Forwards SE Accepting Class IE EDG Qualification Rept
ML20044G007
Person / Time
Site: Calvert Cliffs  
Issue date: 05/19/1993
From: Mcdonald D
Office of Nuclear Reactor Regulation
To: Denton R
BALTIMORE GAS & ELECTRIC CO.
Shared Package
ML20044G008 List:
References
TAC-M85715, TAC-M85716, NUDOCS 9306010312
Download: ML20044G007 (3)


Text

..

/

UNITED STATES j

j NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20SE0001

$q,

[

Hay 19, 1993 Docket Nos. 50-317 and 50-318 a

l Mr. Robert E. Denton Vice President - Nuclear Energy Baltimore Gas & Electric Company i

Calvert Cliffs Nuclear Power Plant 1650 Calvert Cliffs Parkway Lusby, Maryland 20657-4702 l

Dear Mr. Denton:

l a

SUBJECT:

CLASS IE EMERGENCY DIESEL GENERATOR QUALIFICATION REPOR1, CALVERT CLIFFS NUCLEAR POWER PLANT, UNIT I (TAC NO. M85715) AND UNIT 2 (TAC NO. M85716)

By letter dated January 29, 1993, as superceded by letter dated April 7, 1993, i

Baltimore Gas and Electric Company (BG&E) submitted a request for NRC review and approval. of a proposed qualification program for two new safety-related (Class IE) emergency diesel generators.(EDGs) for the Calvert Cliffs Nuclear i

Power Plant, Units 1 and 2.

The EDGs are being added in response to 10 CFR l

50.63, " Loss of All Alternating Current Power," which is referred'to as the-j station blackout (SBO) rule.

By letter dated May 7, 1993, BG&E indicated that it had reviewed its initial' commitment to the SB0 rule for adding two safety-related EDGs and determined that it would add one safety-related and one nonsafety EDG. The proposed design, as the result of this change, will have two dedicated' safety-related l

EDGs per unit with the installed nonsafety EDG being capable of providing-power to either of the Calvert Cliffs Units as an alternative ac power source.

BG&E further indicated that it would provide the details necessary for the NRC i

staff's review and approval of the proposed change from its initial response to the SB0 rule.

l

.The proposed change does n'ot affect the NRC staff's enclosed Safety f

Evaluation (SE) of the qualification program for the safety-related EDG. The staff has reviewed the qualification program and has determined that it is consistent with the recommendations of Regulatory Guide 1.9, Revision 3 (draft), " Selection, Design, Qualification,' Testing and Reliability of.

Emergency Diesel Generator Units Used as Class IE Onsite Electric Power Systems at Nuclear Power Plants," and the requirements of the Institute'of Electronic and Electrical Engineers (IEEE) 387-1984, "IEEE Standard Criteria Generating Stations."

for Diesel-Generator Units Applied as Standby Power Supplies for Nuclear Power 1

240011 k% ps a m. m a a: m m m.2 ;

p p Cr o_

u.

3 9306010312 930519

-ADOCK 050003 l.,

gDR m

Mr. Robert E. Denton May 19, 1993 This acceptance is predicated on the results of the 35 start and load tests confirming the ratings and capabilities of the EDG as discussed in the enclosed SE.

We have completed all actions related to TAC Nos. M85715 and M85716. New TAC Nos. will be opened for tracking the staff's actions in reviewing BG&E's proposed change to the SB0 rule Sincerely, i

~ -l- (

Daniel G. Mcdonald, Senior Project Manager Project Directorate I-1 I

Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Enclosure:

Safety Evaluation cc w/ enclosure:

See next page l

l

'A

Mr. Robert E. Denton Calvert Cliffs Nuclear Power Plant Baltimore Gas & Electric Company Unit Nos. I and 2 CC*

Mr. Michael Moore, President Mr. Joseph H. Walter Calvert County Board of Engineering Division Commissioners Public Service Commission of 175 Main Street Maryland Prince Frederick, Maryland 20678 American Building 231 E. Baltimore Street D. A. Brune, Esquire Baltimore, Maryland 21202-3486 General Counsel Baltimore Gas and Electric Company Kristen A. Burger, Esquire P. O. Box 1475 Maryland People's Counsel Baltimore, Maryland 21203 American Building, 9th Floor 231 E. Baltimore Street Jay E. Silberg, Esquire Baltimore, Maryland 21202 Shaw, Pittman, Potts and Trowbridge 2300 N Street, NW Patricia T. Birnie, Esc.uire Washington, DC 20037 Co-Director Maryland Safe Energy Coalition Mr. G. L. Detter, Director, NRM P. O. Box 33111 Calvert Cliffs Nuclear Power Plant Baltimore, Maryland 21218 1650 Calvert Cliffs Parkway Lusby, Maryland 20657-47027 Resident Inspector c/o U.S. Nuclear Regulatory Commission P. O. Box 287 St. Leonard, Maryland 20685 Mr. Richard I. McLean Administrator - Radioecology Department of Natural Resources 580 Taylor Avenue Tawes State Office Building B3 Annapolis, Maryland 21401 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, Pennsylvania 19406

\\

.