Jump to navigation Jump to search
Forwards Rept of Investigation of Ks Gas & Electric Study of Low Concrete Cylinder Strengths of Reactor Containment Bldg Base Mgt. Concludes Util Study Does Not Assure Structural Adequacy of Base Mat Concrete
ML20049A164
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 02/02/1979
From: Hamm R
HAMM ENGINEERS, INC.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20049A161 List:
References
NUDOCS 7903210570
Download: ML20049A164 (1)


Text

3

! HAMM Et!GINEERS. INC. " " * " ^ "

  • CO;43ULTING ENGINEERS RANCr40 LA COSTA. CAtil'ORtilA 02C08
CivlL
  • STRUCTU.'AL (714) 43 G.9871 February 2, 1979 U. S. Nuclear Regulatory Commission Region IV >

611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 ATTU: Mr. W.C. Seidle, Chief Reactor Construction and Engineering Support Branch RE: Report of the Investigation of KG&E Study of the Low Concrete Cylinder Strengths of The Reactor Containment Building Be.se Mat of Wolf Creek Generating Station, Unit No. 1, Located near Burlington, Kansas Gentlemen:

Attached is a copy of the above report. . .

As you know the investigation of the task force could r.ot verify the KG&E conclusion that the base mat concrete neets the upccified strength level and KG&E at its own risR has had considerable construction completed on top of the base mat foundation. Because of the tremendous impact unfavorable results would have on the existing construction, close monitoring of the additional KG&E investigation and a. thorough review of all data of the investigation is recommended. The nonitoring should invo.vc J at least the presence of an NRC representative during the preparation, soaking and-strength testing and verification of the results of any petrographic examination and chemical analysis by a qualified and experienced URC representative.

It is also recommended that NRC give consideratien to independent testing by NRC involving strength testing, petrographic exanination and chemical analysis of any.lov strength base mat cylinder fragments which were not included in the additional KG&E investigation.

We have appreciated the opportunity to participate.in this investigation. If you have any questions ccacerning the report, please let us know.

Very truly yours, f p'l.u J' ( W k w , lN, Rolland C. Hamm, P.E.

990321C67