ML20050B661

From kanterella
Jump to navigation Jump to search
Decommission Annual Rept for 1981
ML20050B661
Person / Time
Site: Peach Bottom 
Issue date: 04/02/1982
From:
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20050B660 List:
References
NUDOCS 8204070098
Download: ML20050B661 (1)


Text

.-

PHILADELPHIA ELECTRIC COMPANY Peach Bottom Atomic Power Station Unit No. 1 Decommission Annual Report Docket No. 50-171 The following summarizes the status of the Peach Bottom Unit No. 1 Decommission Facility for the year of 1981, based on the semiannual inspections required by Technical Specification Requirement 8.2.4(a).

4 1.

There is no significant damage or-structural deterioration observed in the security fence surrounding the exclusion area.

2.

There is no significant damage or structural deterioration observed in the containment vessel, spent fuel building enclosure, or-radwaste room within the exclusion area.

3.

There is no significant damage or structural deterioration observed in the designated barricades within the exclusion area.

4.

There is no condition observed indicating a degradation in the security controls and procedures.

5.

There is no evidence of ground water movement between the exclusion area and outside the exclusion area.

6.

There is no significant change in the radiation or contamination levels in the facility.

7.

There are no removable contamination levels above 100 dpm detected.

8.

The radiation in the spent fuel pool area was less than 0.1 mr/hr.

9.

Maximum airborne activity was 4.6 x 10-9 uCi/cc.

Isotopic analysis identified source to be naturally occurring short lived daughters from the radium present in the concrete.

4 10.

Absolute filter sample on containment equalization line indicate.

Radiation Level - less than 0.1 mR/hr.

Contamination Level - less than 100 dpm 11.

There were no reportable. occurrences reported during the year to the NRC as required by Technical Specification 8.2.4 (b).

(1

_C W. T. Ullrich i

8204070098 820402 PDR ADOCK 05000171 R

PDR

_-.