June 15,1993 Docket No. 50-423 i
Mr. John F. Opeka Executive Vice President, Nuclear Connecticut Yankee Atomic Power Company Northeast Nuclear Energy Company Post Office Box 270 Hartford, Connecticut 06141-0270
Dear Mr. Opeka:
SUBJECT:
APPROVAL OF REQUEST FOR RELIEF FROM ASME CODE REPAIR REQUIREMENTS FOR ASME CLASS 3-PIPING FOR MILLSTONE 3 (TAC N0. M86147)
This letter is in response to your request for relief from ASME Code.
l requirements submitted by letter dated March ?5, 1993. The enclosed Safety Evaluation addresses the temporary use of a rubber patch, in the repair of a 3-inch service water line according to the guidance in Generic Letter 90-05.
Based on the review summarized in the enclosed Safety Evaluation, the staff concludes that there is reasonable assurance that the integrity of service water piping line 3 SWP-003-067-3 will be maintained until permanent repair can be made, but no later than the next scheduled refueling outage. The staff
)
finds that the use of the rubber patch would provide an acceptable level of j
quality and safety. Therefore, based on the above, the proposed use of a rubber patch is acceptable as an alternative to a Code repair, for the above-mentioned period, and is authorized under 10 CFR 50.55a(g)(6)(i).
Sincerely, Original signed by:
Ronald H. Hernan for: John F. Stolz, Director Project Directorate I-4 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
Enclosure:
Safety Evaluation cc w/ enclosure:
g 6]g g g0ggj23 See next page p
PDR DISTRIBUTION:
Docket File JCalvo OPA NRC & Local PDRs JStolz OC/LFDCB PD I-4 Plant SNorris VMcCree, EDO TMurley/FMiraglia VRooney LTDoerflein, RI JPartlow OGC MBanic
+
EJordan ERossi ggg g
,c p'
m.
GHill (2)
L JLieberman SVarga ACRS (10)A PM:PDI-4 bih4 :PDI-44 OGC M(j OFFICE LA:PDI-4 3
SEY VRooney:bp JStolz k M -"Si xiar.
NAME O
mw i
DATE b/1/93 (b/#1/93 6 / 7 /93 J
k / W93
/ /
i 0FFICIAL RECORD COPY t
d Document Name: G:\\R00NEY\\8614rj l
J
p O
Y E!
.fi A
lig[s !
i n
UNITED STATES NUCLEAR REGULATORY COMMISSION g
,f wasmucron. o c :osssem June 15, 1993 Docket No. 50-423 Mr. John F. Opeka Executive Vice President, Nuclear Connecticut Yankee Atomic Power Company Northeast Nuclear Energy Company Post Office Box 270 Hartford, Connecticut 06141-0270
Dear Mr. Opeka:
SUBJECT:
APPROVAL OF REQUEST FOR RELIEF FROM ASME CODE REPAIR REQUIREMENTS FOR ASME CLASS 3-PIPING FOR MILLSTONE 3 (TAC NO. M86147)
This letter is in response to your request for relief from ASME Code requirements submitted by letter dated March 25, 1993. The enclosed Safety Evaluation addresses the temporary use of a rubber patch, in the repair of a 3-inch service water line according to the guidance in Generic Letter 90-05.
Based on the review summarized in the enclosed Safety Evaluation, the staff concludes that there is reasonable assurance that the integrity of service water piping line 3 SWP-003-067-3 will be maintained until permanent repair can be made, but no later than the next scheduled refueling outage. The staff finds that the use of the rubber patch would provide an acceptable level of quality and safety. Therefore, based on the above, the proposed use of a rubber patch is acceptable as an alternative to a Code repair, for the above-mentioned period, and is authorized under 10 CFR 50.55a(g)(6)(i).
Sincerely,
.)
f'.-.
ftTAW $. bLhhb I~
John F. Stolz, Director Project Directorate I-4 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
Enclosure:
Safety Evaluation cc w/ enclosure:
See next page
l Mr. John F. Opeka Millstone Nuclear Power Station
(
Northeast Nuclear Energy Company Unit 3 i
{
cc:
l Gerald Garfield, Esquire R. M. Kacich, Director i
Day, Berry and Howard Nuclear Licensing Counselors at Law Northeast Utilities Service Company City Place Post Office Box 270 t
Hartford, Connecticut 06103-3499 Hartford, Connecticut 06141-0270 l
W. D. Romberg, Vice President J. P. Stetz, Vice President Nuclear Operations Services Haddam Neck Plant Northeast Utilities Service Company Connecticut _ Yankee Atomic Power Company Post Office Box 270 362 Injun Hollow Road 4
Hartford, Connecticut 06141-0270 East Hampton, Connecticut 06424-3099 Kevin McCarthy, Director Regional Administrator Radiation Control Unit Region I Department of Environmental Protection U.S. Nuclear Regulatory Commission State Office Building 475 Allendale Road Hartford, Connecticut 06106 King of Prussia, Pennsylvania 19406-Allan Johanson, Assistant Director First Selectmen Office of Policy and Management Town of Waterford Policy Development and Planning Division Hall of Records j
80 Washington Street 200 Boston Post Road Hartford, Connecticut 06106 Waterford, Connecticut 06385 S. E. Scace, Vice President P. D. Swetland, Resident Inspector Millstone Nuclear Power Station Millstone Nuclear Power Station Northeast Nuclear Energy Company c/o U.S. Nuclear Regulatory Commission Post Office Box 128 Post Office Box 513 4
Waterford, Connecticut 06385 Niantic, Connecticut 06357 F. R. Dacimo, Nuclear Unit Director M. R. Scully, Executive Director i
Millstone Unit No. 3 Connecticut Municipal Electric Northeast Nuclear Energy Company Energy Cooperative l
Post Office Box 128 30 Stott Avenue Waterford, Connecticut 06385 Norwich, Connecticut 06360 Burlington Electric Department David W. Graham c/o Robert E. Fletcher, Esq.
Fuel Supply Planning Manager 271 South Union Street Massachusetts Municipal Wholesale Burlington, Vermont 05402 Electric Company Post Office Box 426 i
Nicholas S. Reynolds Ludlow, Massachusetts 01056 Winston & Strawn
)
1400 L Street, NW G. H. Bouchard, Director-Washington, DC 20005-3502 Nuclear Quality Services i
Northeast Utilities Service Company Post Office Box 270 Hartford, Connecticut 06141-0270 3
i