Db b 8Ed ORICi!TAL E

o BALTIMORE G AS AND ELE,QMI,9 {0MPANY.,

i P.O. SON f 47's.

' ' ',/

sAuimont. uAnyLAno rips Amun E.WWm.

4 m m,

$sme

. June 29,1982-

/

Mr. Ronald C. Haynes, Director Docket No. 30-3!7 Offim cf Inspection and Enforcement License No. DPR-53 U. S. Nuclear Regulatory Commisssion y'

Region 1 l

631 Park Amme Kingof Prussia,PA.19406

,- y 4

SUBJECT:

82-29 Unit 1 4

^

Dear Mr.Haynes:

?

  • This letter is to confirm our verbal notification of yorpMriRalph Architzel of the inoperability of both Auxiliary Feedwater Purr.ps while in Mode,7 At 0905 on 6-25-32, U-l entered Mode 3. At $2d, he NRC Resident Irspectx noticed that the handswitches for the Main Steam Isolation

. Valves for the Auxiliary Feedwater Pumps were.iri Pull-to-lock. These handswitches were immediately returned to the normal p6sitio1..

The starty procedure, OP-1, has been modified to kify these handswitches in the normal position. prior to enteriri Mode:3. Abo,.,

Surveillance Test Procedure, STP-0-62 will be modified to re<pire an

~

additional check of these valves prior to entering Mode 3. T#

~

A complete desoiption of this event, including causes and corrective.

action will be addressed in a follow-up report.

r Very truly yours, i

L. B. Russell

' ~ ' "

l Plant Sgerintendcat LBR:fid 4

cc:

3. A.Tiernan R. 'd. Douglass

[

Director, Office of Management R.E. Architzel Information & Program Control L.B.Rtaseli l

L.Tenderlich 8207220538 820629 i

PDR ADOCK 05000317 g'L9 PDR S

.