p*

  • t ou f.

?g UNITED STATES

[ [(,

j NUCLEAR REGULATORY COMMISSION y

WASHINGTON, D.C. 20555 0001

,y ~.j COMMONWEALTH EDISON COMPANY AND IOWA-ILLIN0IS GAS AND ELECTRIC COMPANY DOCKET NO. 50-254 OVAD CITIES NUCLEAR POWER STATION. UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 142 License No. DPR-29 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application Sr amendment by Commonwealth Edison Company (the licensee)

.ed February 26, 1993, complies with the standards and iequirements of tne Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the pravisions of the Act, and the rules and regulations of the Ccmmission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 r; Part 51 of the Commission's regulations and all applic w requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.B. of Facility Operating License No. DPR-29 is hereby amended to read as follows:

S 9306080289 930528 DR ADOCK 05000254 p

PDR

i

. B.

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.142, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION 1

UM $.

if ames E. Dyer, Director Project Directorate III-2 Division of Reactor Projects - III/IV/V Office of Nuclear Reactor Regulation i

Attachment:

Changes to the Technical Specifications i

i Date of Issuance: May 28, 1993 1

, -.,----.~ ---

ATTACHMENT TO LICENSE AMENDMENT NO. 142 i

BCILITY OPERATING LICENSE NO. DPR-29 DOCKET NO. 50-254 Revise the Appendix A Technical Specifications by removing the page identified below and inserting the attached page. The revised page is identified by the captioned amendment number and contains a marginal line indicating the area of change.

REMOVE INSERT 3.9/4.9-7 3.9/4.9-7 I

n

QUAD-CITIES DPR-29 a.

By performance of a CHANNEL FUNCTIONAL TEST each time the plant is in COLD SHUTDOWN for a period of more than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, unless performed in the previous 6 months.

b.

At least once per operating cycle by demonstrating the operability of overvoltage,-

undervoltage, and underfre-quency protective instru-mentation by performance of a channel calibration including simulated auto-matic activation of the protective' relays, tripping logic, and output circuit breakers, and verifying the following setpoints:

(1) overvoltage 126.5 V = 2.5%

Min.

123.3 V Max.

129.6 V (2) undervoltage 108 V = 2,5%

Min.

105.3 V Max.

110.7 V-(3) underfrequency 56.0 Hz 1%

of 60 Hz Min.

55.4 Hz Max.

56.6 Hz 3.9/4.9-7 Amendment No. 142.

...o r o,

v

't UNITED STATES j

)Z j

NUCLEAR REGULATORY COMMISSION

,C WASHINGTON, D.C. 20556-0001

'%,.....f COMMONWEALTH EDISON COMPANY AND IOWA-ILLIN0IS GAS AND ELECTRIC COMPANY DOCKET NO. 50-265 OVAD CITIES NUCLEAR POWER STATION. UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 137 License No. DPR-30 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Commonwealth Edison Company (the licensee) dated February 26, 1993, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended -(the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regula!. )ns and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.B. of facility Operating License No. DPR-30 is herehy amended to read as follows:

B.

Technical Specifications The Technical. Specifications contained in Appendices A and B, as revised through Amendment No.137 are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION ll(Y.

AhI ames E. Dyer, Director Project Directorate III-2 Division of Reactor Projects - III/IV/V Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: May 28, 1993 I

T gv.-g

.a v

t.

. - - + - *

.e--.-

a--


~

4

)

ATTACHMENT TO LICENSE AMENDMENT NO.137

]

FACILITY OPERATING LICENSE NO. DPR-30 DOCKET N0. 50-265 Revise the Appendix A Technical Specifications by removing the page identified below and inserting the attached page.

The revised page is identified by the captioned amendment number and contains a marginal line indicating the area of change.

REMOVE INSERT 3.9/4.9-7 3.9/4.9-7 L

T t

I i

i

Quad-Cities 4

DPR-30

b. Verifying the diesel starts from ambient condition on the auto-start signal, energizes the emergency buses with permanently connected loads, i

energizes the auto-connected emergency loads through the load sequencer, and Operates for greater than 5 minutes while its generator is loaded with the emergency loads.

3. When the reactor is in the Cold Shutdown or Refueling mode, a minimum of one diesel generator (either the Unit diesel generator or the Unit 1/2 diesel generator) shall be operable whenev9r any work is being done wMch has the potential for draining the vessel, secondary containment is required, or a core or containment cooling system is required.

F. REACTOR PROTECTION BUS POWER F. REACTOR PROTECTION BUS POWER MONITORING SYSTEM MONITORING SYSTEM

1. Two RPS electric power monitoring
1. The RPS Bus power monitoring channels for each inservice RPS system instrumentation shall be MG set or inservice alternate determined OPERABLE:

power source shall be OPERABLE except when the reactor is in the

a. By performance of a CHANNEL SHUTDOWN mode.

FUNCTIONAL TEST each time the plant is in COLD SHUTDOWN for a period of more than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, unless performed in the previous 6 months.

b. At least once per operating cycle by demonstrating the operabihty of overvoltage, undervoltage, and the underfrequency protective instrumentation by performance of a channel calibration including simulated automatic activation of the protective relays, tripping logic, and output circuit breakers,and verifying the following setpoints:

3.9/4.9-7 Amendment No. 137

.