ML20052H183
| ML20052H183 | |
| Person / Time | |
|---|---|
| Site: | Zimmer |
| Issue date: | 05/06/1982 |
| From: | Borgmann E CINCINNATI GAS & ELECTRIC CO. |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| REF-SSINS-6820 10CFR-050.55E, 10CFR-50.55E, IEB-80-16, QA-1738, NUDOCS 8205200041 | |
| Download: ML20052H183 (1) | |
Text
Tilli CINCINNATI GAS & ELECTRIC COMPANY cff
~'
CINCIN N ATI. OHIO 4 5201 May 6, 1982 Q^
E. A. BORGM AN N SE Neon vtC E FRE S'DE NT U. S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137 Attention:
Mr. James G. Keppler Regional Administrator RE:
WM. II. ZIMMER NUCLEAR POWER STAT',N - UNIT I IE BULLETIN 80-16 & 10CFR50.55(e) - M-16 ROSEMOUNT MODEL 1152 PRESSURE TRANSMITTERS DOCKET #50-358, CONSTRUCTION PERMIT CPPR-88 W.O. #57300 JOB E-5590 FILE NO. NRC-8 & 957-3R Centlemen:
This letter constitutes a final report for both 10CFR50.55(e) M-16 and IE Bulletin 80-16 concerning Rosemount Model 1152 transmitters which could experience an ambiguous output when subjected to an overpressurization input.
The analysis has been completed on the thirty-five (35) safety related BOP transmitters purchased by the Cincinnati Gas & Electric Company. This analysis compared the maximum possible impressed pressure signal to 1407 of each transmitter's design range, which is the point at which the ambiguous output signal begins to appear. Two (2) of the transmitters were found to have the possibility through an extremely unlikely event, to excede the 1407.
Input signal design range. We are thus replacing these two Model 1152 trans-mitters with new Model 1153, fully qualified transmitters which are not subject to the ambiguous output characteristics.
All of the NSSS transmitters supplied by CE were Model 1151's and were not qualified. Therefore, they are all being replaced by Model 1153 transmitters.
It is anticipated that this will be completed by December 31, 1982.
We trust that this wholesale replacement of unqualified and possible design-compromising equipment will fulfill our requirements for responding to IE Bulletin 80-16 and closing 10CFR50.55(e) M-16.
Very truly yours, THE CINCINNTI CAS & ELECTRIC COMPANY 8205200041 820506 By N --
PDR ADOCK 05000358 E. A. BORGMANN S
PDR SENIOR VICE PRESIDENT JEC:ac cc: NRC Senior Resident Inspector Atten:
W. F. Christianson NRC Office of Inspection & Enforcement MAY 171982 Washington, D.C.
20555 2ms xrll2SEJ7 L