ML20044G290

From kanterella
Jump to navigation Jump to search

Discusses Review of Licensee 910524 Submittal Requesting NRC to Reaffirm Approval of Portion of Earlier Request for Relief from Certain Requirements of App R to 10CFR50 & Requests Addl Info
ML20044G290
Person / Time
Site: Waterford 
Issue date: 05/20/1993
From: Wigginton D
Office of Nuclear Reactor Regulation
To: Barkhurst R
ENTERGY OPERATIONS, INC.
References
TAC-M80691, NUDOCS 9306020282
Download: ML20044G290 (4)


Text

_

pg ff k

UNITED STATES

[

}

NUCLEAR REGULATORY COMMISSION f

g WASHINGTON, D.C. 205564101 May 20, 1993 Docket No. 50-382 1

Mr. Ross P. Barkhurst Vice President Operations Entergy Operations, Inc.

Post Office Box B Killona, Louisiana 70066

Dear Mr. Barkhurst:

SUBJECT:

REAFFIRMATION OF APPROVAL OF AN EARLIER REQUEST FOR RELIEF FROM 10 CFR PART 50 APPENDIX R REQUIREMENT (TAC NO. M80691)

We have reviewed Entergy Operations, Inc.'s submittal of May 24, 1991, in which the NRC was requested to reaffirm approval of a portion of an earlier request for relief from certain requirements of Appendix R to 10 CFR Part 50 due to discrepancies identified in the justification of the original submittal of March 26, 1984.

1 There is no fire damper in the east wall of fire area BB or the north wall of fire area 8C. The original submittal indicated that there was a lack of fire dampers in these areas. However, the documented basis in the* original submittal, upon which it appears that the NRC accepted the unprotected openings, was that the " Fire severity of areas adjacent to each damper are less than the fire rating of subject damper." The applicable Supplemental Safety Evaluation Report (SSER 8) did not address the lack of fire dampers in the east wall of fire area BB and the north wall of fire area 8C. SSER 8 4

indicated that "If all of the combustibles on one side of the fire damper were totally consumed in a fire, the damper would still maintain the integrity with a conservative margin."

It appears that the staff believed that dampers were installed. Therefore, we cannot reaffirm the exemption for a lack of a fire damper in the duct between the east wall fire area BB and north wall fire area 8C.

We have reviewed the information concerning Entergy's justification regarding the lack of fire dampers, but require additional information to assess whether or not an exemption should be granted for lack of fire dampers in these areas.

In addition to the information we have received, please provide the following information:

1.

a detailed description of the duct between the east wall of fire area 8B and north wall fire area 8C, including the function (supply or exhaust), air flow routes, design drawings, materials of construction, the size and number of openings in the duct between fire areas 8B and 8C; i

~q

+

i 9306020282 930520 rgii PDR ADOCK 05000382

.g P

PDR

')

Mr. Ross P. Barkhurst.

2.

a complete description of combustible fuel packages (e.g., cable trays / location), including maximum anticipated transient fuel packages and type of fire expected (type of heat release rates) for fire areas 8B and 8C and the corridor; 3.

the distances. (horizontal and vertical) between the fixed combustibles and the opening of the duct in both fire areas; 4.

the shortest distances between redundant safe shutdown equipment (including cabling), considering the pathway through the duct; and 5.

fire detection and sprinkler system as-built drawings for fire areas 8B and 8C.

^

This requirement affects fewer than ten respondents, therefore, is not subject to Office of Management and Budget review under Public Law 96-511.

If there are any questions, please let us know.

Sincerely, ORIGINAL SIGNED BY:

David L. Wigginton, Senior Project Manager Project Directorate IV-1 Division of Reactor Projects - III/IV/V Office of Nuclear Reactor Regulation cc: See next page DISTRIBUTION Docket File NRC & Local PDRs PD4-1 Reading D. Wigginton E. Adensam T. Chan i

P. Noonan ACRS (10) (P-315)

OGC (15B18) l J. Roe A. B. Beach, RIV 0FC LA:PD4-1 A M PMEPA4-1l D(A):PD4-1 l

NAME PNoona'n[#

DWI h on:pk TChan N DATE

'5/ /?//93 4/tM/93 I ko /9'3 COPY YES h YES/NO YES) 0 l 0FFICIAL RECORD COPY Document Name: WAT80691.ltr

r C

Mr. Ross P. Barkhurst I 2.

a complete description of combustible fuel packages (e.g., cable trays / location), including maximum anticipated transient fuel packages and type of fire expected (type of heat release rates) for fire areas 8B and BC and the corridor; 3.

the distances (horizontal and vertical) between the fixed combustibles and the opening of the duct in both fire areas; 4.

the shortest distances between redundant safe shutdown equipment (including cabling), considering the pathway through the duct; and 5.

fire detection and sprinkler system as-built drawings for fire areas 8B and 8C.

l This requirement affects fewer than ten respondents, therefore, is not subject to Office of Management and Budget review under Public Law 96-511.

If there I

are any questions, please let us know.

Sincerely, David L. Wi on, Senior Project Manager Project Directorate IV-1 Division of Rea: tor Projects - III/IV/V Office of Nuclear Reactor Regulation cc: See next page L

?

i l

i b

b

e 5 1 f'

Mr. Ross P. Barkhurst Entergy Operations, Inc.

Waterford 3 cC:

Mr. Hall Bohlinger, Administrator Regional Administrator, Region IV Radiation Protection Division U.S. Nuclear Regulatory Commission Office of Air Quality and Nuclear Energy 611 Ryan Plaza Drive, Suite 1000 Post Office Box 82135 Arlington, Texas 76011 Baton Rouge, Louisiana 70884-2135 Resident Inspector /Waterford NPS Mr. John R. McGaha Post Office Box 822 Vice President, Operations Killona, Louisiana 70066 i

Support Entergy Operations, Inc.

Parish President Council P. O. Box 31995 St. Charles Parish Jackson, Mississippi 39286 P. O. Box 302 Hahnville, Louisiana 70057 William A. Cross Bethesda Licensing Office Mr. Donald C. Mintz, President 3 Metro Center and Chief Executive Officer Suite 610 Entergy Operations, Inc.

Bethesda, Maryland 20814 P. O. Box 31995 Jackson, Mississippi 39286 Mr. Robert B. McGehee i

Wise, Carter, Child & Caraway Chairman P.O. Box 651 Louisiana Public Service Commission Jackson, Mississippi 39205 One American Place, Suite 1630 Baton Rouge, Louisiana 70825-1697 Mr. D. F. Packer General Manager H ant Operations Mr. R. F. Burski, Director Entergy Operations, Inc.

Nuclear Safety P. O. Box B Entergy Operations, Inc.

Killona, Louisiana 70066 P. O. Box B Killona, Louisiana 70066 Mr. L. W. Laughlin, Licensing Manager Entergy Operations, Inc.

~ ~ ~ ~

-1 P. O. Box B Killona, Louisiana 70066 Winston & Strawn Attn:

N. S. Reynolds 1400 L Street, N.W.

Hashington, DC 20005-3502 f

.s 1