)i Sacramento Municipal Utility District Docket No. 50-312 Rancho Seco Nuclear Generating Station Litense No. DPR-54 During an NRC inspection conducted on July 12-16, 1993, a violation of NRC requirements was identified.
In accordance with the " General Statement of
.J Policy and the Procedure for NRC Enforcement Actions", 10 CFR Part 2, Appendix
.)
C, the violation is listed below:
A.
Section D6.12 of the licensee's Permanently Defueled Technical Specifications states that:
" Procedures for personnel radiation protection shall be prepared consistent with the requirements of 10 CFR 19, and 10 CFR 20, and shall be approved, maintained, and adhered to for all operations involving 1
personnel radiation exposure.
.l l
Radwaste Control Precedure (RP).309.II.02 " Container Selection and Packaging Requireuents," Section 6.1.5, required the licensee to perform the following "For 2,11 Radwaste Containers,":
j (1)
Complete a Radwaste Container ID Worksheet, RAD-099; (2)
Record the maximum CONTACT and ONE METER dose rates on the lid or top of the container, and indicate the spot on the container in which the maximum contact reading was obtained; (3)
Perform a loose beta / gamma contamination smear on the filled radwaste container prior to storage.
Contrary to the above, radwaste container (ID# B90-592-0'13) was filled on July 21, 1992, and the licensee did not:
(a)
Complete a Radwaste Container ID Worksheet; (b)
Record and indicate that the radwaste container had a maximum cor. tact reading of 410 mr/hr located on the bottom of the radwaste container; (c)
Perform a loose beta / gamma contamination smear on the filled radwaste container prior to storage.
This is a Severity Level IV violation (Supplement N)
Pursuant to the provisions of 10 CFR 2.201, Sacramento Municir,a1 Utility District is hereby required to submit a written statement or explanation to the U.S. Nuclear Commission, ATTN: Document Control Desk, Washington D.C.
20555, with a copy to the Regional Administrator, Region V, within 30 days of the date of the letter transmitting this notice. This reply should clectly be marked as a " Reply te a Notice of Violation" and should include: (1) the reason for the violation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that have been taken to avoid further violations, and (4) the date when full compliance will be achieved.
9308160003 930730 PDR ADOCK 05000312 G
PDR o
5 4
2
- If an adequate reply is not received within the time specified in this Notice, the Commission may issue an order or demand for information as to why the i
license should not be modified, suspended, or revoked, or.why such other action as may be proper should not be taken. Where good cause is shown,.
consideration will be given to extending the respcnse time.
Dated Walnut Creek, California This day of July,1993 f
f
.I 1
)
I
_