ML20042D697
| ML20042D697 | |
| Person / Time | |
|---|---|
| Site: | Pilgrim |
| Issue date: | 01/31/2019 |
| From: | John Lamb Division of Operating Reactor Licensing |
| To: | |
| SECY/RAS | |
| References | |
| NRC-2018-0279 | |
| Download: ML20042D697 (4) | |
Text
816 Federal Register / Vol. 84, No. 21 / Thursday, January 31, 2019 / Notices Date of initial notice in Federal Register: March 13, 2018 (83 FR 10921). The supplemental letters dated February 9, 2018 and July 17, 2018, provided additional information that clarified the application, did not expand the scope of the application as originally noticed, and did not change the NRC staffs original proposed no significant hazards consideration determination as published in the Federal Register.
The Commissions related evaluation of the amendments is contained in a Safety Evaluation dated December 19, 2018.
No significant hazards consideration comments received: No.
Tennessee Valley Authority, Docket No.
50-391, Watts Bar Nuclear Plant, Unit 2, Rhea County, Tennessee Date of amendment request: October 31, 2018.
Brief description of amendment: The amendment revised the completion date for License Condition 2.C.(5) for the Watts Bar Nuclear Plant, Unit 2, regarding the completion of action to resolve the issues identified in NRC Bulletin 2012-01, Design Vulnerability in Electric Power System (ADAMS Accession No. ML12074A115), from December 31, 2018, to December 31, 2019, to align with the remainder of the Tennessee Valley Authority fleet and with the nuclear industry.
Date of issuance: December 21, 2018.
Effective date: As of the date of issuance and shall be implemented immediately.
Amendment No.: 23. A publicly-available version is in ADAMS under Accession No. ML18334A333; documents related to this amendment are listed in the Safety Evaluation enclosed with the amendment.
Facility Operating License No. NPF-96: The amendment revised the Facility Operating License.
Date of initial notice in Federal Register: November 14, 2018 (83 FR 56876).
The Commissions related evaluation of the amendment and final determination of no significant hazards consideration is contained in a Safety Evaluation dated December 21, 2018.
No significant hazards consideration comments received: One comment was received on December 14, 2018. The public comment and the NRC staff response are provided in the Safety Evaluation.
Dated at Rockville, Maryland, this 25th day of January 2019.
For the Nuclear Regulatory Commission.
Gregory F. Suber, Director, Division of Operating Reactor Licensing, Office of Nuclear Reactor Regulation.
[FR Doc. 2019-00358 Filed 1-30-19; 8:45 am]
BILLING CODE 7590-01-P NUCLEAR REGULATORY COMMISSION
[Docket Nos. 50-293 and 72-1044; NRC-2018-0279]
Pilgrim Nuclear Power Station; Consideration of Approval of Transfer of License and Conforming Amendment AGENCY: Nuclear Regulatory Commission.
ACTION: Application for direct and indirect transfers of license; opportunity to comment, request a hearing, and petition for leave to intervene.
SUMMARY
- The U.S. Nuclear Regulatory Commission (NRC) received and is considering approval of an application filed by Entergy Nuclear Operations, Inc. (ENOI) on November 16, 2018. The application seeks NRC approval of the direct and indirect transfers of Renewed Facility Operating License No. DPR-35 for Pilgrim Nuclear Power Station (Pilgrim) as well as the general license for Pilgrim Independent Spent Fuel Storage Installation (ISFSI), collectively the Licenses. ENOI on behalf of itself and Entergy Nuclear Generation Company (ENGC), Holtec International (Holtec), and Holtec Decommissioning International, LLC (HDI) requests that the NRC consent to (1) the indirect transfer of control of the Licenses to Holtec; and (2) the direct transfer of ENOIs operating authority to HDI. The NRC is also considering amending the renewed facility operating license for administrative purposes to reflect the proposed transfer. The application contains sensitive unclassified non-safeguards information (SUNSI).
DATES: Comments must be filed by March 4, 2019. A request for a hearing must be filed by February 20, 2019. Any potential party as defined in § 2.4 of title 10 of the Code of Federal Regulations (10 CFR), who believes access to SUNSI is necessary to respond to this notice must follow the instructions in Section VI of the SUPPLEMENTARY INFORMATION section of this notice.
ADDRESSES: You may submit comments by any of the following methods (unless this document describes a different method for submitting comments on a specific subject):
- Federal Rulemaking website: Go to http://www.regulations.gov and search for Docket ID NRC-2018-0279. Address questions about Docket IDs in Regulations.gov to Krupskaya Castellon; telephone: 301-287-9221; email:
Krupskaya.Castellon@nrc.gov. For technical questions, contact the individual(s) listed in the FOR FURTHER INFORMATION CONTACT section of this document.
- Email comments to:
Hearingdocket@nrc.gov. If you do not receive an automatic email reply confirming receipt, then contact us at 301-415-1677.
- Fax comments to: Secretary, U.S.
Nuclear Regulatory Commission at 301-415-1101.
- Mail comments to: Secretary, U.S.
Nuclear Regulatory Commission, Washington, DC 20555-0001, ATTN:
Rulemakings and Adjudications Staff.
- Hand deliver comments to: 11555 Rockville Pike, Rockville, Maryland 20852, between 7:30 a.m. and 4:15 p.m.
(Eastern Time) Federal workdays; telephone: 301-415-1677.
For additional direction on obtaining information and submitting comments, see Obtaining Information and Submitting Comments in the SUPPLEMENTARY INFORMATION section of this document.
FOR FURTHER INFORMATION CONTACT: John G. Lamb, Office of Nuclear Reactor Regulation, telephone: 301-415-3100, email: John.Lamb@nrc.gov; U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001.
SUPPLEMENTARY INFORMATION:
I. Obtaining Information and Submitting Comments A. Obtaining Information Please refer to Docket ID NRC-2018-0279 when contacting the NRC about the availability of information for this action. You may obtain publicly-available information related to this action by any of the following methods:
- Federal Rulemaking website: Go to http://www.regulations.gov and search for Docket ID NRC-2018-0279.
- NRCs Agencywide Documents Access and Management System (ADAMS): You may obtain publicly-available documents online in the ADAMS Public Documents collection at http://www.nrc.gov/reading-rm/
adams.html. To begin the search, select Begin Web-based ADAMS Search. For problems with ADAMS, please contact the NRCs Public Document Room (PDR) reference staff at 1-800-397-4209, 301-415-4737, or by email to pdr.resource@
nrc.gov. The ADAMS accession number for each document referenced (if it is VerDate Sep<11>2014 20:21 Jan 30, 2019 Jkt 247001 PO 00000 Frm 00171 Fmt 4703 Sfmt 4703 E:\\FR\\FM\\31JAN1.SGM 31JAN1 amozie on DSK3GDR082PROD with NOTICES1
817 Federal Register / Vol. 84, No. 21 / Thursday, January 31, 2019 / Notices available in ADAMS) is provided the first time that it is mentioned in this document.
- NRCs PDR: You may examine and purchase copies of public documents at the NRCs PDR, Room O1-F21, One White Flint North, 11555 Rockville Pike, Rockville, Maryland 20852.
B. Submitting Comments Please include Docket ID NRC-2018-0279 in your comment submission.
The NRC cautions you not to include identifying or contact information that you do not want to be publicly disclosed in your comment submission.
The NRC will post all comment submissions at http://
www.regulations.gov as well as enter the comment submissions into ADAMS.
The NRC does not routinely edit comment submissions to remove identifying or contact information.
If you are requesting or aggregating comments from other persons for submission to the NRC, then you should inform those persons not to include identifying or contact information that they do not want to be publicly disclosed in their comment submission.
Your request should state that the NRC does not routinely edit comment submissions to remove such information before making the comment submissions available to the public or entering the comment into ADAMS.
II. Introduction The NRC is considering the issuance of an order under § 50.80 of title 10 of the Code of Federal Regulations (10 CFR) and 10 CFR 72.50 approving the direct and indirect transfers of control of Pilgrim Renewed Facility Operating License No. DPR-35 as well as the general license for Pilgrim ISFSI, currently held by ENOI. Specifically, the application, dated November 16, 2018 (ADAMS Accession No. ML18320A031), requests the indirect transfer of control of the licenses from ENOI to Holtec and the direct transfer of ENOIs operating authority of Pilgrim to HDI. In addition, ENGC would be renamed Holtec Pilgrim, LLC. The NRC is also considering amending the renewed facility operating license for administrative purposes to reflect the proposed transfer.
Following approval of the proposed direct and indirect transfers of control of the licenses, Holtec Pilgrim, LLC would be the licensed owner and HDI will be the licensed operator of the Pilgrim facility.
No physical changes to Pilgrim and the Pilgrim ISFSI or operational changes are being proposed in the application.
The NRCs regulations at 10 CFR 50.80 state that no license, or any right thereunder, shall be transferred, directly or indirectly, through transfer of control of the license, unless the Commission gives its consent in writing. The Commission will approve an application for the direct and indirect transfers of a license if the Commission determines that the proposed transferee is qualified to hold the license, and that the transfer is otherwise consistent with applicable provisions of law, regulations, and orders issued by the Commission.
Before issuance of the proposed conforming license amendment, the Commission will have made findings required by the Atomic Energy Act of 1954, as amended (the Act), and the Commissions regulations. As provided in 10 CFR 2.1315, unless otherwise determined by the Commission with regard to a specific application, the Commission has determined that any amendment to the license of a utilization facility or to the license of an ISFSI, which does no more than conform the license to reflect the transfer action involves no significant hazards consideration. No contrary determination has been made with respect to this specific license amendment application. In light of the generic determination reflected in 10 CFR 2.1315, no public comments with respect to significant hazards considerations are being solicited, notwithstanding the general comment procedures contained in 10 CFR 50.91.
III. Opportunity To Comment Within 30 days from the date of publication of this notice, persons may submit written comments regarding the license transfer application, as provided for in 10 CFR 2.1305. The Commission will consider and, if appropriate, respond to these comments, but such comments will not otherwise constitute part of the decisional record. Comments should be submitted as described in the ADDRESSES section of this document.
In addition, the NRC staff will be participating in a public meeting on January 15, 2019, at the Hotel 1620 Plymouth Harbor, 180 Water Street, Plymouth, Massachusetts 02360, between 6:00 p.m. and 9:00 p.m. The agenda for the meeting will be posted on the NRC public website. The NRC will take public oral or written comments on the application for the proposed license transfer and the associated proposed updated Post-Shutdown Decommissioning Activities Report (PSDAR). The meeting will be transcribed and will include (1) presentations by HDI and ENOI, and (2) presentations by the NRC. To be considered, comments must be provided either at the transcribed public meeting or submitted by the comment deadline identified in the DATES section of this document. For additional information regarding the meeting, see the NRCs Public Meeting Schedule website at http://meetings.nrc.gov/pmns/mtg. The agenda will be posted no later than 10 days prior to the meeting.
IV. Opportunity To Request a Hearing and Petition for Leave To Intervene Within 20 days after the date of publication of this notice, any persons (petitioner) whose interest may be affected by this action may file a request for a hearing and petition for leave to intervene (petition) with respect to the action. Petitions shall be filed in accordance with the Commissions Agency Rules of Practice and Procedure in 10 CFR part 2. Interested persons should consult a current copy of 10 CFR 2.309. The NRCs regulations are accessible electronically from the NRC Library on the NRCs website at http://www.nrc.gov/reading-rm/doc-collections/cfr/. Alternatively, a copy of the regulations is available at the NRCs Public Document Room, located at One White Flint North, Room O1-F21, 11555 Rockville Pike (First Floor), Rockville, Maryland 20852. If a petition is filed, the Commission or a presiding officer will rule on the petition and, if appropriate, a notice of a hearing will be issued.
As required by 10 CFR 2.309(d) the petition should specifically explain the reasons why intervention should be permitted with particular reference to the following general requirements for standing: (1) The name, address, and telephone number of the petitioner; (2) the nature of the petitioners right under the Act to be made a party to the proceeding; (3) the nature and extent of the petitioners property, financial, or other interest in the proceeding; and (4) the possible effect of any decision or order which may be entered in the proceeding on the petitioners interest.
In accordance with 10 CFR 2.309(f),
the petition must also set forth the specific contentions which the petitioner seeks to have litigated in the proceeding. Each contention must consist of a specific statement of the issue of law or fact to be raised or controverted. In addition, the petitioner must provide a brief explanation of the bases for the contention and a concise statement of the alleged facts or expert opinion which support the contention and on which the petitioner intends to rely in proving the contention at the hearing. The petitioner must also VerDate Sep<11>2014 20:21 Jan 30, 2019 Jkt 247001 PO 00000 Frm 00172 Fmt 4703 Sfmt 4703 E:\\FR\\FM\\31JAN1.SGM 31JAN1 amozie on DSK3GDR082PROD with NOTICES1
818 Federal Register / Vol. 84, No. 21 / Thursday, January 31, 2019 / Notices provide references to the specific sources and documents on which the petitioner intends to rely to support its position on the issue. The petition must include sufficient information to show that a genuine dispute exists with the applicant or licensee on a material issue of law or fact. Contentions must be limited to matters within the scope of the proceeding. The contention must be one which, if proven, would entitle the petitioner to relief. A petitioner who fails to satisfy the requirements at 10 CFR 2.309(f) with respect to at least one contention will not be permitted to participate as a party.
Those permitted to intervene become parties to the proceeding, subject to any limitations in the order granting leave to intervene. Parties have the opportunity to participate fully in the conduct of the hearing with respect to resolution of that partys admitted contentions, including the opportunity to present evidence, consistent with the NRCs regulations, policies, and procedures.
Petitions must be filed no later than 20 days from the date of publication of this notice. Petitions and motions for leave to file new or amended contentions that are filed after the deadline will not be entertained absent a determination by the presiding officer that the filing demonstrates good cause by satisfying the three factors in 10 CFR 2.309(c)(1)(i) through (iii). The petition must be filed in accordance with the filing instructions in the Electronic Submissions (E-Filing) section of this document.
If a hearing is requested, and the Commission has not made a final determination on the issue of no significant hazards consideration, the Commission will make a final determination on the issue of no significant hazards consideration. The final determination will serve to establish when the hearing is held. If the final determination is that the amendment request involves no significant hazards consideration, the Commission may issue the amendment and make it immediately effective, notwithstanding the request for a hearing. Any hearing would take place after issuance of the amendment. If the final determination is that the amendment request involves a significant hazards consideration, then any hearing held would take place before the issuance of the amendment unless the Commission finds an imminent danger to the health or safety of the public, in which case it will issue an appropriate order or rule under 10 CFR part 2.
A State, local governmental body, Federally-recognized Indian Tribe, or agency thereof, may submit a petition to the Commission to participate as a party under 10 CFR 2.309(h)(1). The petition should state the nature and extent of the petitioners interest in the proceeding.
The petition should be submitted to the Commission no later than 20 days from the date of publication of this notice.
The petition must be filed in accordance with the filing instructions in the Electronic Submissions (E-Filing) section of this document, and should meet the requirements for petitions set forth in this section. Alternatively, a State, local governmental body, Federally-recognized Indian Tribe, or agency thereof may participate as a non-party under 10 CFR 2.315(c).
If a hearing is granted, any person who is not a party to the proceeding and is not affiliated with or represented by a party may, at the discretion of the presiding officer, be permitted to make a limited appearance pursuant to the provisions of 10 CFR 2.315(a). A person making a limited appearance may make an oral or written statement of his or her position on the issues but may not otherwise participate in the proceeding.
A limited appearance may be made at any session of the hearing or at any prehearing conference, subject to the limits and conditions as may be imposed by the presiding officer. Details regarding the opportunity to make a limited appearance will be provided by the presiding officer if such sessions are scheduled.
V. Electronic Submissions (E-Filing)
All documents filed in NRC adjudicatory proceedings, including a request for hearing and petition for leave to intervene (petition), any motion or other document filed in the proceeding prior to the submission of a request for hearing or petition to intervene, and documents filed by interested governmental entities that request to participate under 10 CFR 2.315(c), must be filed in accordance with the NRCs E-Filing rule (72 FR 49139; August 28, 2007, as amended at 77 FR 46562; August 3, 2012). The E-Filing process requires participants to submit and serve all adjudicatory documents over the internet, or in some cases to mail copies on electronic storage media. Detailed guidance on making electronic submissions may be found in the Guidance for Electronic Submissions to the NRC and on the NRC website at http://www.nrc.gov/site-help/
e-submittals.html. Participants may not submit paper copies of their filings unless they seek an exemption in accordance with the procedures described below.
To comply with the procedural requirements of E-Filing, at least 10 days prior to the filing deadline, the participant should contact the Office of the Secretary by email at hearing.docket@nrc.gov, or by telephone at 301-415-1677, to (1) request a digital identification (ID) certificate, which allows the participant (or its counsel or representative) to digitally sign submissions and access the E-Filing system for any proceeding in which it is participating; and (2) advise the Secretary that the participant will be submitting a petition or other adjudicatory document (even in instances in which the participant, or its counsel or representative, already holds an NRC-issued digital ID certificate).
Based upon this information, the Secretary will establish an electronic docket for the hearing in this proceeding if the Secretary has not already established an electronic docket.
Information about applying for a digital ID certificate is available on the NRCs public website at http://
www.nrc.gov/site-help/e-submittals/
getting-started.html. Once a participant has obtained a digital ID certificate and a docket has been created, the participant can then submit adjudicatory documents. Submissions must be in Portable Document Format (PDF). Additional guidance on PDF submissions is available on the NRCs public website at http://www.nrc.gov/
site-help/electronic-sub-ref-mat.html. A filing is considered complete at the time the document is submitted through the NRCs E-Filing system. To be timely, an electronic filing must be submitted to the E-Filing system no later than 11:59 p.m. Eastern Time on the due date.
Upon receipt of a transmission, the E-Filing system time-stamps the document and sends the submitter an email notice confirming receipt of the document. The E-Filing system also distributes an email notice that provides access to the document to the NRCs Office of the General Counsel and any others who have advised the Office of the Secretary that they wish to participate in the proceeding, so that the filer need not serve the document on those participants separately. Therefore, applicants and other participants (or their counsel or representative) must apply for and receive a digital ID certificate before adjudicatory documents are filed so that they can obtain access to the documents via the E-Filing system.
A person filing electronically using the NRCs adjudicatory E-Filing system may seek assistance by contacting the NRCs Electronic Filing Help Desk through the Contact Us link located VerDate Sep<11>2014 20:21 Jan 30, 2019 Jkt 247001 PO 00000 Frm 00173 Fmt 4703 Sfmt 4703 E:\\FR\\FM\\31JAN1.SGM 31JAN1 amozie on DSK3GDR082PROD with NOTICES1
819 Federal Register / Vol. 84, No. 21 / Thursday, January 31, 2019 / Notices on the NRCs public website at http://
www.nrc.gov/site-help/e-submittals.html, by email to MSHD.Resource@nrc.gov, or by a toll-free call at 1-866-672-7640. The NRC Electronic Filing Help Desk is available between 9 a.m. and 6 p.m., Eastern Time, Monday through Friday, excluding government holidays.
Participants who believe that they have a good cause for not submitting documents electronically must file an exemption request, in accordance with 10 CFR 2.302(g), with their initial paper filing stating why there is good cause for not filing electronically and requesting authorization to continue to submit documents in paper format. Such filings must be submitted by: (1) First class mail addressed to the Office of the Secretary of the Commission, U.S.
Nuclear Regulatory Commission, Washington, DC 20555-0001, Attention:
Rulemaking and Adjudications Staff; or (2) courier, express mail, or expedited delivery service to the Office of the Secretary, 11555 Rockville Pike, Rockville, Maryland 20852, Attention:
Rulemaking and Adjudications Staff.
Participants filing adjudicatory documents in this manner are responsible for serving the document on all other participants. Filing is considered complete by first-class mail as of the time of deposit in the mail, or by courier, express mail, or expedited delivery service upon depositing the document with the provider of the service. A presiding officer, having granted an exemption request from using E-Filing, may require a participant or party to use E-Filing if the presiding officer subsequently determines that the reason for granting the exemption from use of E-Filing no longer exists.
Documents submitted in adjudicatory proceedings will appear in the NRCs electronic hearing docket which is available to the public at https://
adams.nrc.gov/ehd, unless excluded pursuant to an order of the Commission or the presiding officer. If you do not have an NRC-issued digital ID certificate as described above, click cancel when the link requests certificates and you will be automatically directed to the NRCs electronic hearing dockets where you will be able to access any publicly available documents in a particular hearing docket. Participants are requested not to include personal privacy information, such as social security numbers, home addresses, or personal phone numbers in their filings, unless an NRC regulation or other law requires submission of such information. For example, in some instances, individuals provide home addresses in order to demonstrate proximity to a facility or site. With respect to copyrighted works, except for limited excerpts that serve the purpose of the adjudicatory filings and would constitute a Fair Use application, participants are requested not to include copyrighted materials in their submission.
The Commission will issue a notice or order granting or denying a hearing request or intervention petition, designating the issues for any hearing that will be held and designating the Presiding Officer. A notice granting a hearing will be published in the Federal Register and served on the parties to the hearing.
For further details with respect to this application, see the application dated November 16, 2018 (ADAMS Accession No. ML18320A031, as supplemented on November 16, 2018 (ADAMS Accession No. ML18320A040).
V. Access to Sensitive Unclassified Non-Safeguards Information for Contention Preparation Any person who desires access to proprietary, confidential commercial information that has been redacted from the application should contact the applicant by telephoning Susan H.
Raimo, Entergy Services, LLC, at 202-530-7330 for the purpose of negotiating a confidentiality agreement or a proposed protective order with the applicant. If no agreement can be reached, persons who desire access to this information may file a motion with the Secretary and addressed to the Commission that requests the issuance of a protective order.
Dated at Rockville, Maryland, this 2nd day of January 2019.
For the Nuclear Regulatory Commission.
John G. Lamb, Senior Project Manager, Special Projects and Process Branch, Division of Operating Reactor Licensing, Office of Nuclear Reactor Regulation.
[FR Doc. 2019-00371 Filed 1-30-19; 8:45 am]
BILLING CODE 7590-01-P NUCLEAR REGULATORY COMMISSION
[NRC-2019-0001]
Sunshine Act Meetings TIME AND DATE: Weeks of January 21, 28, February 4, 11, 18, 25, 2019.
PLACE: Commissioners Conference Room, 11555 Rockville Pike, Rockville, Maryland.
STATUS: Public and Closed.
MATTERS TO BE CONSIDERED:
Week of January 21, 2019 Thursday, January 24, 2019 9:55 a.m.Affirmation Session (Public Meeting) (Tentative), Draft Final RuleMitigation of Beyond-Design-Basis Events (Tentative)
This meeting will be webcast live at the Web addresshttp://www.nrc.gov/.
10:00 a.m.Strategic Programmatic Overview of the New Reactors Business Line (Public Meeting),
(Contact: Donna Williams: 301-415-1322)
This meeting will be webcast live at the Web addresshttp://www.nrc.gov/.
Week of January 28, 2019Tentative Monday, January 28, 2019 1:30 p.m.NRC All Employees Meeting (Public Meeting), Marriott Bethesda North Hotel, 5701 Marinelli Road, Rockville, MD 20852 Week of February 4, 2019Tentative There are no meetings scheduled for the week of February 4, 2019.
Week of February 11, 2019Tentative There are no meetings scheduled for the week of February 11, 2019.
Week of February 18, 2019Tentative There are no meetings scheduled for the week of February 18, 2019.
Week of February 25, 2019Tentative There are no meetings scheduled for the week of February 25, 2019.
ADDITIONAL INFORMATION: The meeting scheduled on January 31, 2019 at 9:00 a.m., Transformation at the NRC:
Innovation, has been postponed.
CONTACT PERSON FOR MORE INFORMATION:
For more information or to verify the status of meetings, contact Denise McGovern at 301-415-0681 or via email at Denise.McGovern@nrc.gov. The schedule for Commission meetings is subject to change on short notice.
The NRC Commission Meeting Schedule can be found on the internet at: http://www.nrc.gov/public-involve/
public-meetings/schedule.html.
The NRC provides reasonable accommodation to individuals with disabilities where appropriate. If you need a reasonable accommodation to participate in these public meetings, or need this meeting notice or the transcript or other information from the public meetings in another format (e.g.,
braille, large print), please notify Kimberly Meyer-Chambers, NRC Disability Program Manager, at 301-287-0739, by videophone at 240-428-3217, or by email at Kimberly.Meyer-Chambers@nrc.gov. Determinations on VerDate Sep<11>2014 20:21 Jan 30, 2019 Jkt 247001 PO 00000 Frm 00174 Fmt 4703 Sfmt 4703 E:\\FR\\FM\\31JAN1.SGM 31JAN1 amozie on DSK3GDR082PROD with NOTICES1