43 & N44 power range reactor ERCS #2 SAS avg p r rng pwr level P

CV AVG 120.0 N/A N/A power level sensors.

07/02/91 Avg power range pwr level 4

Excore LOW N/A

~1U5082A N1 INTER RNG AMP Analog 1.0E-11 N/A N/A This point reflects the CV-AVG of 358 & 368 neutr m flux intermediate range ERCS O2 Avg intermed rng power level P CV-AVG 1.0E-3 N/A N/A levet sensors.

10/16/91 Avg intermed range pur level 2 Excore LOW N/A 1U5081A NI SOURC RNG cps Analog 0.7 N/A N/A This point reflects the CV AVG of 31E & 32F neutron flux source range levet.

ECCS #2 Avg srce rng pwr P

CV AVG 1.0E6 N/A N/A The power supply does not shut off for these sensors.

90/16/91 Avg source range pwr level 2

Escore LOW N/A 1U5019A REAC VES LEV Analog 0.0 0.0 4.4 inch /% This point reflects the CV-AVG of the reactor vessel levet based on reactor ECCS #2 SAS avg reactor vesset level P CV-A"G 120.0 120.0 Note coolant pu m operation. If RCPs are off then wide range RYLIS sensors are 07/02/91 Avg reactor vessel tevel 4

Contmnt Failed FROM RVLIS used. Else, dynamic head RYLIS sensors are used. RVLIS is Westinghwse reactor vessel levet indication system.

Note: DP tem compensation is provided in the RVLIS ccuputer which seties this value to the ERCS computer.

Note: Top of fuel = 56.7%. Bottom of fuet = 24%.

1U5510Q TEMo CORE EX DegF Analog 32.0 N/A N/A This point reflects the CV-AYG hottest reactor incere thermocouple.

ECCS #2 SAS 1st hotest incore T/C P

CV AVG 2300.0 N/A N/A Note: T/C = thermocouple.

07/02/91 36 incore Failed N/A 1U50FFA SUG MARGIN DegF Analog

-200.0 N/A N/A This point reflects the result of a two term linear equation using RCS ERCS #2 SAS RCS subcooling margin P

See note 1000.0 N/A N/A saturation teeperature ( Tem. saturated vapor as a function of presure OF/02/91 RCS subcooling margin 3

Failed N/A based on the 1967 ASME steam tables ) and avg core exit temp ( CV AVG of the incere thermocouples ).

1U5952A CORE FLOW X

Analog 0.0 N/A N/A This point reflects the CV-AVG of these 6 flow values:

ERCS O2 RC avg flow P

CV-AVG 115.0 N/A N/A ( A RC 411, PIv<0400A ), ( A-RC 412, PID=F0401A ), ( A-RC 413, PID=F0402A ),

07/1P/99 6

Failed N/A ( B RC 414, PID=F0420A ), ( B-RC 415, PID=F0421A ), ( B-RC 416, PID=F0422A )

. ~.

CorthTrn States Power Conpany Prairie Island Nuclear Generating Plant - UNIT 1 (Pil)

WRC-EROS Data point Library Mar 10, 1993 Rev 2.

Page 3 of 7 Lo/H1

- PID NRC ERDS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDE2 ERCS POINT DESCRIPTION P/S PROCESS HI RANGE SET POINT ZERO REF DATE GENERIC /COND DESCRIPTION

  1. SNSR LOCAfl0N FAIL MODE OP TEMP COMP Unique system description IU5032A SG LEVEL 1/A Analog 0.0 20.0 1%=180 gal GSTP
  • 1= Sensor located 433" above the tube sheet. NR sensors cover a span of 144'8 ECCS #2 SAS evg stm gen 1 H2O Level P CV-AVG 100.0 67.0 Note *2
  • 2=Zero reference 23" above tube bundle, 420"
  • top of tube bundle.

07/02/91 Avg stm gen 1 H2O Level I

Note *1 Failed Note *5

  • 3=This point reflects CV-AVG of toop A stm gen level ( NR461, NR462 & NR463)
  • 4= level reference teg=yes, water filled with condenser pot.
  • 5 0P teep compensation not used.

iU5034A SG LEVEL 2/8 Analog 0.0 23.0 %=180 gal SSTP

  • 1= Sensor located 433" above the tube sheet. NR sensors cover a span of 144" EICS C2 SAS avs stm een 2 H2O lev P

CV-AVG 100.0 67.0 Note *2

  • 2=Zero reference 23" above tube bundte, 420" = top of tube bundte.

' 07/05/91 Avg stm gen 2 H2O Level 3

Note *1 Failed N/A *3=This point reflects CV-AVG of loop B stm gen level ( NR471, NR472 & NR473)

  • 4= level reference Leg =yes, water fitted with condenser pot.

1U5036A SG PRESS 1/A PSIG Analog 0.0 500.0 N/A CV-AVG of loop A stm gon pressure ( 468, 469, 482 ).

EICS C2 SAS avg atm gen 1 presure P

CV-AVG 1400.0 1075.0 N/A 07/05/91 Avg stm gen 1 pressure 3

Failed N/A 1U5038A SG PRESS 2/B PSIG Analog 0.0 500.0 N/A CV-AVG of loop B stm gen pressure ( 478, 479, 483 ).

ERCS C2 SAS avg stm gen 2 presure P

CV-AVG 1400.0 1075.0 N/A 07/05/91 Avg stm gen 2 pressure 3

Failed N/A 1U5040A MN FD FL 1/A tb/Mr Analog 0.0 N/A N/A CV-AVG of loop A fw flow 466(xmtr) & 467(xmtr).

EICS C2 SAS avg stm gent feed flow P

CV-AVG 4470000 N/A N/A

  • 1=0P comp not used.

07/05/91 Avg steam gen 1 feed flow 2

Failed Note *1 1U5042A MN FD FL 2/B lb/Mr Analog 0.0 N/A N/A CV-AVG of loop B fw ficw 476(xmtr) & 477(xmtr).

ERCS C2 SAS avg stm gen 2 feed flow P

CV-AVG 4470000 N/A N/A *1=0P coup not used.

07/05/91 Avg stm gen 2 feed flow 2

Failed N/A 1U5044A AX FD FL 1/A GPM Analog 0.0 N/A N/A this point reflects the quality validation of AFU flow to A steam generator ERCS #2 SAS avg stm gen 1 aux fd ft P

QV 200.0 N/A N/A against the SAS constants of steem aux feed flow Lo EU & Hi EU.

the 07/05/91 Stm gen 1 aux feed flow 1

Failed N/A constants are currently set at 0.0 and 200.0.

  • 1=0P comp not used.

1U50454 AX FD FL 2/8 GPM Analog 0.0 N/A N/A This point reflects the quality validation of AFU flow to B steam generator ERCS C2 SAS avg stm gen 2 aux fd ft P

QV 200.0 N/A N/A against the SAS constants of steam aux feed flow to EU & Mi EU. The 07/05/91 stm gen 2 aux feed flow 1

Failed N/A constants are currently set at 0.0 and 200.0.

  • 1=0P comp not used.

Corthora States Power Copperty Prairie Island Nuclear Generating Plant - UNIT 1 (Pli)

NRC-EROS Data point Library Mar 10, 1993 Rev 2.

Page 4 of 7 Lo/Hi PID. NRC EROS PARAMETER EU ANLG/OlG LO RANGE ALRM/ TRIP CONVERSION FEEDEQ ERCS POINT DESCRIPTION P/S PROCESS HI RANGE SET-PolNT ZERO REF DATE-GENERIC /CONO DESCRIPTION

  1. SNSR LOCATION Fall MODE DP TEMP COMP Unique system description

'105049Q HL TEMP 1/A DegF Analog 50.0 N/A N/A This point reflects the quality validation of A RC het leg tenp 450A against EQCS C2 SAS hot leg 1 feeperature P

QV 700.0 N/A N/A the SAS constants of hot leg teep Lo EU and.Hi EU.

The constants are 07/03/91 Hot leg 1 tenveroture 1

Failed N/A currently set at 50.0 and 700.0.

1U5051A HL TEMP 2/B DegF Analoe 50.0 N/A N/A This point reflects the quality validation of B-RC hot leg temp 451A against ERCS O2 SAS hot leg 2 Tenperature P

QV 700.0 N/A N/A the SAS constants of hot leg tenp to EU and HI EU.

The constants are 07/05/91 Nat leg 2 tenperature 1

Failed N/A currently set et 50.0 and 700.0.

1U5053A CL TEMP 1/A DegF Analog 50.0 GFP 520 N/A This point reflects the quality validation of A-RC cold leg teep 450s against ERCS #2 SAS cold leg i Tepperature P

QV 700.0 GFP 555 N/A the SAS constants of cold leg tenp to EU and HI EU.

The constants are OF/05/91 Cold leg 1 teoversture 1

Felled N/A currently set et 50.0 and 700.0.

Note: Alerm setpoints are et full power. In other modes, setpoints are calcu-lated lased on system pressure.

1U5055Q CL TEMP 2/8 DegF Analog 50.0 GFP 520 N/A This point reflects the quiJrty validation of B RC cold leg teep 4518 against ERCS #2 SAS cold leg 2 Tenperature P

QV 700.0 SFP 555 N/A the SAS constants of cold led temp to EU and Hi EU. The constants are 07/05/91 Cold leg 2 temperature 1

Failed N/A currently s=t et 50.0 and 700.0.

Note: Alarm setpoints are at full power. In other pedes, setpoints are calcu-lated based on system pressure.

1U5C01A RCS PRESSURE PSIG Analeg 0.0 GFP 1900 N/A CV-AVG of the 4 narrow range pressure sensors. If the validated quality of ECCS #2 SAS evg RCS pressure P

CV-AVG 3000.0 GFP 2385 N/A the sensors is bed, then use CV-AVG of 2 wide range pressure sensors.

07/06/91 Avg RCS pressure 6

N/A Note: At other then full power mode, SAS calculates Mi and to eterm limits.

1U500FA PRZR LEVEL Analog 0.0 14.8 64.6 gel /% This point represents the CV-AVG of PRZR 426, 427 & 428 level sensors.

ERCS #2 SAS evg PRZR H2O tvl (NR)

P CV-AVG 100.0 90.0 527 get Szro *1=0P conp not used.

07/06/91 Avg pressurizer M20 level 3

Failed Note *1 Noter Zero % level is 18'9" above top of fuel.

1F0128A RCS CMG/MU Cpn Analog 0.0 N/A N/A Sensor located 20 feet above discharge pnp.

ERCB O2 Charge p p disch hde flow 100.0 N/A N/A 07/06/91 1

note Low N/A w

'b,ri-sw wv1-4't--s*

    • '4e'4m*-*--M-
  • -J' u'+' ^ '

%-P8'

'9-4-W-ww-t-+f*

Wmu'r 9 *- *-

^WM 4 m f-

"'8" M

'T'19-9v'-F

-'N

"-W

W e

W

  • ='w-gW'*vv
  • w

+a'e i'N'9

^++e wd-'

F-WPa*9+

Corthern States Power Cwpeny Prairie Island Nuclear Generating Plant - UNIT 1 (P11)

NRC-EROS Data point Library Mar 10, 1993 Rev 2.

Page 5 of' 7 Lo/MI PID NRC ERDS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS PGINT DESCRIPTION P/S PROCESS HI RANGE SET-POINT ZERO REF DATE-GENERIC /COND DESCRIPit0N

  1. SNSR LOCAfl0N FAIL MODE DP TEMP COMP Unique system description 1U5154A MP St FLCW Gpn Analog 0.0 NONE N/A Stn of P!0->(1F0922A si flow to cold legs) & (1F0923A St flow to rx vst)

E2CS C2 Total safety injection flow P

1500.0 NONE N/A 10/09/91 2

N/A 1UO651A LP St Flou Gpm Anatog

-1.0 1250.0 N/A Stn of PID >(1F0626a RNR toop flow) & (1F0928A RHR flow to vst)

ERCS #2 Total RNR flow P

9000.0 2500.0 N/A 10/09/91 2

N/A 1U5153A CTMNT SMP NR ( narrow rng )

Analog 0.0 N/A 14.7 gal /% Average of 2 values ( step 8 725 PID=F09224 ) & ( strm 8 726 P!D=F0923A ) NR ERCS #2 Step 8 avg levet NR P

CV AVG 100.0 N/A Zero ( narrow range ) levels. Strp crea = 42 sq 7t. Depth =47". Conversion = 14.7 07/17/91 2

Failed N/A gal / % up to 84%. Above 84% conversion = 1903 gal / %.

1U501TA CTMNT SMP WR ( wide range )

Ft.

Analog 0.0 0.0 40,741 get/ft This point reflects the CV AVG of contaltnent levels 727 WR & 728 WR. Range EXCS #2 SAS ave contruent strp Lwl P

CV-AVG 12.0 0.5 0.0 ft In ft = 0 to 11.5 ( 100% ). Contalrnent area = 5446 sq ft. Conversion factor 07/06/91 Avg containment stry level 2

Failed N/A is 40,741 gat /f t or 4685 gal /%. Accuracy is +/- 17.2% due to conplexities.

1U5061AL EFF GAS RAD MC1/HR Analog 5.3E-3 N/A This point is the shletd btdg stack effluent radiattem in mill-curries /hr ERCS #2 stock effl redn low rng P

526 N/A menon 133 equivalent. Cocputed using ( 2R0022A mr/hr

  • 5.26E 04 ) / 1F5429A.

10/10/91 2

N/A 1F5429A is stack flow rate in CFM. 2R0022A is low range red monitor.

105061AN EFF GAS RAD MCI /HR Anatog 5.3E-5 N/A This point Is the shletd btdg stack effluent radiation in mitt-curries /hr EICS C2 stack efft redn high rng P

5260 N/A Menon 133 equivalent. Copputed using ( 2R0050A mr/hr

  • 52.674 ) / 1F5429A.

10/10/91 2

N/A 1F5429A le stack flow rate in CFM. 2R0050A is hl range rad monitor.

1R0021A EFF LIQ RAD CPM Analog 10.0 N/A N/A ERCS C2 Circ 4.tr disch r 5

1000000 1000.0 N/A 10/10/91 1

N/A 1U5024A COND A/E RAD CPM Analog 10.0 10.0 N/A This point refetcts the qdality validation of CDSR air ejector gas ERCS #2 SAS air ejector radiation P

QV 1.0 E6 5000.0 N/A radioactivity against the SAS constants of air ejector radiation which are 07/06/91 Air ejector radiatien 1

Failed N/A currently set at 10 and 1,000,000.

1U5022A CNTMNT RAD R/Hr Analog 1.0 1.0

'N/A This point reflects the CV-AVG of high range CNTMT aree monitor or high range ERCS #2 SAS High CNTMT radiation P-CV-AVG 1.0 E08 2.0 E4 N/A CNTMT area monitor A or high range CNTMt area monitor 8.

07/06/91 High Containment radiation 2

Failed N/A

... m

.~.

. ~. -.

3 Northtrn States Power Ccevany Prairie Island Nuclear Generating Plant

  • LMIT 1 (Pil)

NRC ERDS Data point Library Mar 10, 1993 Rev 2.

Page 6 of 7 Lo/Pi PID NRC ERDS PARAMETER EU ANLG/ DIG LO RANGE ALDM/ TRIP C04YER$104 FEEDER ERCS POINT DESCRIPTION P/S PROCESS NI RANGE SET-POINT ZERO REF DATE-GENERIC /COND DESCRIPTION

  1. 5NSR LOCATION FAIL MODE OP TEMP COMP Unique system description 2R0009A RCS LTOG RAD MR/Nr Analog 0.1 N/A N/A

. ERCS C2 RC tetdown line radiation S

10000.0 1000.0 N/A 07/06/91 1

Failed N/A 1U5163A MAIN SL 1/A MR/Mr Analog 1.0 N/A N/A fuls point refelets the quotity validation of A stm line red level against ERCS #2 SAS main steamline A rad'n P

QV 1.0 E5 N/A N/A the SAS constants of main steamline radiation Lo EU & NI EU which are set at 07/06/91 Main steamline A radiation 1

Failed N/A 1 & 100000.

1U5144A MAIN SL 2/8 MR/Mr Analog 1.0 N/A N/A This point refelets the quality validation of 8 stm line red levet against ECCS C2 SAS main steamline 8 rad'n P

QV 1.0 E5 N/A N/A the SAS constants of main steamline radiation Lo EU & NI EU which are set at 07/06/91 Main steamline s radiatten 1

Failed N/A 1 & 100000.

1U5026A SG BD RAD 1A CPM Analog 10.0 10.0 N/A This point refelets the cpolity validation of A steam gen blowdown radiation ERCS C2 SAS stm gen blowdown rad'n P

QV 1.0 E6 1.0 E4 N/A against the SAS constants of steam gen blowdom radiation to EU & M1 EU which 07/pi*ot Stm gen blowdown radiation 1

Failed N/A are currently set at 10 & 1,000,000.

1U5015A tNTMNT PRESS PSIG Analog

-5.0 5.0 N/A This point reflects the CV-AVG of containment pressure WR 717 & 718 sensors.

ECCS C2 SAS avg containment press P

CV-AVG 200.0 4.0 N/A 07/06/91 Avg containment pressure 2

Failed N/A 1U5u13A CNTp4T TEMP Degr Analog 0.0 N/A N/A *1=High storm is 10 DegF greater than rolling 5 min avn of containment teep.

ERCS #2 SAS avg containmutt teep P

Mov AVG 400.0 note *1 N/A This point reflects the CV-AVG of containment air tenp elevation 697 and 738 07/06/91 Avg containment tenp 3

Failed N/A and 755 sensors.

1UiO214 M2 CONC ( concentration )

Analog 0.0 N/A N/A This point reflects the CV AVG of contalrvnent H2 concentration sensors 719 &

~ECCS #2 SAS avg contairvnant N2 conc P CV-AVG 10.0 N/A N/A 721.

07/06/91 Avg contairrent H2 conentrn 2 Failed N/A

.1U5068A BWST 1EVEL Analog 0.0 h/A 2922 Gal /% This point reflects the CV-AVG of RWST ( refueling water storage tank ) level ERCS C2 SAS avg RWST tevel P

CV-AVG 100.0 N/A 1898 Gal sensors 920 and 921.

07/06/91 Avg RWST level 2

Failed N/A i

1U4105A WIND SPEED MPH Analog 0.0 N/A N/A Sensor location = meteertogical tower A 10 meter height.

ERCS C2 Met twr 10M avg wind spd A P

none 100.0 N/A N/A 15 minute moving average of 30sec readings.

10/1o/91 1

10 meter Failed N/A i

.m

.--.,,....,+,w-r

,,,,,e.

.w,e,%-

.-n--,.---

w. =..-

e-.... - -,

-v.-

.,--.,m,

,cw

..we-.--.,--e---

w-..

-,.w

.v, g-=

t.

NorQhern States Power Coppar*y Prairie Island Nuclear Generating Plant - UNIT 1 (Pil)

NRC-ERDS Data point Library Mar 10, 1993 Rev 2.

Page 7 of 7 Lo/HI PID ~ NRC ERDS PARAMETER EU AhtG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS POINT DESCRIPTION P/S PROCESS NI RANGE SET-PolNT ZERO REF.

DATE GENERIC /CONO DESCRIPTION

  1. $NSR LOCATION FALL MODE OP TEMP COMP Unique system deseriptIon IU4106A WIND SPEED MPH Anetog 0.0 N/A N/A Sensor location = meteorlogical tower 810 meter height.

ERCS #2 Met twr 10M avg wind spd 8 P

none 100.0 N/A N/A 15 minute moving average of 30sec readings.

-10/16/91 1

to meter Foited N/A 1T41094 WIND DIR Deg Analog 0.0 N/A N/A Sensor location a meteorlogical tower A 10 meter helpht.

ERCS #2 Pri met twr 10M wind dir A S

360.0 N/A N/A -Instantaneous values updated in 30 see Intervals.

07/09/91 1

10 meter Failed N/A Indication is in the from direction.

1T4110A WIND DIR Deg Analog 0.0 N/A N/A Sensor location a meteortogical tower A 10 meter height.

ERCS C2 Pri met tur 10M wind dir 8 5

540.0 N/A N/A Instantaneous values unfated in 30 see Intervals.

.07/09/91 1

10 meter Failed N/A Indication is in the from direction.

1U2907A STA8 CLASS OF/100 Analog

-9.0 N/A N/A Sensor location a meteorloglcal tower 10 & 60 meter height.

ERCS #2 Met twr avs detta tepp A P

Diff 9.0 N/A N/A This value represents the difference in tenperature in degF/100Ft.

10/76/99 2

10 & 60 M.

Failed N/A 1U2908A StA8 CLASS OF/100 Analog 9.0 N/A N/A Sensor location a meteorlogical tower 10 & 60 meter height.

-ERCS #2 Met twr avg detta teep 8 P

Diff 9.0 N/A N/A This value represents the difference in temper 3ture in degF/100Ft.

10/16/91 2

10 & 60 M.

Failed N/A i

_. ~ - -,

.e4 g.

ATTACHMENT 2 l

REVISION 2 TO-PRAIRIE ISTAND UNIT 2 EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY i

t i

e f

e i

3 4

' t b

v

,I

+

i i

I e

6 I

1 i

..f

~

Corthten States Power Carpany Pralrle Island Nuclear Generating Plant

  • Unit 2 (PI2)

NRC-E905 Data point Library Mar 10, 1993 Rev 2.

Page 1 of 7 i

i i

l Heading definitions used in this report are:

l

.Other notes:

l l

1 1

l PID

= Point 10.

l The data fields NI power supply cut off and turn on levels are l

l EU

= Engineering units.

l not provided because the power supplies are not cut off.

l l P/S

= PROC or SENS. ( Processesd or sensor value )

l l

l #SNSR

= Neber of sensors.

l Temperature compmsation for DP transmiters la mentioned in the l

l Antg/ Dig = Analog or digital point type.

l unique system description If applicable. Else the answer is no.

l l Process a How processed.

l l

l CV-AVG = Chauvenet Validated Average of.

l Level reference leg only applies to SG LEVEL 1/A & 2/B.

l l

QV

= Quality validation against constants.

l See unique system description for these two points.

l l Location = Sensor location.

l l

l HI RANGE = Inr.trument highest range.

l ERCS is the Emergensy Response Caputer System at the plant &

l l LO RANGE = Instrument lowest range.

l la the feeder for all of the cata used by ERDS.

l l ZERO REF = Zero refernece point.

l l

.j j

....... E,D, m,U.A,,.......

i l

l # PID NRC PARAMETER ERCS POINT DESCRIPTION

  1. PID htC PARAMETER ERCS Po!NT DESCRIPTION
  1. PID NRC PARAMETER ERCS POINT DESCRIPTION l

l l

1 l 1 2U5048A NI POWER RNG SAS avg pwr reg pwr level 16 2U5049A HL TEMP 1/A SAS hot leg 1 Tenperature 31 2U5022A CNTMNT RAD SAS High CNTMT radiation l

l 2 2U5082A MI INTER RNG Avg intermed rng power level 17 2U5051A HL TEMP 2/B SAS hot leg 2 Tenperature 32 2R0009A RCS LTDN RAD RC letdown line radiation l

l 3 2U5081A NI SOURC RNG Avg srce rpg pwr level 18 2U5053A CL TEMP 1/A SAS cold leg 1 Temperature 33 2U5143A MAIN SL 1/A SAS main steamline A rad'n l

l 4 2U5011A REAC VES LEV SAS avg reactor vessel level 19 2USC55A CL TEMP 2/B SAS cold leg 2 Terperature 34 205144A MAIN SL 2/B SAS main steamline B rad'n l

l 5 2U551CA TEMP CORE ER SAS ist hotest incere T/C 20 2U5001A RCS PRESSURE SAS avg RCS pressure 35 2U5026A SG BD RAD SAS stm gen blowdown rad'n l

'l 6 2U50TTA SUB MARGIN SAS RCS subcooling margin 21 2U5007A PRZR LEVEL SAS avg PRZR H2O Lyl (NR) 36 2U5015A CNTMNT PRESS SAS avg containment press l

l 7 2VS152A CORE FLCW RC avg flow 22 2F0128A RCS CHG/MU Charge pnp disch hdr flow 37 2U5013A CNTMNT TEMP SAS avg contalment tepp l

l 8 2U5032A 'SG LEVEL 1/A SAS avg stm gen 1 H2O level 23 2U5154A HP St FLOW Total safety injection flow 38 2U5021A H2 CONC SAS avg contalment H2 conc l-l 9 2U5034A SG LEVEL 2/8 SAS avg stm een 2 H2O level 24 2UO651A LP St FLOW Total RHR flow 39 2U5068A BWST LEVEL SAS' avg RWST level l

l102U5036A SG PRESS 1/A SAS avg sta gen 1 presure 25 2U5153A CTMNT SMP NR Sw p B avg level NR 40 2U4105A WIND SPEED Met twr 10M avg wind spd A l

l.112U5038A SG PRESS 2/B SAS avg sta gen 2 presure 26 295017A CTMNT SMP WR SAS avg contment smp tvl 41 204106A WIND SPEED Met twr 10M avg wind spd B l

l122U5040A MN FD FL 1/A SAS avg sta gent feed flow 26 2U5061AL EFF GAS RAD Shld bld gas efftnt low rng 42 1T4109A WIND DIR Met twr 10M wind dir A l

-l132U5042A MN FD FL 2/8 SAS avg stm gen 2 feed flow 28 2U5061AH EFF GAS RAD Shld bid gas efftnt hl rng 43 174110A WIND DIR Met tar 10M wind dir B l

l142LJ444A 3X FD FL 1/A SAS avg sta gen 1 aux fd ft 29 1R0021A EFF LIQ RAD Circ wtr disch rad mnte 44 202007A STAB CLASS Met twe 50M avg detta tenp A l l 15 2U504% A4 FD FL 2/B SAS avg stm gen 2 aux fd il 30 2U5024A COND A/E RAD SAS air ejector radiation 45 2U2908A STAB CLASS Met twr 50M avg delta tenp B l

, Forthtrn States Power Conpar;y Pralrle Interd Nuclear Generating Plant - Unit 2 (PI2)

NRC-ERDS Data point Library Mar 10, 1993 Rev 2.

Page 2 of 7 tc/Hi PIO NRC ERDS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS PolNT DESCRIPTION P/S PROCESS HI RANGE SET-PolNT ZERO REF DATE GENERIC /CJNO DESCRIPfl04

  1. SNSR LOCATION Fall MODE DP TEMP COMP Unique system description 2U50484 NI POWER RNG X

Analog 0.0 N/A N/A This point reflects the CV-AVG of N41, N42, N43 & N44 power range reactor ERCS #2 SAS avg pwr rng pwr level P

CV-AVG 120.0 N/A N/A cower level sensors.

07/02/91 Avg power range pwr level 4

Excore LOW N/A

- 2U5082A NI INTER rig AMP Analog 1.0E-11 N/A N/A This point reflects the CV-AVG of 35B & 36B neutron flux intermediate ERCS C2 Avg Intermed rng power level P CV-AYG 1.0E-3 N/A N/A level sensors.

10/16/91 Avg intermed range pwr level 2 Excore LOW N/A 2U5081A MI SOURC RNG CPS Analog 0.1 N/A N/A This point reflects the CV-AVG of 31E & 32F neutron flux source range level.

E:CS C2 Avg arte rng pwr P

CV-AVG 1.0E6 N/A N/A The power stpply does not shut of f for these sensors.

10/16/91 Avg source range pwr level 2

Excore LOW N/A 235011A REAC VES LEY Analog 0.0 0.0 4.4 inch /% This point reflects the CV-AVG of the reactor vessel level based on reactor E%CS C2 SAS avg reactor vessel level P CV-AVG 120.0 120.0 Note coolant punp operation. If RCPs are off then wide range RvLIS sensors are 07/02/91 Avg reactor vessel level 4

Contnmnt Failed FROM RVLIS used. Else, dynamic head RVLIS sensors are used. RVLIS is Westinghouse reactor vessel level indication system.

Note: DP teep coppensation is provided in the RVLIS computer which supplies this value to the ERCS computer.

Note: Top of fuel = 56.7%. Bottom of fuel = 24%.

2U5510A TEMP CORE EX DegF Analog 32.0 N/A N/A This point reflects the CV-AVG hottest reactor incore thermocouple.

ERCS C2 SAS ist hotest incore T/C P

CV-AVG 2300.0 N/A N/A Note: T/C = thermocouple.

07/02/91 36 Incore Failed N/A 2U5077A SUB MARGIN DegF Analog

-200.0 N/A N/A This point reflects the resutt of a t so term linear equation using RCS j

ERCS C2 SAS RCS subcooling margin P

See note 1000.0 N/A N/A saturation baperature ( Tenp. saturated vapor as a function of presure l 07/02/91 RCS sthcooling margin 3

Failed N/A based on

'967 ASME steam tables ) and avg core exit teep ( CV AVG of the Incore thermocouples ).

j 2t$152A CORE FLOW X

Analog 0.0 N/A N/A This point reflects the CV-AVG of these 6 flow values:

i. EICS C2 RC avg flow P

CV-AVG 115.0 N/A N/A ( A-RC 411, PIDeF0400A ), ( A-RC 412, PID=F0401A ), ( A-RC 413, PID*F0402A ),

G7/17/91 6

Failed N/A ( B RC 414, PID=F0420A ), ( B-RC 415, PID=F0421A ), ( B-RC 416, PID=F0422A )

l I

l l

~

s Ecrthtrn States Power Company Prairie Island Nuclear Generating Plant - Unit 2 (P12' NRC-EROS Data point Library Mar 10, 1993 Rev 2.

Page 3 of 7 Lo/Hi PID NRC EROS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS POINT DESCRIPTION P/S PROCESS HI RANGE SET-POINT ZERO REF DATE GENERIC /CONO DESCRIPfl0N

  1. SNSR LOCATION FAIL MODE DP TEMP COMP Unique system description 2U503.2A SG LEVEL 1/A Analog 0.0 20.01%=180 gal GSTP
  • 1= Sensor located 433" above the tube sheet. NR sensors cover a span of 144" ERCS C2 SAS avg stm gen 1 M20 level P

CV-AVG 100.0 67.0 Note *2

  • 2=Zero reference 23" above tube bundle, 420" = top of tthe txedle.

07/02/91 Avg sta sen 1 M20 level 3

Note *1 Failed Note *3

  • 3=This point reflects CV-AVG of loop A stm een level ( NR461 NR462 & NR463)
  • 4= level reference leg =yes, water filled with condenser pot.
  • 5=0P terp conpensation not used.

2U5034A SG LEVEL 2/3 Analog 0.0 20.0 %=180 gal GSTP

  • 1= Sensor located 433" above the tube sheet. NR sensors cover a spen of 144" ERCS #2 SAS avn atm gen 2 H2O Lev P

CV-AVG 100.0 67.0 Note *2

  • 2=Zero reference 23" above tube bundle, 420" = top of tube bundle.

07/05/91 Avg stm gen 2 H2O tevel 3

Note *1 Failed N/A *3=This point reflects CV-AVG of toop B stm gen level ( NR471, NR472 & NR473)

  • 4= level reference leg *yes, water fitted with condanser pot.

2U5036A SG PRESS 1/A PSIG Analog 0.0 500.0 N/A CV-AVG of loop A stm gen pressure ( 468, 469, 482 ).

ERCS #2 SAS avg stm gen 1 presure P

CV AVG 1400.0 1075.0 N/A 07/05/91 Avg stm gen 1 pressure 3

Failed N/A 2U5038A SG PRESS 2/3 PSIG Analog 0.0 500.0 N/A CV-AYG of loop B stm gen pressure ( 478, 479, 483 ).

ERCS #2 SAS avg sta gen 2 presure P

CV-AYG 1400.0 1075.0 N/A 07/05/91 Avg atm gen 2 pressure 3

Failed N/A 2U5040A PN F0 FL 1/A Lb/Nr Analog 0.0 N/A N/A CV-AVG of loop A fw flow 466(Kmtr) & 467(xmtr).

ERCS f2 SAS avg stm geel feed flow P

CV-AVG 4470000 N/A N/A *1:0P coep not used.

07/05/91 Avg steam gen 1 feed flow 2

Failed Note *1 205042A MN FD FL 2/B lb/Mr Analog 0.0 N/A N/A CV AYG of loop B fu flow 476(xmtr) & 477(xmtr).

ERCS #2 SAS avg stm gen 2 feed flow P

CV-AVG 4470000 N/A N/A *1=0P coup not used.

07/05/91 Avg sta sen 2 feed flow 2

Failed N/A 2U5044A AX FD FL 1/A GPH Analog 0.0 N/A N/A This point reflects the quality validation of AFW flow to A steam generator ERCS #2 SAS avg stm gent aux fd fl P

QV 200.0 N/A N/A against the SAS constants of steam aux feed flow Lo EU & Hi EU. The 07/05/91 Stm gen 1 sum feed flow 1

Failed N/A constants are currently set at 0.0 and 200.0.

  • 1=0P coep not used.

2U5045A AX FD FL 2/B GPM Analog 0.0 N/A N/A This point reflects the quality validation of AFU flow to B steam generator ETCS #2 SAS avg stm gen 2 aux fd ft P

QV 200.0 N/A N/A against the SAS constants of steam aux feed flow Lo EU & Hi EU. The 07/05/91 sta gen 2 aux feed flow 1

Failed N/A constants are currently set at 0.0 and 200.0.

  • 1=DP conp not used.

~-.

~ - -, -

Corthern States Power Company Prairie Island Nuclear Generating Plant - Unit 2 (PI2)

NRC-EROS Data point Library Mar 10, 1993 Rev 2.

Page 4 of 7 Lo/Hi PID NRC ERDS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS POINT DESCRIPTION P/S PROCESS HI RANGE SET-POINT ZERO REF DATE CENERIC/CONO DESCRIPTION

  1. SNSR LOCATION FAIL MODE DP TEMP COMP Unique system description

, 2U5049A nl TEMP 1/A DegF Analog 50.0 N/A N/A This point reflects the quality validation of A-RC hot leg tenp 450A against ERCS #2 SAS hot leg 1 Te m erature P

QV 700.0 N/A N/A the SAS constants of hot leg tenp Lo EU and Hi EU.

The constants are 07/05/91 Hot leg 1 temerature 1

Failed N/A currently set at 50.0 and 700.0.

2U5051A HL TEMP 2/8 DegF Analog 50.0 N/A N/A This point reflects the quality validation of B-RC hot leg tenp 451A against ERCS #2 SAS hot leg 2 Temperature P

QV 700.0 N/A N/A the SAS constants of hot leg tenp to EU arxl HI EU. The constants are 07/05/91 Hot le0 2 temperature 1

Failed N/A currently set at 50.0 and 700.0.

2U5033A CL TEMP 1/A DegF Analog 50.0 QFP 520 N/A This point reflects the quality validation of A-RC cold leg teep 450s against ERCS #2 SAS cold leg 1 Tenversture P

QV 700.0 GFP 555 N/A the SAS constants of cold leg temp Lo EU and HI EU.

The constants are 07/05/91 Cold leg 1 tenperature 1

Falled N/A currently set at 50.0 and 700.0.

Note: Alarm setpoints are at full power. In other modes, setpoints are calcu-lated based on system pressure.

205055A CL TEMP 2/8 DegF Analog 50.0 GFP 520 N/A This point reflectb the quality validation of B-RC cold leg terp 4518 against ERCS C2 SAS cold leg 2 Terperature P

QV 700.0 GFP 555 N/A the SAS constants of cold leg temp Lo EU and Hi EU. The constants are 07/05/91 Cold teg 2 terperature 1

Failed N/A currently set at 50.0 and 700.0, Note: Alarm setpoints are at full power. In other modes, setpoints are calcu-lated based on system pressure.

2U5001A RCS PRESSUkE PSIG Analog 0.0 SFP 1900 N/A CV-AVG of the 4 narrow range pressure sensors. If the validated quality of ERCS #2 SAS avg RCS pressure P

CV-AYG 3000.0 SFP 2385 N/A the sensors is bed, then use CV-AVG of 2 wide range pressure sensors.

07/06/91 Avg RCS pressure 6

N/A Note: At other than full power mode, SAS calculates Hi and to alarm limits.

2U5007A PRZR LEVEL Analog 0.0 14.8 64.6 gal /% This point represents the CV-AVG of PRZR 426, 427 & 428 levet sensors.

ERCS #2 SAS evg PRZR H2O tvl (NR)

P CV-AVG 100.0 90.0 R T gal Gzro

  • 1=0P comp not used.

07/06/91 Avg pressurizer H2O level 3

Failed Note *1 Note: 2ero % tevel is 18'9" above top of fuel.

2F0128A RCS CHG/NU Cpn Analog 0.0 N/A N/A Sensor located 20 feet above discharge punp.

ERCS #2 Charge pnp disch bdr flow S

100.0 N/A N/A 07/06/91 1

note Low N/A

Northw n States Power Carpany Prairie Island Nuclear Generating Plant - Unit 2 (P12)

NRC-ERDS Data point Library Mar 10, 1993 Rev 2.

Page 5 cf 7 4

Lo/Hi PID NRC EROS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS POINT DESCRIPTION P/S PROCESS HI RANGE SET-PolNT ZERO REF DATE GENERIC /COND DESCRIPTION

  1. SNSR LOCATION FAIL MODE DP TEMP COMP Unique system description 2U5154A HP SI /l0W Grm Analog 0.0 NONE N/A Sin of PID->(2F0922A SI flow to cold legs) & (2F0923A S1 flow to rx vst)

E%CS #2 Total safety injection flow P

1500.0 NONE N/A 10/09/91 2

N/A M16514 LP St FLOW r4m Analog

-1.0 1250.0 N/A Stn of PID->(2F0626a RHR loop flow) & (2F0928A RNR flow to vst)

ERCS #2 Tctal RHR flow P

9000.0 2500.0 N/A 10/09/91 2

N/A 2U51534 CTMNT SMP M narrow rng )

Analog 0.0 N/A 14.7 gat /% Average of 2 values ( sump B 725 PID=F0922A ) & ( step B 726 PID=F0923A ) NR E CS #2 Step B evg ' esel NR P

CV-AVG 100.0 N/A Zero ( narrow range ) levels. Strp area = 42 sq f t. Depth =47". Conversion = 14.7 07/17/91 2

Failed N/A gal / % up to 84%. Above 84% conversion = 1903 gal / 1.

Zu5017A CTMNT SMP WR ( wide range )

Ft.

Analog 0.0 0.0 40,741 gal /ft this point reflects the CV-AVG of containment levels 727 WR & 728 WR. Range ERCS C2 SAS avg contment step tvl P

CV-AVG 12.0 0.5 0.0 ft in ft = 0 to 11.5 ( 100% ). Containment area = 5446 sq ft. Conversion factor 07/06/91 Avg contalment strp level 2

Failed N/A is 40,741 gal /f t or 4685 gal /%. Accuracy is +/- 17.2% due to copplexities.

2U5061AL EFF GAS RAD MCI /HR Analog 5.3E-3 N/A This point is the shield bldg stack effluent rediation in mill-curries /hr ERCS C2 stack effl redn low rng P

526 N/A menon 133 equivalent. Corputed using ( 2R0022A mr/hr

  • 5.26E-04 ) / 2F5429A.

10/10/91 2

N/A 2F5429A is stack flow rate in CFM. 2R0022A is low range rad monitor.

205061AH EFF GAS RAD MCl/HR Analog 5.3E-5 N/A This point is the shield bldg stack effluent radiation in mill curries /hr ERCS #2 stack efft redn high rng P

5260 N/A menon 133 equivalent. Conputed using ( 2R0050A mr/hr

  • 52.674 ) / 2F5429A.

10/10/91 2

N/A 2F5429A is stack flow rate in CFM. 2R0050A is hl range red monitor.

II0021A EFF LIQ RAD CPM Analog 10.0 N/A N/A ERCS #2 Circ wtr disch r S

1000000 1000.0 N/A 10/10/91 1

N/A 2U5024A COND A/E RAD CPM Analog 10.0 10.0 N/A this point refelets the quality validation of CDSR eir ejector gas ERCS #2 SAS air ejector radiation P

QV 1.0 E6 5000.0 N/A radioactivity against the SAS constants of air elector radiation wtilch are 07/i4/91 Air ejector radiation 1

Failed N/A currently set at 10 and 1,000,000.

2U5022A CNTMNT RAD R/Mr Analog 1.0 1.0 N/A This point reflects the tv-nvu of high range CNTMT area monitor or high range ERCS #2 SAS High CNTMT radiation P

CV-AVG 1.0 EOS 2.0 E4 N/A CNTMT area monitor A or high range CNTMT area monitor B.

07/06/91 High Contalrnent radiation 2

Failed N/A

n Corthern States Power Ccmpany Prairie Island Nuclear Generating Plant Unit 2 (PI2)

NRC-ERDS Data point Library Mar 10, 1993 Rev 2.

Page 6 of 7

=.

I Lo/Hi PID NRC ERDS PARAMETER EU ANLG/DIC LO RANGE ALRM/ TRIP CONVERSION

. FEEDER ERCS POINT DESCRIPfl04 P/S PROCESS HI RANGE SET-PolNT ZERO REF DATE GENERIC /COND DESCRIPfl0N

  1. 5NSR LOCATION FAIL MODE DP TEMP COMP Unique system description 2R0009A RCS LTON RAD MR/Hr Analog 0.1 N/A N/A ERCS C2 RC letdown line radiation S

10000.0 1000.0 N/A 07/06/91 1

Failed N/A 2U5143A MAIN SL 1/A MR/pr 7nalog 1.0 N/A N/A This point refelets the quality validat8cn of A sta line red level against EECS #2 SAS main steamline A rad'n P

QV 1.0 E5 N/A N/A the SAS constants of main steamline radiation to EU & Hi EU which are set at 07/06/91 Main steamline A radiation 1

Failed N/A 1 & 100000.

2U5144A MAIN SL 2/8 MR/Hr Analog 1.0 N/A N/A This point refelets the quality validation of B stm line red level against E;CS #2 SAS main steamline 8 rad'n P

QV 1.0 E5 N/A N/A the SAS constants of main steamline radiation Lo EU & Ni EU which are set at 07/06/91 Main steamline a radiation 1

Failed N/A 1 & 100000.

2U5026A SG BD RAD 1A CPM Analog 10.0 10.0 N/A This point refelets the quality validation of A steam gen blowdown radiation ERCS #2 SAS stm gen blowdown rad'n P

QV 1.0 E6 1.0 E4 N/A against the SAS constants of steam gen blowdown radiation to EU & Hi EU which 07/06/91 Stm gen blowdown radiation 1

Failed N/A are currently set at 10 & 1,000,000.

2U50154 CNTMNT PRESS PSIG Analog 5.0

-5.0 N/A This point reflects the CV-AVG of contalment pressure WR 717 & 718 sensors.

ERCS C2 SAS avg contaircent press P

CV-AVG 200.0 4.0 N/A 07/06/91 Avg contairwient pressure 2

Failed N/A 2U50134 CNTMNT TEMP DegF Analog 0.0 N/A N/A *1=High alarm is 10 DegF greater than rolling 5 min avg of containment tem.

ERCS C2 SAS avg conteirvnent tem P

Mov AVG 400.0 note *1 N/A This point reflects the CV-AVG of contairunent air tem elevation 697 and 738 07/06/91 Avg containment tem 3

Failed N/A and 755 sensors.

PU5021A H2 CONC ( concentration )

Analog 0.0 N/A N/A This point reflects the CV-AV3 of containment H2 concentration sensors 719 &

EROS #2 SAS avg contairvnent H2 conc P CV-AVG 10.0 N/A N/A 721.

07/06/91 Avg containment H2 conentrn 2 Failed N/A 2U5068A SWST LEVEL 1

Analog 0.0 N/A 2922 Gal /% This point reflects the CV-AVG of RVST ( refueling water storage tank ) level ERCS C2 SAS avg RWST level P

CV-AVG 100.0 N/A 1898 Gal sensors 920 and 921.

07/06/91 Avg RWST level 2

Failed N/A 104105A WIND SPEED MPH Analog 0.0 N/?

N/A Sensor location = meteorlogical tower A 10 meter height.

EXCS C2 Met twr 10M avg wind spd A P

none 100.0 Wi?.

N/A 15 minute moving everage of 30sec readings.

10/16/91 1

10 meter Failed N/A

~

=

Northern States Power Co4mny Prairie Island Nuclear Generating Plant - Unit 2 (Pl2)

NRC-EROS Data point Library Mar 10, 1973 Rev 2.

Page 7 of 7 Lo/Hi PID NRC ERDS PARAMETER EU ANLG/ DIG LO RANGE ALRM/ TRIP CONVERSION FEEDER ERCS POINT DESCRIPTION P/S PROCESS NI RANGE SET-POINT ZERO REF DATE GENERIC /COND DESCRIPfl0N

  1. ';NSR LOCATION FAIL MODE DP TEMP COMP Unique systems description 104106A WIND SPEED MPH Analog 0.0 N/A N/A Sensor location a meteorlogical tower B 10 meter height.

E;CS #2 Met twr 10M avg wind spo B P

none 100.0 N/A N/A 15 minute moving average of 30sec readings.

10/16/91 1

10 meter Failed N/A 174109A WIND D!R Deg Analog 0.0 N/A N/A Sensor location = meteorlogical tower A 10 meter height.

ERCS #2 Pri met twr 10M wind dir A S

360.0 N/A N/A Instantaneous values updated in 30 see intervals.

07/09/91 1

10 meter Falled N/A Indication is in the from direction.

174110A WIND DIR Deg Analog 0.0 N/A N/A Sensor location = meteorlogical tower A 10 meter height.

ERCS 82 Prl met twr 10M wind dir B S

$40.0 N/A N/A Instantaneous values updated in 30 sec intervals.

07/09/91 1

10 meter Failed N/A Indication is in the from direction.

lu2907A STAB CLASS DF/100 Analog

-9.0 N/A N/A Sensor location a meteorlogical tower 10 & 60 meter height.

ERCS C2 Met twr avg delta teco A P

Diff 9.0 N/A N/A This value represents the difference in tenperature in degF/100Ft.

10/16/91 2

10 & 60 M.

Failed N/A 1U2908A STAB CLASS OF/100 Analog

-9.0 N/A N/A Sensor location a meteorlogical tower 10 & 60 meter height.

ERCS #2 Met twr avg detta tenp B P

Diff 9.0 N/A N/A This value represents ?ta dif ference in tenperature in degF/100Ft.

10/16/91 2

10 & 60 M.

Failed N/A 1