Donald A. Wells Manager Ooamy Assurance g

(313) 237 % 57 Edison EEd==

May 10, 1982 EF2-58066 Mr. Janes G. Keppler, Regional Administrator Region III U.S. Nuclear Regulatory Ccmnission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Subject:

Final Report of 10CFR50.55(e) Item on Control Rod Drive (CRD)

Housing Assemblies (#51).

Dear Mr. Keppler:

This is Detroit Edison's final report on the Control Rod Drive (CRD)

Housing Assemblies. The problem was originally reported to Mr. J. Konklin of NRC Region III by Detroit Edison's Mr. H.A. Walker, Supervisor-Construc-tion Quality Assurance, on January 26, l' d.

A Fermi site contractor had noted chips or burrs on the inside of the CRD housing assemblies. These burrs were fastened to the metal underneath the shoulder on the inside of the CRD assemblies, and appeared to be a lack of ccuplete machining of the inside surface. These irregularities did not affect the mating of the CRD thermal sleeve which fits inside in contact with this surface. This had been previously determined by the thermal sleeve trial fit. Results of Detroit Edison's investigation indicate that with the thental sleeve installed it is alnost impossible for the chips to reach the CRD.

It is therefore considered not to have safety impact.

If you have questions concerning this matter, please contact Mr. H.A. Walker, Supervisor-Construction Quality Assurance.

Very truly yours, DAW / HAW /cp 8206040422 820510 ds MAY 2 81982 J( 1 PDR ADOCK 05000341 S

pop

.w.

'Mr. James G. Keppler, Regional Mministrator May 10, 1982 Page 'IWo EF2-58066 cc: Mr. Richard DeYoung, Director

-Office _of Inspection and Enforcement Division of Reactor Inspection Programs U.S. Nuclear Regulatory Ccmuission Washington, D.C. 20555 Mr. Bruce Little, Resident Inspector U.S. = Nuclear Regulatory Ccmnission 6450 North Dixie Highway Newport, Michigan. 48166 i