.f

)

GENuchar En:rgy Genere Dectnc Compant j

115 Cartner Avenue Sun.ime. CA 95125 1

July 27,1993 Docket No. STN 52-001 i

I i

Chet Poslusny, Senior Project Manager Standardization Project Directorate Associate Directorate for Advanced Reactors and License Renewal Office of the Nuclear Reactor Regulatien

Subject:

Submittal Supporting Accelerated ABWR Schedule - ABWR CDF Sensitivity to ESF Equipment Out of Service

Dear Chet:

The attached tabulation documents results of sensitivity analyses performed to determine tbc impact on ABWR CDF which would result from the removal of ESF equipment from service.

Calculations were performed with the ABWR internal event PRA model, and values presenteo represent changes from the base case CDF value of 1.56E-07 per year. The CDF change for each case reflects the impact of completely removing the identified equipment from service. The change in CDF for any specific out of service time can be obtained by prorating between the base case CDF and that presented for the equipment completely removed from service.

We believe. the attached table responds to all of the calculations which the NRC has requested during our recent meetings in San Jose.

Please provide a copy of this transmittal to Millard Wohl.

Sincerely, ok Wrf Jack Fox Advanced Reactor Programs ec: Alan Beard (GE)

Jack Duncan (GE)

Norman Fletcher (DOE)

Bob Raftery (

Cal Tang (GE t) mm 1

i Y

ll 02003g 9309030391 930727 p

PDR ADOCK 05200001 id A

pyg g

w

Tech Spec Senstivity Runs Case Subsystem OOS fJ1E

_a_

"e Chance Internal Events Base Case 1.56E-07 r

One ECCS Subsystem Out Of Service (005)

RHR A 1.71E-07 1.50E-08 9.62 %

RHRB 1.67E-07 1.10E-08 7.05 %

RHR C 1.62E-07 6.00E-09 3.85 %

HPCF B 3.83E-07 2.27E4)7 145.519 HPCF C 1.68E-07 1.20E-08 7.69 %

RCIC 1.75E-06 1.59E-06 1021.79%

Two ECCS Subsystems 005 HPCF B & HPCF C 7.32E-07 5.76E-07 369.23 %

RCIC & HPCF C 2.15E-06 1.99E-06 1278.21 %

RHR A & RHR B 5.96E-07 4.40E-07 282.05 %

RCIC & RHR B 1.88E 06 1.72E-06 1105.13 %

HPCF B & RHR A 7.05E-07 5.49E-07 351.92 %

RCIC & RHR A (Div.1) 1.99E-06 1.83E-06 1175.64%

RCIC & RHR C 1.88E-06 1.72E-06 1105.13 %

HPCF C & RHR A 3.82E-07 2.26E-07 144.87 %

HPCF C & RHR B 3.99E-07 2.43E-07 155.77 %

HPCF C & RHR C (Div. 3) 4.94E-07 3.38E-07 216.67 %

HPCF B & RHR B (Div. 2)

8. tide-07 7.04E-07 451.28 %

HPCF B & RHR C 8.60E-07 7.04E-07 451.28 %

RHR A & RHR C 4.75E-07 3.19E-07 204.49%

RHR B & RHR C 4.92E-07 336E-07 215.38 %

RCIC & HPCF C 1.90E-06 1.74E-06 1117.95 %

Three ECCS Subsystems OOS RCIC, HPCF B & HPCF C 5.08E-06 4.92E-06 3156.41%

RCIC, RHR B & RHR C 3.94E-06 3.78E-06 2425.64%

HPCF B, HPCF C & RHR A 4.26E-06 4.10E-06 2630.77 %

RHR A RHR B & RHR C 6.58E-06 6.42E-06 4117.95 %

HPCF B RHR A & RHR C 5.80E-06 5 M E-06 3617.95 %

HPCF C, RHR A & RHR B 5.48E-06 5.32E-06 3412.82%

RCIC, HPCF B & RHR C 3.66E-06 3.50E-06 2246.15 %

RCIC, RHR B & HPCF C 3.42E-06 3.26E-06 2092.31%

i l

7/26/03 i

Tech Spec Senstivity Runs Case Subsystem OOS CDF

_A.

'c Chance RCIC, RHR A & RHR B 5.79E-06 5.63E-06 3611.54 %

RCIC, RHR A & HPCF B 5.26E-06 5.10E-06 3271.79 9 RCIC RHR A & HPCF C 4.10E-06 3.94E-06 2528.21%

RCIC, RHR A & RHR C 4.71E-06 4.55E-06 2919.23 %

HPCF 3. RHR B & RCIC 5.34E-06 5.18E-06 3323.087c HPCF B, RHR A & RHR B 9.79E-06 9.63E-%

6175.M W RHR B, HPCF B & HPCF C 6.20E-06 6.04E-06 3874.36%

HPCF B, RHR B & RHR C 8.10E-06 7.94E-06 5092.319 RCIC HPCF C & RHR C 4.15E-06 3.99E-06 2560.269 HPCF C RHR A & RHR C 6.90E-06 6.74E-06 4323.089 HPCF B, HPCF C & RHR C 6.20E-06 6.04E-06 3874.36%

HPCF C. RHR B & RHR C 7.74E-06 7.58E-06 4861.54 %

Suppression Pool Cooling mode of RHR OOS WDPC A 1.56E-07 0.00E+00 0.00 %

WDPC B 1.56E-07 0.00E+00 0.00%

WDPC C 1.56E-07 0.00E+00 0.00 %

WDPC B & WDPC A 1.81E-07 2.50E-08 16.03 %

WDPC A & WDPC C 1.81E-07 2.50E-08 16.03 %

WDPC B & WDPC C 1.81E-07 2.50E-08 16.03 %

WDPC A, WDPC B & WDPC C 6.45E-07 4.89E-07 313.46 %

Standby Service Water Train (s) OOS RCW A 1.56E-07 0.00E+00 0.00 %

RCW B 1.56E-07 0.00E+00 0.00 %

RCW C 1.56E-07 0.00E+00 0.007c RCW A & RCW B 1.81E-07 2.50E-08 16.03 Pc RCW A & RCW C 1.81E-07 2.50E-08 16.03 %

RCW B & RCW C 1.82E-07 2.60E-08 16.67 %

RCW A, RCW B & RCW C 6.45E-07 4.89E-07 313.46 %

Emergency Diesel Generator 005 (CTG

.Available)

EDG C 1.67E-07 1.10E-08 7.05 %

EDG D 1.69E-07 1.30E-08 8.339 EDG E 1.67E-07 1.10E-08 7.05 %

2 mom

t Tech Spec Senstivity Runs e

Case Subsystem OOS CDF

_A "c Chance EDG C & EDG E 2.83E-07 1.27E-07 81.41 %

EDG C & EDG D 2.85E-07 1.29E-07 82.69 %

EDG D & EDG E 3.17E-07 1.61E-07 103.219 Alternate Off-site power 1.70E-07 1.40E-08 8.97 %

line OOS Alternate Off-site power line & Emergency Diesel Generator OOS Alternate Off-site power line &

2.57E-07 1.01E-07 64.74 %

EDG C OOS Alternate Off-site power line &.

2.64E-07 1.08E-07 69.23 %

EDG D 005 Alternate Off-site power line &

2.63E-07 1.07E-07 68.59 %

EDG E OOS All Off-site Power OOS (N 231E-05 2.29E-05 14707.69 %

recovery)

DC Power Division OOS Div.I 2.09E-06 1.93E-06 1239.74 %

Div. 2 1.19E-06 1.03E-06 662.82 %

Div.3 5.94E-07 438E-07 280.77 %

Div. 4 1.56E-07 0.00E+00 0.00%

ADS Valves One Valve OOS 1.56E-07 0.00E+00 0.004 1wo Valves OOS 1.56E-07 0.00E+00 0.00 %

Three Valves OOS 1.56E-07 0.00E+00 0.00 %

Two ECCS Divisions OOS Divisions I & 11 OOS 8.22E-05 8.20E-05 52592.31 %

Divisions I & Ill OOS 5.99E-05 5.97E-05 38297.44 %

Divisions II & III OOS 1.54E-04 1.54E-04 98617.95 %