nT M* S?W N

Commonwealth Edison

[P' b_' 5 LaSalla County Nuclear Station L

3 l'

-r_'

Rural Routo #1, Box 220 Marseilles, Illinois 61341

)/D i

'A2 Telephone 815/357-6761 M' PT

.(

U DF6TI nyysos FileN July 1, 1982 James G. Keppler Regional Administrator Director of Regulatory Operations - Region t il U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Sir:

in accordance with LaSalle County Station Unit 1 Facility Operating i_

License NPF-11, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliances for LaSalle County Nuclear Generating Station Permit No. ILOO48151.

1 R. H. Hol aupciin enden LaSalle County 1 tion RHH/GW/dJp Enclosure cc: DVR Report 1-1-82-109 8207190255 820701 h

gDRADOCK 05000373 PDR

1.

DVR NUMBER:

1-1-82-109 11.

LASALLE COUNTY STATION:

Unit 1 Ill. EVENT DESCRIPTION The N.P.D.E.S. Permit maximum Ilmit for concentration of total suspended solids (15 mg/I) in Outfall 001c - Low Volome Wastes was exceeded in the Regenerative Wastes Solution Discharge Tank on 5/26/82.

Chemical analysis i

of a composite sample for the discharge Indicated the TSS concentration to be 131 mg/1. This occurrence is being reported under Tech Spec, App. B, Section 3.2.,

IV.

PROBABLE CONSEQUENCES OF THE OCCURRENCE The general public's health and safety was not affected by this occurrence.

Total Suspended Solids excursions for this outfall is a continuing situe-tion.

Although no one single source of TSS can he identified, multiple sources will result in probable future excursions.

V.

CAUSE on 5/25/82, clean up af ter maintenance in the area resulted in dirt and debris being hosed down area floor drains'.

These floor drains are routed to the Regen. Wastes Soln. Discharge Tank (0WM03T).

Since no further treatment of this tank prior to discharge is provided, the high total suspended solids from the clean up activities resulted in the N.P.D.E.S.

Permit limit be,ing exceeded.

VI.

CORREYlVEACTION Instructions have been provided to the operators to discontinue flushing excessive amounts of dirt and debris into floor drains.

Also, floor drains routed to N.P.D.E.S. outfalls have been identified and labeled appropriately.

Prepared by:

Chuck Nash s

e a.

Commonwealth Edison jc LaSalla County Nucl ar Station n --

RuralRouta dl, Box 220 M;rs:ilts, llTinois 61341 Telephone 815/357 6761 June 22, 1982, U. S. Environmental Protection Agency

- Region'V, Enforcement.DIvisIonGO-il:N$..dl.U.E 'i 47

.<:)-c.u j c.bW

~

ATTN:'.'Chlef, Compl i ance Uni t 'M? ' ' t -

dshi.

Cr

~ ;d" 230 South Dearborn Street Chicago, Illinois 60604 lilinois Environmental Protection Agency Division of Water Pollution Control Compliance Management Unit 2200 Churchill Road Springfield, Illinois 62706

SUBJECT:

NPDES Noncompliances for LaSalle County. Nuclear Generating ~

Station Permi t No. ILOO48151

-..jTA?J J.iEE. -

2 Dea r '.S I i#.:'~

  • fy.1, fj %.5 & &.,.:,y g..-

~' ~-=

.~*tnii.51-W O.%

+ a.lf p.;.=s L'. Q. j % yi*

54CM::TooorMcsWfthiStYn~dEdl66dit25032 ~

O.thyiirhJiAi ngydFr';5.'Jfe"

'g ii3%yi$'nhh7Ytn:chedNIYRf5,;.

MD

~'

' N y d1 7 dre Nist 4,(ndtM7sf8f"fio F.omp~11'a'sc ta ron m.7~

,, 7,y:y,,

.z

~ ~

m.

~; 7. mgp;y s n 3q, y,yy,y, ; gz,ygr

.if there are any questions, please contact Mr. Charles L. Nash of my staff, at

~

' + -(815) 357-6761, extension 235.

l 1

m 9

/

-+

l Om R.

'H.

Ho L,,..

... i.., Station ~

er tendent RHH/FRL/CLN/djp

~~

',gf

'^

Attch.

cc:

Director of Water Quality, Environmental Affairs i

l l