r PHILADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET P.O. BOX 8699 O

PHILADELPHI A. PA.19101 (215)841 4502 g

fh,] { {O[-

vic t e,e tsms,e r

........u.........

h!r. Ronald C. Ilaynes, Director United States Nuc1 car Regulatory Commission Office of Inspection and Enforcement, Region I 631 Park Avenue King of Prussia, PA 19406

Subject:

USNRC IE Region Letter dated April 26, 1982 RE: Site Inspection of April 12-26, 1982 Inspection Report No. 50-352/82-07 f, 50-353/82-05 Limerick Generating Station, Units 1 f 2 i

File:

QUAL 1-2-2 (352/82-07 f 353/82-05)

Dear h!r. Ilaynes:

In response to the subject letter regarding items identified during the subject inspection of construction activities authori::ed by NRC License Nos. CPPR-106 and -107, we transmit herewith the following:

Attachment I - Response to Appendix A Also enclosed as required by the Notice of Violation, is an affidavit relating to the response.

Should you have any questions concerning these items, we would be pleased to discuss them with you.

i l

Sincerely, k'$kbf i

Attachment Copy to:

Director of Inspection and Enforcement l

United States Nuclear Regulatory Commission Washington, DC 20555 l

J. P. Durr, USNRC Resident Inspector 1

l I

l l

r206100167 820604 PDR ADOCK 05000352 l

C PDR L

~

COMMONWEALTil 0F PENNSYLVANIA ss.

COUNTY OF Pili L AD E L PIII A J0llN S.

KEMPER, being first duly sworn, deposes and says:

That he is Vice President of Philadelphia Electric Company, the holder of Construction Permits CPPR-106 and CPPR-107 for Limerick Generating Station Units 1 and 2; that he has read the foregoing Response to Inspection Report No. 50-352/82-07 and 50-353/82-05 and knows the contents thereof; and that the statemer..s and matters set forth therein are true and correct to the best of his knowledge, information and belief.

$ /d.. /-

l

/~

Subscribed and sworn to before me this M day N t@@V of (L M b. k M Notary Public PATR!CI A D. SCHOLL Natary PuM c, OhdadeWa itdadtt;t:3 Co.

My Commissen Expues Feruny 10. :N

ATTACHMENT I RESPONSE TO APPENDIX A Violation 10CFR50 Appendix B Criterion V requires that activities affecting quality be carried out in accordance with instructions and proced-ures. General Electric Specification 22A2724, Revision 3, Para-i graph 4 and Table I, Paragraph 5, require that components such as reactor protection instrumentation receive periodic inspection for conditions such as protective covers, seals, and damage; and l

that controls and instrumentation be protected from dust, dirt, damage and humidity.

Contrary to the above, the turbine stop and control valve scram bypass pressure transmitters PT-01-lN052 A through D were not inspected and protected as required:

they were deleted from the storage and maintenance program on April 24, 1981 after being partially installed, and their covers and seals were not intact on April 13, 1982.

4 Response To Violation The four installed turbine stop and control valve scram bypass pressure transmitters, PT-01-lN052A through D, are now adequately protected and have been included in the Storage Maintenance Program. All process lines are capped and the conduit taps are either capped or have the conduit connections in place. The instruments are being stored in-place in accordance with the established requirements.

To prevent recurrence Rechtel Power Corporation has included all installed instruments in the Storage Maintenance Program on May 19, 1982. This program covers both Bechtel and GE instrumentation and meets the requirements of GE Specification 22A2724.

Each area and elevation of the plant will have a documented maintenance in-spection performed on a monthly basis by Bechtel Quality Control.

The first storage maintenance activity was performed on May 25, 1982.

a s

I 1/1 352/82-07 353/82-05

.-