ML20051L965

From kanterella
Jump to navigation Jump to search
Forwards Listing of Changes,Tests & Experiments Completed During Apr 1982
ML20051L965
Person / Time
Site: Quad Cities  
Issue date: 05/03/1982
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: Case E
Office of Nuclear Reactor Regulation
References
NJK-82-199, NUDOCS 8205170324
Download: ML20051L965 (2)


Text

$~D - 39'/

a Commonwealth Edison g c, f' Ouad Citi:s Nucl:ar Power Si: tion 22710 206 Avenue North Corcova, Illinois 61242 Telephone 309/654-2241 NJK-82-199 s

to Y

C.)

y, j,CFg,g May 3, 1982

k. n!A y"I!Qa IN2xf IOC 3

Mr. Edson G. Case, Deputy Director

/f Of fice of Nuc1 car Reactor Regulation

/,

U. S. Nuclear Regulatory Commission

'b i 4

Washington, D. C.

20555

\\~

Dear Mr. Case:

Enclosed please find a listing of those changes, tests, and experi-ments completed during the month of April 1982, for Quad-Cities Station Units 1 and 2, DPR-29 and DPR-30 A summary of the safety evaluation is being reported in compliance with 10 CFR 50.59.

Thirty-nine copies are provided for your use.

Very truly yours, COMt0NWEALTH EDISON COMPANY QUAD-CITIES NUCLEAR POWER STATION b

s9l.l h

't/

N. J. Kalivianakis Station Superintendent bb Enclosu re cc:

T. J. Rausch l

F 4, t

82051703 M

r

-q M-4-2-77-46 HPCI Manual Initiation Pushbutton Description The installation of the HPCI Manual Pushbutton will provide a manual fast start capability for the HPCI System, should the need arise.

The time involved will be decreased from 10 minutes to 20 seconds. The installation consisted ~of wiring a pushbutton actuator on the 902-3 panel in parallelivith the existing logic for Reactor vessel ' low-low water level HPCI initiation.

Evaluation This modification will provide a marked decrease in the system initiation

- time to allow faster actuation of the system.

To prevent accidental

-initiation, a plexiglass enclosure is installed around the pushbutton.

The switch was wired with a double set of contacts in series to prevent D.C. arcing.

Since existing components of the HPCI System will not be altered, the margin of safety, as defined in the Technical Specifications, will not be affected.