P wm ma 3 l t % m Ja TIIE CINCINNATI GAS & ELECTRIC COMPANY cy r
^
ZIMMER POWER STATION, P. O. B0X 201, MOSCOW,0H 45153 CINCINN AR OWO 45201 April 27, 1987 QA-1725 E. A. DORGMAN N St Nion ver rar sict %t U. S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137 Attention:
Mr. J. G. Keppler Director RE:
WM. H. ZIMMER NUCLEAR POWER STATION UNIT 1 1.E. INSPECTION REPORT #81 DOCKET NO.
50-358, CONSTRUCTION PERMIT CPPR-88 W.O.
- 57300 JOB E-5590 FILE NO. NRC-1 Gentlemen:
This letter constitutes a supplementary response to the subject report which identified certain items which potentially did not fully meet Code requirements in piping welds and adjacent base materials.
Our original response, QA-1636, dated Fei;ruary 23, 1982, mis-takenly identified weld HP 43 as being a fillet weld on a thermo-well (the thermowell weld actually being HPK 43).
Subsequent in-vestigation revealed that weld HP 43 was a circumferential butt weld, was in the as welded condition and had a 3/8" vall thickness and a 3/16" reinforcement. The maximum allowable by Code is 5/32".
The above deficiency has been identified on Nonconformance Re-port #C-QAD-82-2208-E. The disposition of this NR will be expedi-ted by CG6E and it is estimated that this NR will be closed out by 5/31/82 M AY 121982 8206070796 820602 PDR ADOCK 05000358 G
F Mr. J. G. Keppler, Director U. S. Nuclear Regulatory Commission Region III April 27, 1982 - QA-1725 Page 2 We trust the above will be found as an acceptable response to the Subject Inspection Report.
Very truly yours, THE CINCINNATI CAS & ELECTRIC COMPANY By E. A. BORGMANN SENIOR VICE PRESIDENT JRV:plc cc: Office of Inspection and Enforcement Washington, D. C. 20555 NRC Resident Inspector Attn:
W. F. Christianson l
l l