ML20044G540

From kanterella
Jump to navigation Jump to search
Responds to 930408 Fax Concerning Application of LBB to Unit 2.Opposes Proposal to Set Limits at Extreme Range of Leak Detection Capability
ML20044G540
Person / Time
Site: Beaver Valley
Issue date: 04/26/1993
From: Wichman K
Office of Nuclear Reactor Regulation
To: Choi Y
KOREA, REPUBLIC OF (SOUTH KOREA)
References
NUDOCS 9306030272
Download: ML20044G540 (1)


Text

.

APR 2 5 m3 l

t Dr. Young Hwan Choi f

Reactor Systems Department Korea Institute of Nuclear Safety P.O. Box 16 Daeduk-danji, Taejon Korea I

Dear Dr. Chot:

l This is in response to your fax of April 8,1993. First of all let me thank you for Mr. Kim's address and fax number.

I intend to contact him soon.

In regard to your questions concerning the application of LBB to Beaver l

Valley, Unit 2, it is my belief that it is not good engineering practice to set limits (e.g., 0.5 gpm leakage) at the extreme range of leak detection capability.

If, however, all of the leak detection systems can reliably detect 0.5 gpm leakage, then there should be no need for administrative procedures and 0.5 gpm should be the Technical Specification limit in lie 1 of 1.0 gpm.

It should also be noted that local leak detection devices (e.g.

acoustic emission monitors) can also be utilized as required for LBB purposes.

Relative to the current status of the 10 CFR 50.55(a)(g) endorsement of ASME Code Section XI please refer any questions to:

Mr. Gilbert C. Millman Office of Nuclear Regulatory Research Mail Stop NLS 2178 U.S. N.R.C.

i Washington, D.C. 20555 FAX: 301-492-3696 l

Just after my last communication with you (my fax dated March 24, 1993) I was informed that my planned trip to Korea was not approved. As part of an agency l

budget cutting process stemming from President Clinton's executive order, most l

foreign travel by NRC personnel has been eliminated. My personal regrets at l

l not being able to visit you in May. We will however, keep communicating to our mutual benefit.

l Best regards, i

l Keitls/

R. Wichman, Chief l

Material Integrity Section, EMCB i

U.S. Nuclear Regulatory Commission Washington, D.C.

20555 l

cc:

R. Hauber, IP DISTRIBUTION:

G. Millman, RES Costret F Het i

ENCS-RF..

KRWichman-I k.

j KW man:tc 0FFICIAL RECORD COPY i

4 Q 93 WP FILENAME: g:\\WICHMAN\\RSPNSE.KRW

.l E70024 g8 i

9306030272 930426 L

?

PDR ADDCK 05000412 Q,[Ig P

PDR j

i

, +