A THE CINCINNATI GAS & ELECTRIC COMPANY rTF

~~

3 CINCINN ATI. OHIO 4 520t February 10, 1982 QA-1625 E. A. BORGM ANN Semon vicE PAES1 CENT Os

,,/fO Q' D

//

.72CE!'/ED 3

U.

S.

Nuclear Regulatory Commission Cr, M R 021982m-Q Region III 799 Roosevelt Road d UICICM:n tuum Glen Ellyn, Illinois 60137 G

$288 g

Attention:

Mr.

J.

G.

Keppler Q3 p

Director N

RE:

WM.

H.

ZIMMER NUCLEAR POWER STATION-UNIT I 10CFR50.55(e) ITEM M-30 ANDERSON GREENWOOD VALVES WITH MISMARKED FLOW ARROW-DOCKET NO.

50-358, CONSTRUCTION PERMIT CPPR-88, W.O.#57300 JOB E-5590 FILE NO. NRC-8 M-30 Gentlemen:

This letter constitutes a final report concerning the subject condition initially reported to the NRC Resident Inspector as a potentially reportable deficiency under 10CFR50.55(e).

On January 11, 1982, CG6E submitted an interim report, QA-1591, indicating that certain h" instrumentation valves were found to be labeled with flow arrows marked in the incorrect flow direction.

Of primary concern was the possibility that some of these valves may be installed in the improper direction.

To determine the safety-related significance of this condition, CG6E requested that the vendor, Anderson Greenwood Company, perform an investigation of possible valve performance failures should they be utilized in such a position.

The investigation is complete and the results indicate that the valves will function satisfactorily and reliably for design pressure and temperature if installed in either direction when operated in the normally open position, normally closed position, or when operated from one posi-tion to the other.

6\\P B203o30477 e2021o PDR ADOCK 05000350 FEB 241962 S

PDR fgfl

)

Mr.

J.

G.

Keppler February 10, 1982 Page 2 File No. NRC-8 M-30 From the results of this investigation, it has been determined that because this condition could not adversely affect the safety of operations.of the plant, the deficiency is not reportable.

s We trust the above will be found acceptable as a final report under 10CFR50.55(e).

Very truly yours, THE CINCINNATI GAS 6 ELECTRIC COMPANY

(

r

&ct ~

E.

A.

BORGMANN SENIOR VICE PRESIDENT FKP:plc cc:

NRC Resident Inspector Attn:

W.

F.

Christianson NRC Office of Inspection & Enforcement Washington, D.C.

20555 n