ML20052B178

From kanterella
Jump to navigation Jump to search
Advises That Secondary Power Operated Relief Valves in Westinghouse PWRs Should Be Considered safety-related, Appropriately Upgraded & Should Be Covered by Specific Tech Spec Requirement
ML20052B178
Person / Time
Site: 05000000, Kewaunee
Issue date: 02/22/1977
From: Hunter D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Fiorelli G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML18043A232 List:
References
FOIA-82-122 NUDOCS 8204300124
Download: ML20052B178 (1)


Text

UNITED STATES NUCLEAR REGULATORY COiWilSSION REGloN lll 799 ROOSEVELT RO AD CLEN ELLYN. lLLINOtS 60137 February 22, 1977 MEMORANDUM FOR:

G. Fiorelli, Chief, Reactor Operations and Nuclear Support Branch FROM:

D. R. Hunter, Reactor Inspector Reactor Projects Section 2

SUBJECT:

WESTINGHOUSE PRESSURIZED WATER REACTORS, SECONDARY POWER OPERATED RELIEF VALVES During continuing review (my memo to you dated 2/11/77, same subject) of the emergency procedures and the FSAR, Section 14, at the Kewaunee plant concerning the steam generator tube failure incident, an additional question was generated concerning the classification of the secondary steam generator power operated relief valves as nonsafety related in the Kewaunee and other PWR plants.

The secondary power operated relief valves are s>ecifically utilized during a steam generator tube rupture incident, coinci ent with a loss of power (assumed) to cooldown the primary system via t!.e unaffected steam generator

.by releasing steam to the atmosphere.

Subseq'_ent to the cooldown of the plant and the depressurization of the primar" system to below the secondary plant safety valve setpoints, the offsite r: lease can be terminated without exceeding the 10 CFR 100 limits.

Because the secondary power relief valves are being assumed available for the incident by the FSAR safety analysis:

1.

The secondary power operated relief valves should be considered safety related and appropriately upgraded.

2.

The secondary power operated relief valves should be covered by a specific Technical Specifications requirement.

D. R. Hunter Reactor Inspector 0*

  • e, a

=

c 2

(

d

    1. /6-19N 820430011T