Text
a,%
+f.*
UNITED STATES j
e[
NUCLEAR REGULATORY COMMISSION n
- f sp WASHINGT ON, D. C. 20555
%,.... + p#
MAY 161990 I
1 Mr. Clayton W. Brown, president BISCO Construction Group t
Brand Industrial Services -Inc.
2 1420 Renaissance Drive 1
Park Ridge, Illinois 60068
Dear Mr. Brown:
Your letter dated April 18, 1990, outlined concerns regarding NRC Information Notice No. 88-56, " Potential Problems With Silicone Foam Fire Barrier Penetra-tion Seals." The NRC staff has reviewed NRC Information Notice No. 88-56 and your letter and has concluded the following:
(1) Silicone foam appears to be an acceptable material for fire barrier penetration seals provided certain installation parameters are controlled as discussed in NRC Information Notice No. 88-56.
(2) Experience with silicone foam indicates that the method of installetion (e.g.
dammingtechnique),technicalandqualitycontrolofmaterial, materia 1mixingprocess,pouringandcuringprocess,methodoffinal inspection, and training and experience of installing personnel can affect the quality of the fire barrier penetration seals. One important aspect is whether or not a visual inspection of the silicone foam material is
>erformed. NRC staff inspectors have noted that silicone foam vendors Tave procedurally required a " visual inspection" during the installation stage; however, in practice the temporary or permanent dams have not been removed to perform a visual inspection.
l (3) Variousfirebarrierpenetrationse.1nonconformingconditions(e.g.,
i voids, gaps, and splits) have been reported by licensees in the past.
In order to mitigste these nonconforming conditions, licensees have taken the following corrective actions:
developed programs for inspection and periodic reinspection of installed seals including visual inspection of the silicone foam material repaired nonconforming seals evaluated alternative materials for repairing old seals and install-ing new seals o
developed alternative methods for installing and inspecting new silicone foam seals a
/03 U
6 l
[f3 L
NRC File CENTER COPY 9005290079 900516 PlW ORG NRRB
7 fX e
I MAY f 61990 F
Mr. Clayton W. Brown,
(4) Finally, in your letter dated April 18, 1990, you stated in part, " BISCO has always been aware of this potential problem and designed their system around temporary dams that are removed for proper inspection and any i
i necessary repairs." However, the NRC staff understands that BISCO leaves a dam in place on the bottom side of the floor installation (refer to NRC inspection report 99901020/87-01 and tir. Thomas W. Giimore's letter to i
Ellis W. Merschoff dated June 22, 1987, in response to the NRC report).
If you have any additional comments or concerns, please contact Dr. Carl H.
L Berlinger, Chief of the Generic Comunications Branch.
Sincerely, Off inal cl ced by E
E R.onns I. Eurley Thomas E. Murley, Director Office of Nuclear Reactor Regulation i
DISTRIBUTION TEMurley, NRR FJMiraglia, NF.R WTRussell, NRR CERossi, NRR SA;,
g A
u CHBerlinger, NRR b
t'A NCampbell, NRR gg I h yvo4s%g GHolahan, NRR CSmyre, NRR Or,t M e
CVandenburgh, NRR
.p 2 L &
M**~
DMossburg (YTf0909069) g p( m PBaranowsky, NRR JACalvo NRR M*
i JJPetrosino, NRR
(
PDR (w/incomin )-
L-(Centre D Files w7 incoming)a DCB l
DOEA R/F-OGCB R/F NCampbell R/F
//
f f I [8
- SEE PREVIOUS PAGE FOR C0llCURRENCE f
'@r Document Name:
LETTER TO BISCO
/90 05 30
- A NRR d
WTRussell (g
- 0GCB:DOEA:NRR*RVIB:DRIS:NRR *C/0GCB:DOEA:NRR
- D OEA:NRR NCampbell JJPetrosino CHBeritnger CERossi 05/3/90 05/3/90 05/
05/04/90 05/07/90 L
i i
.c v f c
(?} Sl'l?
N